Zhengzhou Winsen Electronics Technology Co., Ltd
Infrared Refrigerant Sensor Module
(Model: ZRT510)
User’s Manual Version 1.2
Issue Date. 2023.06.21
Zhengzhou Winsen Electronics Technology Co., Ltd
ISO9001 Certificated Company
Statement
This manual’s copyright belongs to Zhengzhou Winsen Electronics Technology Co., LTD. Without the written permission, any part of this manual shall not be copied, translated, stored in database or retrieval system, also can’t spread through electronic, copying, record ways.
Thanks for purchasing our product. In order to let customers use it better and reduce the faults caused by misuse, please read the manual carefully and operate it correctly in accordance with the instructions. If users disobey the terms or remove, disassemble, change the components inside of the sensor, we shall not be responsible for the loss.
The specific such as color, appearance, sizes &etc., please in kind prevail.
We are devoting ourselves to products development and technical innovation, so we reserve the right to improve the products without notice. Please confirm it is the valid version before using this manual. At the same time, users’ comments on optimized using way are welcome.
Please keep the manual properly, in order to get help if you have questions during the usage in the future.
Zhengzhou Winsen Electronics Technology CO., LTD.
ZRT510 Refrigerant Sensor Module
Profile
ZRT510 refrigerant sensor module is a smart infrared type sensor module, using non-dispersive infrared (NDIR) principle to detect the existence of refrigerant, with good selectivity and non-oxygen dependent. It is a compact high performance sensor module made by combining mature infrared gas detection technology with micro machining and sophisticated circuit design. It is easy to use with excellent performance.
Main Features
*High sensitivity, high resolution, fast response
*RS485 communication
*Temperate compensation, excellent linear output, good stability, long lifespan
*Self-heating function, anti-water vapor interference, anti-poisoning, direct replacement for catalytic sensors
Main applications
*HVAC
*Industrial process and safety monitoring
Main parameters
Table1.
Model No. | ZRT510 |
Detection Gas | R454B(R32 or R290 can be customized) |
Working voltage | 5±0. 1 V DC, ripple<50mV |
Average current | < 60mA (without opening the heating function) |
Peak current | < 300mA |
Interface mode | XHQ-4 |
Communication mode | RS485(UART or PWM can be customized) |
Data update | 1s |
Preheat time | < 30s |
Response Time | Under 25% LFL environment, the time reaching alarm point (7% LFL) is less than 10 seconds |
Working T&H | -40~80 ℃, 0~100% RH |
Storage T&H | -40~60 ℃, 0~100% RH |
Sizes | 75.4*57*21.5 mm (without connecting cable) |
Weight | 32.5g (without connecting cable) |
Lifespan | > 15 years |
Certification | UL 60335-2-40 : 2022 & IEC 60335-2-40 : 2022 |
Resolution
Table2.
Detection Gas | Detection Range | Resolution | Accuracy |
R32 | 0~50% LFL | 1% LFL | 1.±2.5%LFL (-20-60℃, 0-95%RH) 2.±5.0%LFL (Others) |
Dimensions
- 1 5V
- 2 GND
- 3 485B
- 4 485A
- 5 Reserved
- Interposing terminal: SUMITOMO6189-10 46
Fig1.sensor module size
Pin Definition:
Table3.
Pin | Pin Definition | ![]() Fig2. Sensor Module Pins |
Pin 1 | VCC | |
Pin 2 | GND | |
Pin 3 | RS485-B | |
Pin 4 | RS485-A | |
Pin 5 | Reserved |
Communication protocol:
ZRT510 module is RS485 communication, communication protocol and data format are as follows:
1. Communication settings:
Table4. Communication settings
Physical Layer | RS485 |
Software Protocol Type | Modbus RTU |
Data Byte Order | High byte first |
CRC byte order | Low byte first |
Data frame | Start bit: 1 bit Data bit: 8 bits Stop bit: 2 bits No parity |
Baud rate | 2400bps |
Modbus address | 0x01 (default) |
Supported Function Codes | 0x03 (Read multiple holding registers) 0x06 (write single register) |
Supported Exception Codes | 0x01 (Illegal function) 0x02 (illegal address) 0x03 (Illegal data value) 0x04 (server-side device fault) |
2. Register definition:
Table5. Register Definition Table
Access Type | Name | Register Address | No. of Registers | Data Type | Description |
Read | Register Specification Version | 0x0100 | 1 | [uint8, uint8] | Protocol specification version, the high byte is the major version number and the low byte is the minor version number. |
Write | Device Reset | 0x0101 | 1 | bool | The sensor will be reset by writing 1 to the register. |
Data Search | |||||
Read | Operation mode | 0x0110 | 1 | enum | Operation mode of the device, no measurement values are available during startup. 0: start-up; 1: measurement in progress. |
Read | Leak signal | 0x0111 | 1 | bool | Flag that turns on when the concentration exceeds the alarm threshold. By default, the leak signal remains on for 5 minutes after the concentration falls below the leak signal threshold again. 0: No leak detected; 1: Leak is actively detected or for the duration after the leak detection. |
Read | Error Code | 0x0112 | 1 | uint16 | Refer to <6> Fault Definition Table |
Read | Gas concentration LFL | 0x0113 | 1 | int16 | The last measured gas concentration in %LFL multiplied by 10 (e.g. 250 means 25%LFL). Resolution: 1% LFL; Range: 0-100% LFL. |
Read | Sensor Module Temperature | 0x0114 | 1 | int16 | Last measured temperature in °C multiplied by 10 (e.g. 210 means 21.0 °C). Resolution: 0.1 °C; Range: -40 to 85°C. |
Read | Sensor Module Humidity | 0x0115 | 1 | int16 | Last measured humidity in %RH multiplied by 10 (e.g. 305 means 30.5%RH). Resolution: 0.1%RH; Range: 0-100%RH. |
Setting | |||||
Read / Write | Device Address | 0x0120 | 1 | uint8 | Slave address of the Modbus interface Range: 1 – 247; Default value: 1 A soft reset or power reapplication is required to apply a change to this value. |
Read | Leak signal trigger threshold | 0x0124 | 1 | uint16 | The gas concentration level that triggers the leak signal. Resolution: 0.1% LFL (e.g. 251 means 25.1% LFL) |
Read | Lifetime warning signal trigger threshold | 0x0126 | 1 | uint16 | The life count value of the trigger life warning signal in days. Resolution: 1 day; Range: 0-65535 days. |
Read | Life Alarm Signal Trigger Threshold | 0x0127 | 1 | uint16 | The life count value of the trigger life alarm signal in days. Resolution: 1 day; Range: 0-65535 days. |
Device Information | |||||
Read | Device Marking | 0x0140 | 1 | string[20] | Reads the device tag. To be set, no default value. Indicates that the string is filled with 0 and terminated without 0. |
Read | Firmware Version | 0x014A | 1 | uint8[2] | Firmware version. Format: High byte: major version; Low byte: minor version. |
Read | Gas Type | 0x014C | 1 | enum | The type of gas for which the sensor module is configured. |
Read | Life counter (days) | 0x014E | 1 | uint16 | The service life of the device in days. Resolution: 1 day; Range: 0-65535 days. Device stores timing values every 12 hours. |
Read | Life counter (hours) | 0x014F | 1 | uint16 | The value of the service life of the device is supplemented by the number of hours, which together with the integer digits form the life value. The unit is hours. Resolution: 1 hour (for example: 12 means 12 hours, if the number of life days is 100, the total life is: 100 days and 12 hours); Range: 0-23 hours. This value is updated every 1 hour. |
3. Fault definition
Table6. Fault Definition Table
Bit(0-15 from right to left) | Fault | Description |
0 | Internal errors | Errors that cause measurement data to be unavailable, such as internal communication errors. |
1 | Value exceeds limit | The sensor detects a temperature, relative humidity or gas concentration that exceeds the specified limits. |
2 | – | – |
3 | Self-test failed | Internal check for errors caused by incorrect operation, invalid settings, etc. |
4 | Sensor module failure | Unable to recover from an error that requires replacement of the sensor module. |
5 | Exceed life limit alarm | The service life limit has been reached. |
6 | Approaching life limit warning | The lifetime warning threshold has been reached. |
4. Data sending and receiving format:
Table7. Basic Format
Device Address | Function Code | Data | CRC Checksum |
1 byte | 1 byte | N byte | 2 byte |
Table8. Function Code 03 – Read Holding Register Request Format
Device Address | Function Code | Start register address high byte | Start register address low byte | Read the high byte of the number of registers | Read the low byte of the number of registers | CRC Checksum |
1 byte | 03 | 1 byte | 1 byte | 1 byte | 1 byte | 2 byte |
Table9. Function Code 03 – Read Holding Register Correct Answer Format
Device Address | Function Code | Return the number of data bytes | Register 1 data high byte | Register 1 data low byte | …… | CRC Checksum |
1 byte | 03 | 1 byte | 1 byte | 1 byte | …… | 2 byte |
Table10. Function Code 06 – Write Single Holding Register Request Format
Device Address | Function Code | Register address high byte | Register address low byte | Write value high byte | Write value low byte | CRC Checksum |
1 byte | 06 | 1 byte | 1 byte | 1 byte | 1 byte | 2 byte |
Table11. Request frame error response format
Device Address | Function Code | Exception code values | CRC Checksum |
1 byte | Request frame function code +0x80 | 1 byte | 2 byte |
* Note: CRC checksum calculation: CRC-16/MODBUS x16+x15+x2+x1
Notes:
- Please use the sensor module within requested and stable voltage. It may be damaged if the voltage is too high or not work properly if the voltage is too low.
- Please do not use the product in high T&H, strong electromagnetic or dusty environment for long time.
- Please do not impact or vibrate the module seriously.
- Please do not install the module in the severe convection environment.
Zhengzhou Winsen Electronics Technology Co., Ltd
Add: No.299, Jinsuo Road, National Hi-Tech Zone, Zhengzhou 450001 China
Tel: +86-371-67169097/67169670
Fax: +86-371-60932988
E-mail: sales@winsensor.com
Website: www.winsen-sensor.com
Tel: 86-371-67169097/67169670 Fax: 86-371-60932988 Email: sales@winsensor.com