PLC Connection Guide
Weintek Built-in CODESYS
Supported series: Weintek Built-in CODESYS HMI
HMI Setting:
Parameters | Recommended | Options | Notes |
PLC type | Weintek Built-in CODESYS | ||
PLC I/F | Ethernet |
Online simulator | NO |
- Under “MainTask” set POU PLC_PRG.
- Add “Symbol configuration” into Devices list.
- Select PLC_RPG and its tag information is shown, build the project.
[build] -> [Generate Code] - A *.xml file is generated in the directory of the project.
- In System Parameter Settings click [New] to add Weintek Built-in CODESYS driver into the device list and then click [Tag Manager].
- In Tag Manager click Get tag -> Import Tag, and then select the tag file (.xml) generated by the PLC software.
- When the tags are imported successfully, click [Exit] to leave.
Support Device Type:
Data type | EasyBuilder data format | Memo |
Bool | bit | |
Byte | 16-bit BCD, Hex, Binary, Unsigned | 8-bit |
SInt | 16-bit BCD, Hex, Binary, Signed | 8-bit |
USInt | 16-bit BCD, Hex, Binary, Unsigned | 8-bit |
Word | 16-bit BCD, Hex, Binary, Unsigned | 16-bit |
Int | 16-bit BCD, Hex, Binary, Signed | 16-bit |
UInt | 16-bit BCD, Hex, Binary, Unsigned | 16-bit |
DWord | 32-bit BCD, Hex, Binary, Unsigned | 32-bit |
DInt | 32-bit BCD, Hex, Binary, Signed | 32-bit |
Real | 32-bit Float | 32-bit |
UDInt | 32-bit BCD, Hex, Binary, Unsigned | 32-bit |
LInt | 64-bit Signed | 64-bit |
ULInt | 64-bit Unsigned | 64-bit |
LWord | 64-bit Unsigned | 64-bit |
LReal | 64-bit Float | 64-bit |
String | Word array for ASCII input and display | Length=word |
Note1: String length must be set identical to the length in Codesys software.
Note2: EBPro V6.03.02 or later supports 64 bits data type (cMT Series only), but please note that the address limit range is 48 bits in maximum.
Wiring Diagram:
Diagram 1
Ethernet cable: