LUMEL logoTRANSFORMER SERIES
LCTM, LCTR, LCTB, LCTS, LCTP
Operating Manual

LCTM Transformer

Low Voltage-Current Transformer –

  • LCTM
  • LCTR
  • LCTB
  • LCTS
  • LCTP

LUMEL LCTM Transformer

Functional description

Current transformers of the model range mentioned above are inductive single conductor-current transformers operating according to the transformer principle. Due to the applicated measuring principle, current transformers of this type may only be installed in alternating current (AC) networks.

Safety instructions

Warning icon In order to avoid personal and material damage the following assembling steps must by performed only by authorised, qualified and trained personnel.
Electric Warning Icon If the secondary circuit is operated without a burden/load (open) high voltages may appear. These voltage values are dangerous for persons as well as for the functional reliability of the current transformer.
It is forbidden to operate the current transformer without a secondary circuit (open)!

Technical parameters

Primary current:30A to 6000A
Secondary current:1A or 5A
Accuracy class:0.2, 0.2s, 0.5, 0.5s & 1
Over current limiting factor:FS5, FS10, FS15
Rated frequency:50Hz or 60Hz
Rated continues thermal current (standard):1,2 x In
Rated short time thermal current Ith:60 x In, 1 s (Max 40kA)
Rated isolation level:0,6/3/-kV or 0,6/4/-kV
Place of installation:Indoor
Altitude:up to 2000 m
Degree of protection:IP20
Ambient temperature:-5ºC …+50ºC
Storage temperature:-25ºC …+70ºC
Applied standards:IEC 60044-1 / IEC 61869-1/2 IEC 61010-2

Assembly

  1. Ensure a safe work environment during assembly, maintenance and inspection operations. If necessary interrupt the current supply of the primary conductor and take precautions against unintentional switching.
  2. (i) For Split core CT : Open the current transformer and fix it on the primary conductor using the fixing clamps (mounting material).
    (ii) For Window type CT : Bar or cable primary insert through primary cable or bus bar & fix it using mounting screw assembly.
    P1: Direction of power supply
    P2: Direction of power source
    Attention: (i) Do not close the current transformer, high voltages may appear on the open secondary leads.
    (ii) Check for cleanness of the cut surfaces of the split core.
  3. Connect the secondary wires of the current transformer with the measuring device (ampere meter, energy meter).
    Pay attention to the installation guide of the measuring device.
  4. Now fasten the current transformer, press until the lock engage.
  5. If necessary, start the current supply again.
  6. Check whether the current transformer is assembled correctly and the secondary leads are connected properly.
  7. For split core CT, use “lock pin” supplied along with CT to protect accidental opening of CT, during in use.

Wiring diagram

LUMEL LCTM Transformer - Wiring diagram

Mounting of CT

LUMEL LCTM Transformer - Mounting of CT 1
CABLE MOUNTINGBUS BAR MOUNTING
LUMEL LCTM Transformer - Mounting of CT 2
BUS BAR MOUNTINGWALL MOUNTING
LUMEL LCTM Transformer - Mounting of CT 3
DINRAIL MOUNTING HORIZONTALDINRAIL MOUNTING VERTICAL
LUMEL LCTM Transformer - Mounting of CT 4
BUS BAR MOUNTING 3PH CTCABLE MOUNTING 3PH CT
LUMEL LCTM Transformer - Mounting of CT 5
DINRAIL MOUNTING
HORIZONTAL 3PH CT
DINRAIL MOUNTING
VERTICAL 3PH CT
LUMEL LCTM Transformer - WALL MOUNTING 3PH CT
WALL MOUNTING 3PH CT

Environmental instruction
When the product has reached it´s “end of life“, it must be recycled. Pass it to an electrical waste disposal. Do not dispose as unsorted municipal waste!

CE SYMBOL
LUMEL S.A.
ul. Słubicka 4, 65-127 Zielona Góra, Poland
tel.: +48 68 45 75 100
www.lumel.com.pl
Technical support:
tel.: (+48 68) 45 75 143, 45 75 141, 45 75 144, 45 75 140
e-mail: export@lumel.com.pl
Export department:
tel.: (+48 68) 45 75 130, 45 75 131, 45 75 132
e-mail: export@lumel.com.pl
Calibration & Attestation:
e-mail: laboratorium@lumel.com.pl

Documents / Resources

LUMEL LCTM Transformer [pdf] User Manual
LCTM, LCTR, LCTB, LCTS, LCTP, LCTM Transformer, LCTM, Transformer

References

Leave a comment

Your email address will not be published. Required fields are marked *