LS ELECTRIC H100 Variable Speed Drive User Guide
Introduction
This quick start reference is meant to be a supplement to the User Manual included in the VFD packaging. This reference is a continuation to the H100+ “Basic Setup” quick start. It assumes proper motor and VFD protection features have been setup.

Improper wiring and operation may result in serious personal injury or death.
Step 1 – Transducer Identification and Wiring

“24V” is used to power the transducer.
“I2” is used for the 4-20mA input terminal from the transducer.
Polarity MUST be correct.


Utilize the “V1” terminal or “I2”.
Note: If using I2 for a voltage input set SW4 to the right. This sets “I2” up as “V2”.
Step 2 – Basic PID Parameter Setup


MACROCode | Group | No | Description | Default | Setting options | Recommended Setting |
17 | PID | 1 | PID Selection ( Enables PID ) | Yes | Yes/No | 1 – Yes |
18 | PID | 10 | PID Reference selection | Keypad | # (0-6) | 0- Keypad (typically) |
19 | PID | 11 | PID Reference 1 | 0 PSI(-100 to 100 PSI) | Based onfeedback scaling | ** SET THIS LAST ** |
20 | PID | 20 | PID Feedback Source | (3) = I2 | # (0-9), refer to the LCD keypad. | Depends on the system requirement, typically “I2”. Refer to wiring done on step 1. |
21 | PID | 25 | PID P-Gain 1 | 100% | 0 – 200% | Adjust as needed to improve performance. |
22 | PID | 26 | PID I-Time 1 | 2.00 Sec. | 0 – 200 Sec. | Adjust as needed to improve performance. |
24 | PID | 50 | PID Unit Selection | PSI | 0-41, refer tothe LCD keypad. | Set to the unit being controlled. |
25 | PID | 51 | PID Unit Scale Multiplier | x10 | x0.01 up to x100 | Depends on the system requirement |
26 | PID | 53 | PID Unit Fitting [MAX] | 100 PSI | 100 PSI | Set to the max transducer value. For example, 100PSI |
H100+ Step 3 – Commonly Set Parameters and Functions
- PID-59 Sleep Level type
The following sleep level types can be selected:
Setting
- Frequency (Factory Default)
- Output Current
- PID Feedback Value
- RPM
- Flow Rate
- PID-62 PID Sleep 0 DT
- PID-63 PID Sleep 0 Lev
If the operating frequency stays below the frequencies set at PID-63 for the set times at PID-62, the VFD enters standby mode. - PID-56 Pump Minimum Speed
Pump minimum speed sets the low limit on the command frequency. Minimum Limit operates based on the greatest value of following:- AP2 40 Thrust Frequency, PID 56 Pump Minimum Speed, ADV 25 Freq Limit Lo
- PID-57 Wake UpLev type
0. Absolute or 1. Deviation (Factory default) can be selected for the Wake-up level - PID-64 PID Wake Up 0 DT
- PID-65 PID Wake Up 0Lev
Sets the reference for PID operation in PID sleep mode. PID operation resumes when PID feedback variation (from the PID reference) exceeds the values set in PID-65 for more than the time set in PID-64.
Lost Feedback Detection
Lost Feedback Detection shuts the pump down when the feedback is lost. The VFD can be set to take the action programmed in AP2-75.
- AP2-75 LostFbkMode
Setting
- None
- Warning
- Trip & Coast
- Lost Preset
- PRT-14 Lost Cmd Time
- PRT-15 Lost Preset Frequency
High/Low Feedback Detection
Low/High feedback detection detects whether PID feedback is higher than high feedback level or lower than low feedback level to trigger Warning or Trip&Coast stop.
- AP2-48 High Feedback Detection Mode
- AP2-49 High Feedback Level Fault Delay Time
- AP2-50 High Feedback Level
- AP2-51 Low Feedback Mode
- AP2-52 Low Feedback Level Fault Delay Time
- AP2-53 Low Feedback Level
- AP2-54 Hysteresis Level
Thrust Bearing Control

- AP2-40 Thrust Frequency
- AP2-41 Thrust Bearing Acceleration Time
- AP2-42 Thrust Bearing Deceleration Time
Step 4 –Verifying Operation
The VFD must be in AUTO mode for PID to operate. Additionally, an active run command must be present. This is dependent on DRV06. The Pressure Control macro “pins” feedback and setpoint to the main monitor screen for easy viewing. Compare the Feedback monitor on the main screen to a mechanical gauge. See below examples.
Step 5 –PID Troubleshooting
VFD is not running
- Check run command
- Check that feedback is below the setpoint
- Check sleep and wakeup levels
Feedback is always at “0”.
- Check that PID20 matches physical terminal used for feedback.
- Check transducer polarity.
- Check analog input monitor to verify signal. IN05(V1), IN35(V2), or IN50(I2).
- Check that sleep delay time is longer than accel time to prevent “sleep cycling”
- Gradually increase P gain and decrease I-Time.
Documents / Resources
![]() | LS ELECTRIC H100 Variable Speed Drive [pdf] User Guide H100 Variable Speed Drive, H100, Variable Speed Drive, Speed Drive, Drive |