RATH 2500-LUPSM Relay Control Card Installation Guide
RATH 2500-LUPSM Relay Control Card

  1. On the back of RP7701500, locate the “Expansion Port” and unscrew the two screws holding the cover in place.
    Expansion Port
  2. Insert the Relay Control Card from the 2500-LUPSM into the Expansion Port and screw into place.
  3. Plug the serial side of the supplied DB9 cable into the Relay Control Card.
  4. Use pigtail wires to connect the 2500-LUPSM to monitoring device or fire panel. Each pair monitors a different fault. See Chart 1 for function.

Note: All pairs will be Normally Open and Close when in a fault.

Pins
Relay Control Card

Chart 1: 

Pin AssignmentFunctionI/O
Pin 1UPS FaultO/P
Pin 2Summary AlarmO/P
Pin 5Common (For Relays)O/P
Pin 7Battery LowO/P
Pin 9Utility Line FailO/P

APPENDIX A: Relay Control Card RELAYIO500 

Function Description: 

StatusCondition
Blue Pair Pin 1 to Pin 5UPS Fault (Inverter Fault / DC Bus Fault / Over Temperature / Output Short / Battery Over Charge / Battery Test Fail 1 / Fan Error 1)
Orange Pair Pin 2 to Pin 5Summary Alarm (Inverter Fault / DC Bus Fault / Output Short / Over Temperature / Over Load / Battery Missing / Battery Over Charge / Battery Low / Wiring Fault / Runtime Low 2 / Battery Test Fail 1 / Load Over Setting Level 1 / Fan Error 1)
Green Pair Pin 7 to Pin 5Battery Low
Brown Pair Pin 9 to Pin 5Utility Line Fail (AC Power Loss / Ground Fault / External AC Failure

Warranty

2 YEAR WARRANTY

N56W24720 N. Corporate Circle • Sussex, WI 53089
800-451-1460www.rathcommunications.com

Documents / Resources

RATH 2500-LUPSM Relay Control Card [pdf] Installation Guide
2500-LUPSM Relay Control Card, 2500-LUPSM, Relay Control Card

References

Leave a comment

Your email address will not be published. Required fields are marked *