All PAD detectors’ and modules’ addresses are set by changing the dip switches located on each device. An address must be set prior to connection.

PAD Addresses 

PAD addresses are comprised of a seven (7) position dip switch used to program each device with an address ranging from 1–127. Refer to the table below to set dip switches on any PAD detector or module.

Catetan: unggal “gray” box indicates that the dip switch is "Dina," sareng masing-masing “white” box nunjukkeun “Pareumeun.”
PAD Addresses

Anu baheulaamples ditémbongkeun di handap ngagambarkeun setelan dip switch alat PAD urang: nu 1st example nembongkeun alat teu kajawab dimana sakabeh setelan dip switch dina standar "Pareum" posisi, 2nd illustrates hiji alat PAD kajawab via setélan switch dip.

  • All dip switches are set to the default “OFF” position. (Device Not Addressed)
    Switches Instruction
  • Dip switches set for address 42. Switches #2, 8, & 32 are “ON”. (2+8+32=42)
    Switches Instruction
  • Dip switches set for address 90. Switches #2, 8, 16 & 64 are “ON”. (2+8+16+64=90)
    Switches Instruction

Pangrojong Costumer

Potter Electric Signal Company, LLC
St. Louis, MO
telepon: 800-325-3936
www.pottersignal.com

Logo Potter

Dokumén / Sumberdaya

POTTER IPA Series Alamat Detéktor jeung Modul PAD [pdf] Buku Panduan Pamilik
IPA Series Addressing PAD Detectors and Modules, IPA Series, Addressing PAD Detectors and Modules, PAD Detectors and Modules, Detectors and Modules, Modules, Detectors

Ninggalkeun comment hiji

Email alamat anjeun teu bakal dipedar. widang dibutuhkeun nu ditandaan *