SONBEST SR3688B 4-Channel Wind Speed and Direction Recorder

SONBEST SR3688B 4-Channel Wind Speed and Direction Recorder Product Image

SR3688B using the standard RS485 bus MODBUS-RTU protocol, easy access to PLC,DCS and other instruments or systems for monitoring wind speed, conductivity state quantities. The internal use of high-precision sensing core and related devices to ensure high reliability and excellent long-term stability, can be customized RS232,RS485,CAN,4-20mA,DC0~5V\10V,ZIGBEE,Lora,WIFI,GPRS and other output methods.

Technical Parameters

Technical parameterParameter value
BrandSONBEST
Wind speed range0~30m/s
Start wind0.2m/s
Wind speed accuracy±3%
Shell materialaluminum
Wind direction range0~360°
Wind direction resolution22.5°
Communication InterfaceRS485
PowerDC12~24V 1A
Running temperature-40~80°C
Working humidity5%RH~90%RH

Product Size

Product Size

How to Wiring?

How to Wiring

Application Solution

Application Solution

  • Single Module Application Scheme
    Single Module Application Scheme
  • Multi Module Application Scheme
    Multi Module Application Scheme
  • External Battery Usage Plan
    External Battery Usage Plan

Key Position & Screen Display Description

Key Position and Screen Display Description

 

Key Position and Screen Display Description 02

  1. Upload interval display, up to 100 seconds can be set.
    This item is set by SET.
  2. When the key is pressed “Enter Key” , when the icon becomes “”, the timing will stop on the left.
    When the key is pressed “Enter Key” , when the icon becomes “Play Symbol”, the left side starts timing.
  3. Number of records: The number of records will be increased once at the end of the countdown on the left.

Press “SET” to enter the clock setting ”Enter Key” Use to shift and adjust the value up and down.

Key Position and Screen Display Description 03

Press “SET” a second time to enter the storage interval setting.
The upper limit can be set to 100 seconds/time.

Key Position and Screen Display Description 04

Press the third “SET” to enter the record start point setting.
The upper limit can be set to more than 60,000.

Key Position and Screen Display Description 05

How to Use?

16-DIMENSIONAL MAP OF WIND DIRECTION

How to Use

 

Communication Protocol

Communication Protocol

The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device is shipped, the default baud rate is 9600, 8, n, 1

  1. Read Data (Function id 0x03)
    Inquiry frame (hexadecimal), sending example: Query 1# device 1 data, the host computer sends the command:01 03 00 00 00 02 C4 0B.
    Device IDFunction idStart AddressData LengthCRC16
    010300 0000 02C4 0B

    For the correct query frame, the device will respond with data:01 03 04 00 7A 00 00 DB EA , the response format is parsed as follows:

    Device IDFunction idData LengthData 1Data 2Check Code
    01030400 7900 7ADB EA

    Data Description: The data in the command is hexadecimal. Take data 1 as an example. 00 79 is converted to a decimal value of 121. If the data magnification is 100, the actual value is 121/100=1.21. Others and so on.

  2. Data Address Table
    AddressStart AddressDescriptionData typeValue range
    4000100 00wind speedRead Only0~65535
    4000200 01conductivityRead Only0~65535
    4010100 64model coderead/write0~65535
    4010200 65total pointsread/write1~20
    4010300 66Device IDread/write1~249
    4010400 67baud rateread/write0~6
    4010500 68moderead/write1~4
    4010600 69protocolread/write1~10

     

  3. Read and Modify Device Address
    1. Read or query device address
      If you don’t know the current device address and there is only one device on the bus, you can us e the command FA 03 00 64 00 02 90 5F Query device address.
      Device IDFunction idStart AddressData LengthCRC16
      FA0300 6400 0290 5F

      FA is 250 for the general address. When you don’t know the address, you can use 250 to get the real device address, 00 64 is the device model register.
      For the correct query command, the device will respond, for example the response data is: 01 03 02 07 12 3A 79, the format of which is as shown in the following table:

      Device IDFunction idStart AddressModel CodeCRC16
      01030255 3C 00 013A 79

      Response should be in the data, the first byte 01 indicates that the real address of the current device is, 55 3C converted to decimal 20182 indicates that the current device main model is 21820, the last two bytes 00 01 Indicates that the device has a status quantity.

    2. Change Device Address
      For example, if the current device address is 1, we want to change to 02, the command is:01 06 00 66 00 02 E8 14.
      Device IDFunction idStart AddressDestinationCRC16
      010600 6600 02E8 14

      After the change is successful, the device will return information: 02 06 00 66 00 02 E8 27 , its format is parsed as shown in the following table:

      Device IDFunction idStart AddressDestinationCRC16
      010600 6600 02E8 27

      Response should be in the data, after the modification is successful, the first byte is the new device address. After the general device address is changed, it will take effect immediately. At this time, the user needs to change the query command of the software at the same time.

  4. Read and Modify Baud Rate
    1. Read baud rate
      The device default factory baud rate is 9600. If you need to change it, you can change it according to the following table and the corresponding communication protocol. For example, read the current device’s baud rate ID, the command is:01 03 00 67 00 01 35 D5 , its format is parsed as follows:
      Device IDFunction idStart AddressData LengthCRC16
      010300 6700 0135 D5

      Read the baud rate encoding of the current device. Baud rate encoding: 1 is 2400; 2 is 4800; 3 is 9600; 4 is 19200; 5 is 38400; 6 is 115200.
      For the correct query command, the device will respond, for example the response data is: 01 03 02 00 03 F8 45, the format of which is as shown in the following table:

      Device IDFunction idData LengthRate IDCRC16
      01030200 03F8 45

      Coded according to baud rate, 03 is 9600, ie the current device has a baud rate of 9600.

    2. Change the baud rate
      For example, changing the baud rate from 9600 to 38400, ie changing the code from 3 to 5, the command is: 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64 15.
      Device IDFunction idStart AddressTarget Baud RateCRC16
      010300 6600 0164 15

      Change the baud rate from 9600 to 38400, changing the code from 3 to 5. The new baud rate will take effect immediately, at which point the device will lose its response and the baud rate of the device should be queried accordingly. Modified.

  5. Read Correction Value
    1. Read Correction Value
      When there is an error between the data and the reference standard, we can reduce the display error by adjusting the correction value. The correction difference can be modified to be plus or minus 1000, t hat is, the value range is 0-1000 or 64535 -65535. For example, when the display value is too small, we can correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the command 100 is hex 0x64 If you need to reduce, you can set a negative value, such as -100, corresponding to the hexadecimal value of FF 9C, which is calculated as 100-65535=65435, and then converted to hexadecimal to 0x FF 9C. The correction value starts from 00 6B. We take the first parameter as an example. The correction value is read and modified in the same way for multiple parameters.
      Device IDFunction idStart AddressData LengthCRC16
      010300 6B00 01F5 D6

      For the correct query command, the device will respond, for example the response data is: 01 03 02 00 64 B9 AF, the format of which is as shown in the following table:

      Device IDFunction idData LengthData valueCRC16
      01030200 64B9 AF

      In the response data, the first byte 01 indicates the real address of the current device, and 00 6B is the first state quantity correction value register. If the device has multiple parameters, other parameters operate in this way. The same, the general temperature, humidity have this parameter, the light generally does not have this item.

    2. Change correction value
      For example, the current state quantity is too small, we want to add 1 to its true value, and the current value plus 100 correction operation command is:01 06 00 6B 00 64 F9 FD.
      Device IDFunction idStart AddressDestinationCRC16
      010600 6B00 64F9 FD

      After the operation is successful, the device will return information: 01 06 00 6B 00 64 F9 FD, the parameters take effect immediately after successful change.

Disclaimer
This document provides all information about the product, does not grant any license to intellectual property, does not express or imply, and prohibits any other means of granting any intellectual property rights, such as the statement of sales terms and conditions of this product, other issues. No liability is assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use of this product, including the suitability for the specific use of the product, the marketability or the infringement liability for any patent, copyright or other intellectual property rights, etc. Product specifications and product descriptions may be modified at any time without notice.

Contact Us

Company: Shanghai Sonbest Industrial Co., Ltd
Address: Building 8,No.215 North east road, Baoshan District, Shanghai, China
Web: http://www.sonbest.com
SKYPE: soobuu
Email: sale@sonbest.com
Tel: 86-021-51083595 / 66862055 / 66862075 / 66861077