SIEMENS logoFSD901-U2/ FSD901-R2/ FSD901-U3/FSD901-R3
Floor Repeater Display
Product ManualSIEMENS FSD901-U2 Floor Repeater Display for Fire Detection System -

Overview

The floor repeater display is an indication and operation unit in a fire detection system with the following functions:

Indication of eventsOperation
  • Alarm
  • Trouble
  • Supervisory
  • Status
  • Scrolling through lists
  • Reset
  • Acknowledge
  • Unsilence
  • Silence

The display on the floor repeater terminal is synchronized with the fire control panel and displays the same event texts.

Characteristic

  • Small floor repeater operating, and display panels applied in FC2005/FC901 fire detection system
  • Large backlight LCD display(160X64)
  • Communication with controller via RS485 (individual addressing)
  • Additional 24 VDC power supply necessary
  • In total, up to 8 FSD can be connected to a fire control panel
  • Access control by key
  • Flat, elegant housing

Function

  • Display of alarms, troubles, supervisory and status event
  • Same message layout as the fire control panel
  • With the navigation keys an indicated list in the display can be scrolled through
  • The internal buzzer can be switched off manually by pressing button “Acknowledge”
  • Reset events displayed on the FSD
  • Silence and unsilence

Application

SIEMENS FSD901-U2 Floor Repeater Display for Fire Detection System - Fig.1 Front view

No.NameFunction
1.LCDDisplay of alarms, troubles, supervisory and status
2.AlarmLight up in case of fire
3.Four-way buttonFor menu navigation
4.PowerLight up when power supply is normal
5.TroubleLight up in case of trouble event
6.Ground FaultLight up in case of ground fault event
7.SilencedAll activated silenceable devices are silenced
8.SupervisoryLight up in case of supervisory event
9.Audibles onLight up when NAC or silenceable device is activated
10.<Reset>Clear all events
11.<Acknowledge>Acknowledges unacknowledged events
12.<Unsilence >All silenced devices are activated again
13.<Silence >Silence all activated silenceable devices
14.LockSet user access level by key

User Level

FSD floor repeater display control access right through lock on door. There are two user levels for access right:

User levelLock key position
L0SIEMENS FSD901-U2 Floor Repeater Display for Fire Detection System - icon
L1SIEMENS FSD901-U2 Floor Repeater Display for Fire Detection System - icon1

The operation items for L0/L1 are listed as below:

ItemsL0L1
View real time events
Acknowledge
Reset
Silence
Unsilence
Lamp test

Operation

TaskOperation
View real time events1. Press “↓” / “↑” to navigate a real time event.
2. Press “←” to return to first event.
Lamp testPress both “Silence” and “Unsilence” button for 5s to do lamp test.
Acknowledge or reset eventsPress “Acknowledge” or “RESET”.
Unsilence devicesPress “Unsilence”, all silenced devices are activated again.
Silence devicesPress “Silence”, silence all activated silenceable devices.

Address and Baud Rate
8-digit Dip-switch S1 is used for setting the FSD901 address and Baud Rate Setting.
The first 1-4 digits is for setting the FSD901 address 1-8, the 7-8 digits is for setting RS485 communication baud rate. The 5 and 6 digits are reserved for future use.

AddressDIP switch
1234
1OnOffOffOff
2OffOnOffOff
3OnOnOffOff
4OffOffOnOff
5OnOffOnOff
6OffOnOnOff
7OnOnOnOff
8OffOffOffOn
Baud RateDIP switch
78
9600 bpsOffOff
19200 bpsOnOff
38400 bpsOffOn
115200 bpsOnOn

FC2005 and FC901 can only support 19200 bps, other options reserve for future usage.

EOL Resistor
2-digit Dip-switch S20 is used for setting EOL resistor of RS485.

1 and 2On:Internal EOL resistor is connected
1 and 2Off:Internal EOL resistor is disconnected

For RS485 Class A, loop mode, no EOL resistor is needed.
For RS485 Class B, stub mode, internal EOL resistor of the repeater display at the end of RS485 must be connected.

Installation

SIEMENS FSD901-U2 Floor Repeater Display for Fire Detection System - Fig 2 DimensionSIEMENS FSD901-U2 Floor Repeater Display for Fire Detection System - Fig 3 Connection

Note:

  • Point G is not used for any connection.
  • Power in from the non-resettable auxiliary power output on panel.

SIEMENS FSD901-U2 Floor Repeater Display for Fire Detection System - Fig 4

  1. Insert the loop line and external power wire through the floor repeater display.
  2. Mark the position for the 4 installation holes on flat wall (Fig. 2), drill the holes, put expansion bolts in and insert the screws leaving a small gap for hanging the display.
  3. Hang the floor repeater display over those screws through installation holes.
  4. Open the front panel (Fig. 4/5), tighten the screws and make sure the display is fixed firmly.
  5. Connect cables to terminals referring to the connection diagram (Fig. 3). Correctly set the internal 120Ω EOL resistor referring to the section “EOL Resistor”.
  6. Close the front panel.
    SIEMENS FMT-A-ADPT ClassA Riser Module - icon FSD connects to separate power supply, which needs to be UL Listed for Fire Safety Use and Power Limited.

Dimension (mm)

SIEMENS FSD901-U2 Floor Repeater Display for Fire Detection System - Dimension

Technical data

Operating voltage24 VDC nominal / 19…28 VDC
Operating current (quiescent)60 mA
Activation current70 mA
Operating temperature0…+49 °C
Humidity≤93% rel.
Communication protocolUFP (RS485-BUS)
Connection terminals14-18 AWG
ColorBlack / Red
Operating locationIndoor / dry

Details for ordering

TypeMaterial No.Part No.DesignationWeight
FSD901-U2S54433-C102-A4100935670Desigo system display (black)1.5 kg
FSD901-R2S54433-C102-A3101061934Desigo system display (red)1.5 kg
FSD901-U3S54433-C102-A1101061935Cerberus system display (bl)1.5 kg
FSD901-R3S54433-C102-A2100935673Cerberus system display (red)1.5 kg

Issued by
Siemens Industry, Inc.
Smart Infrastructure
8 Fernwood Road
Florham Park, NJ 08932
Tel. +1 973-593-2600
www.sbt.siemens.com/FIS
© Siemens Industry, Inc., 2019
Technical specifications and availability subject to change without notice