TRANE Tracer VV550 Variable Air Volume Controller

Tracer VV550 Variable Air Volume Controller

Introduction

Tracer VV550 and Tracer VV551 variable air volume (VAV) controllers provide single-duct digital control for VAV boxes. They support the following VAV control sequences:

  • Space temperature control
  • Flow tracking
  • Ventilation flow control

The Tracer VV550 VAV controller is available factory-installed on Trane VariTrane VAV boxes (Figure 1).
The Tracer VV551 VAV controller is available for field installation for a variety of VAV applications (Figure 2).

Figure 1. Tracer VV550 controller

Figure 2. Tracer VV551 controller (uses same board as Tracer VV550)

Figure 2. Tracer VV551 controller
(uses same board as Tracer VV550)

Because the Tracer VV550 and Tracer VV551 VAV controllers use the same logic controller, both offer the same wide range of application and control flexibility. The Tracer VV551 VAV controller includes additional laborsaving packaging features for field installed applications.
Tracer VV550/551 VAV controllers can operate as part of a Trane Integrated Comfort™ system (ICS), as part of a building management system from another manufacturer, or as a standalone device.
When it is part of a Trane ICS, a Tracer VV550/551 VAV controller enables the building automation system (BAS) to perform functions such as scheduling, trending, alarming, remote communications, and VAV air system (VAS) coordination. The controller communicates with a Tracer Summit BAS over the LonTalk® communications link. The controller can also communicate with other building control systems that are compliant with the LonMark® Space Comfort Controller (SCC) profile
Tracer VV550/551 VAV controllers can be configured using the Rover™ service tool. They have the following inputs and outputs (Figure 3 on page 6):
Analog inputs:

  • Space temperature (10 kΩ thermistor)
  • Space setpoint (1 kΩ potentiometer)
  • Primary/discharge air temperature (10 kΩ thermistor)
  • Primary air flow Binary inputs:
  • Occupancy or generic Binary outputs:
  • Air valve close
  • Air valve open
  • Heat 1
  • Heat 2
  • Heat 3 or fan On/Off

™ ® The following are trademarks or registered trademarks of their respective companies: ICS, Rover, Tracer, Tracer Summit, and Trane of American Standard Inc.; Lon Mark, Lon Talk, and Lon Works of the Echelon Corporation.

Automatic calibration

Tracer VV550/551 VAV controllers automatically calibrate the flow transducer each time the box transitions to the unoccupied state. This eliminates the need to initiate/schedule calibration for most installations. The exception is 24/7 sites, in which case the Tracer Summit building automation system can be used to initiate/schedule calibration.

Ventilation flexibility

Tracer VV550/551 VAV controllers can manage ventilation in the following ways:

  • Fixed occupancy ventilation setpoint
  • Scheduled (or otherwise calculated) ventilation setpoint
  • Occupancy sensor to switch between normal and reduced ventilation
  • CO2 sensor for demand-controlled ventilation

This flexibility gives owners and facility managers an option to simply select one of several effective solutions for managing ventilation.

Flow tracking

Tracer VV550/551 VAV controllers can easily be applied in flow tracking applications. In a flow tracking application, supply and exhaust boxes are paired together for the purpose of maintaining either positive or negative space static pressure. This feature allows the installer to quickly define the relationship of the supply and exhaust air boxes without the need for custom programming.

Ventilation flow control with tempering

Tracer VV550/551 VAV controllers have been designed for ventilation flow control applications. These applications pair a fresh air unit or self-contained unit with ventilation boxes to provide fresh (tempered) air to a floor/area. With this feature, the installer can quickly configure the flow control boxes and set up the system without the need for custom programming.

Local versus remote reheat flexibility

Tracer VV550/551 VAV controllers can be configured to have local and/or remote heat. This configuration flexibility enables the controllers to be applied across a broad range of VAV applications.

Occupied and unoccupied operation

The occupancy input on a Tracer VV550/ 551 VAV controller works with a motion (occupancy) sensor or a time clock to determine the occupancy mode. An occupancy request can also be communicated from a building automation system to determine the mode of the controller. Whether standalone or combined with a communicated occupancy request, a Tracer VV550/551 controller can be used with an occupancy sensor to save energy whenever a space is vacant.

Timed override

The timed override function for afterhours operation allows users to request unit operation by the touch of a button on the unit zone sensor. Additionally, users can press the CANCEL button at any time to place the unit back into unoccupied mode. This occupancy feature minimizes energy use by running the system only as scheduled or as demanded after hours.

Service pin from the Trane zone sensor

Certain installation scenarios require access to the SERVICE button on the controller. Access to this button typically requires a ladder or a lift. The Tracer VV550/551 VAV controller allows a technician to replicate pressing the SERVICE button by pressing the zone sensor ON button. This feature eliminates the need for accessing the SERVICE button, saving the technician time and energy.

Auto-commissioning sequence

Tracer VV550/551 VAV controllers provide an automatic commissioning sequence. With a discharge air temperature sensor installed, this feature exercises the air valve, fan, and heat in the box and records the discharge air temperature before and after the action. This allows the installer to easily checkout the operation of the box and commission by exception. The data from this test is retained in the controller for immediate reports or retrieval at a later date (for comparison purposes).

Manual test function

A Tracer VV550/551 VAV controller includes a manual test button, which enables a technician to easily exercise the outputs of the controller. On consecutive button presses, the controller steps through a predefined sequence that exercises all of the controller outputs.

Drive minimum and maximum from zone sensor

When applied with a Trane zone sensor module that includes a thumbwheel setpoint, a Tracer VAV VV550/551 controller can easily be overridden to minimum and maximum flow. By simply turning the thumbwheel to , the controller drives the air valve to the minimum cooling flow setpoint. Similarly, turning the thumbwheel to drives the air valve to the maximum cooling flow setpoint. This simple override feature is most useful during the checkout and balancing phases of a project.

Trane controller compatibility

Tracer VV550/551 VAV controllers are compatible with the latest generation of Trane control products. The controllers communicate over a LonTalk® communications link. This allows Tracer VV550/551 VAV controllers to exist on the same communication wire as other Trane controllers and to share data with them as required.

Interoperability

Tracer VV550/551 VAV controllers are designed with LonWorks® technology and are LonMark® certified. They follow the guidelines of the LonMark® Space Comfort Controller (SCC) profile. As such, the Tracer VV550/551 controllers enable control system integration flexibility.

Wiring diagram

See Figure 3 on page 6.

Wiring diagram for Tracer VV550/551 VAV controllers

Figure 3. Tracer VV550/551 wiring diagram

Figure 3. Tracer VV550/551 wiring diagram

Network architecture

Tracer VV550/551 VAV controllers can operate on a Tracer Summit BAS, on a building management system from another manufacturer, on a peer-to-peer network, or as stand-alone devices. The Rover service tool can configure the controllers at any accessible location on the Lon Talk® communication link (Figure 4).

Figure 4. Network architecture with Tracer VV551 VAV controllers

Figure 4. Network architecture with Tracer VV551 VAV controllers

Zone sensor options

Zone sensors are available in a variety of configurations. Table 1 describes the features of the five Trane zone sensors that are available for use with Tracer VV550/551 VAV controllers. The same five sensors are shown in Figure 5.
Contact your Trane sales office about other compatible zone sensors.
Table 1. Zone sensors for use with Tracer VV550/551

GCC order number

ZoneTimed override buttonsLCD

Comm jack

Setpoint thumbwheel

Temperature sensorON

CANCEL

4190 1087

 x   x
4190 1088 xxx 

x

4190 1090

xxxx x
4190 1094xx   

x

4190 1120

xxxxx

x

Figure 5. Zone sensors for use with Tracer VV550/551

Figure 5. Zone sensors for use with Tracer VV550/551

Dimensions and specifications

Power requirements

Supply: 18–32 Vac (24 Vac nominal) at 50/60 Hz

Operating environment

Temperature: 32 to 140°F (0 to 60°C)
Relative humidity: From 5 to 95% non-condensing

Storage environment

Temperature: -40 to 185°F (-40 to 85°C)
Relative humidity: From 5 to 95% non-condensing

Dimensions

(See Figure 6 on page 10.)
Board only
Height: 4.5 in. (11.4 cm)
Width: 5.5 in. (13.8 cm)
Depth: 2 in. (5.1 cm)
With enclosure (VV551)
Height: 7.5 in. (13.7 cm)
Width: 6.5 in. (16.7 cm)
Depth: 5.5 in. (14.0 cm)

Weight with enclosure (Tracer VV551)

With no actuator: 3.9 lb (1.77 kg)
With Belimo actuator: 5.0 lb (2.27 kg)
With Trane actuator: 5.2 lb (2.36 kg)

Analog inputs

Space temperature; thermistor:
10 kΩ@ 77°F (25°C) From 14 to 122°F (-10 to 50°C)
Space setpoint; potentiometer: 1 kΩ
From 50 to 90°F (-10 to 32.2°C) Primary/discharge air temperature; thermistor: 10 kΩ@ 77°F (25°C)
From -40 to 212°F (-40 to 100°C)
Primary air flow; pressure transducer: From 0 to 2 in. water (0 to 498 Pa)

Binary input

Occupancy or generic (dry contact)

Binary outputs

Air valve close: maximum output rating: 12 VA
Air valve open: maximum output rating: 12 VA
Heat stage 1: maximum output rating: 12 VA
Heat stage 2: maximum output rating: 12 VA
Heat stage 3/Fan on/off: maximum output rating: 12 VA

Agency listings/compliance

Tracer VV550:
UL 873 and CSA C22.2 No. 24-93: Temperature Indicating and Regulating Equipment
Tracer VV551:
UL and C-UL 916, Energy management equipment
UL 94-5V (UL flammability rating for plenum use) FCC Part 15, Class A

Figure 6. Tracer VV551 dimensions

Figure 6. Tracer VV551 dimensions
Figure 6. Tracer VV551 dimensions

Data lists

Table 2 provides an input/output listing for Tracer VV550/551 VAV controllers.
Table 3 provides the configuration properties for the controller. The content of the lists conforms to both the Lon Mark® SCC functional profile 8500 and the Lon Mark® node object.

Table 2. Input/output listing

Input descriptionInputSNVT type
Space temperaturenviSpaceTempSNVT_temp_p
SetpointnviSetpointSNVT_temp_p
Occupancy, schedulenviOccScheduleSNVT_tod_event
Occupancy, manual commandnviOccManCmdSNVT_occupancy
Occupancy sensornviOccSensorSNVT_occupancy
Application modenviApplicModeSNVT_hvac_mode
Heat/cool mode inputnviHeatCoolSNVT_hvac_mode
Fan speed commandnviFanSpeedCmdSNVT_switch
Auxiliary heat enablenviAuxHeatEnableSNVT_switch
Valve overridenviValveOverrideSNVT_hvac_overid
Flow overridenviFlowOverrideSNVT_hvac_overid
Emergency overridenviEmergOverrideSNVT_hvac_emerg
Source temperaturenviSourceTempSNVT_temp_p
Space CO2nviSpaceCO2SNVT_ppm
Clear alarms/ diagnosticsnviRequest*SNVT_obj_request
Air flow setpoint inputnviAirFlowSetptSNVT_flow
Ventilation ratio limitnviVentRatioLimSNVT_temp_p
Ventilation for the zone inputnviVentSetptSNVT_flow
* Part of the node object.
Output descriptionOutputSNVT type
Space temperaturenvoSpaceTempSNVT_temp_p
Unit status, modenvoUnitStatusSNVT_hvac_status
Effective setpointnvoEffectSetptSNVT_temp_p
Effective occupancynvoEffectOccupSNVT_occupancy
Heat cool modenvoHeatCoolSNVT_hvac_mode
SetpointnvoSetpointSNVT_temp_p
Discharge air temperaturenvoDischAirTempSNVT_temp_p
Terminal loadnvoTerminalLoadSNVT_lev_percent
Space CO2nvoSpaceCO2SNVT_ppm
Effective air flow setpointnvoEffectFlowSPSNVT_flow
Air flownvoAirFlowSNVT_flow
File table addressnvoFileDirectory*SNVT_address
Object statusnvoStatus*SNVT_obj_status
Alarm messagenvoAlarm MessageSNVT_str_asc
* Part of the node object.

Table 3. Configuration properties

Configuration property descriptionConfiguration propertySNVT typeSCPT reference
Send heartbeatnciSndHrtBtSNVT_time_secSCPTmaxSendTime (49)
Occ temperature setpointsnciSetpointsSNVT_temp_setptSCPTsetPnts (60)
Minimum send timenciMinOutTmSNVT_time_secSCPTminSendTime (52)
Receive heartbeatnciRecHrtBtSNVT_time_secSCPTmaxRcvTime (48)
Location labelnciLocationSNVT_str_ascSCPT location (17)
Local bypass timenciBypassTimeSNVT_time_minSCPT bypass Time (34)
Manual override timenciManualTimeSNVT_time_minSCPT manOverTime (35)
Space CO2 limitnciSpaceCO2LimSNVT_ppmSCPTlimitCO2 (42)
Nominal air flownciNomFlowSNVT_flowSCPTnomAirFlow (57)
Air flow measurement gainnciFlowGainSNVT_multiplierSCPTsensConstVAV (67)
Minimum air flownciMinFlowSNVT_flowSCPTminFlow (54)
Maximum air flownciMaxFlowSNVT_flowSCPTmaxFlow (51)
Minimum air flow for heatnciMinFlowHeatSNVT_flowSCPTminFlowHeat (55)
Maximum air flow for heatnciMaxFlowHeatSNVT_flowSCPTmaxFlowHeat (37)
Minimum flow for standbynciMinFlowStdbySNVT_flowSCPTminFlowStby (56)
Firmware major versionnciDevMajVer*n/aSCPTdevMajVer (165)
Firmware minor versionnciDevMinVer*n/aSCPTdevMinVer (166)
Flow offset for tracking applicationsnciFlowOffsetSNVT_flow_fSCPToffsetFlow (265)
Local heating minimum air flownciMinFlowUnitHtSNVT_flowSCPTminFlowUnitHeat (270)
* Part of the node object.

Customer Support

Trane
A business of American Standard Companies www.trane.com
For more information, contact your local Trane office or e-mail us at comfort@trane.com
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
firealarmresources.com

TRANE -Logo

Documents / Resources

TRANE Tracer VV550 Variable Air Volume Controller [pdf] Instruction Manual
VV551, VV550, Tracer VV550 Variable Air Volume Controller, Tracer VV550, Variable Air Volume Controller, Air Volume Controller, Controller

References

Leave a comment

Your email address will not be published. Required fields are marked *