Addressing PAD Protocol Detectors & Modules
All PAD detectors’ and modules’ addresses are set by changing the dip switches located on each device. An address must be set prior to connection.
PAD Addresses
PAD addresses are comprised of a seven (7) position dip switch used to program each device with an address ranging from 1–127. Refer to the table below to set dip switches on any PAD detector or module.
Catetan: unggal “gray” box indicates that the dip switch is "Dina," sareng masing-masing “white” box nunjukkeun “Pareumeun.”
Anu baheulaamples ditémbongkeun di handap ngagambarkeun setelan dip switch alat PAD urang: nu 1st example nembongkeun alat teu kajawab dimana sakabeh setelan dip switch dina standar "Pareum" posisi, 2nd illustrates hiji alat PAD kajawab via setélan switch dip.
- All dip switches are set to the default “OFF” position. (Device Not Addressed)
- Dip switches set for address 42. Switches #2, 8, & 32 are “ON”. (2+8+32=42)
- Dip switches set for address 90. Switches #2, 8, 16 & 64 are “ON”. (2+8+16+64=90)