KE2 Temp + Valve Controller

KE2-Temp+Valve-Controller-PRODUCT

This reference should remain on site with the installed KE2 Temp + Valve controller.

KE2 Temp+Valve Control
For Temp. Air Defrost, and Electronic Valve Control Condensed Quick Start Guide KIT PN 21301

KE2-Temp+Valve-Controller-FIG-1KE2-Temp+Valve-Controller-FIG-2

What’s in the KE2 Temp + Valve kit, pn 21301

KE2-Temp+Valve-Controller-FIG-3

  • A (1) KE2 Temp + Valve controller (pn21393 – controller only)
  • B (1)10’ pressure transducer
  • C (1) temperature sensor – 45”
  • D (1) temperature sensor – 10’
  • E (4) self-tapping mounting screws
  • F(1) sensor ziptie
  • G(1) screwdriver
  • H(2) screws for high voltage shield

Supplies List

Truck stock items are required to install the controller:

  • conduit between the controller & evaporator
  • (2) conduit connectors (straight or elbow as required)
  • (4) high voltage wires (matched to LLS/compressor contactor & the controller load)
  • wire labeling (numbers colors etc
  • additional wire ties
  • 18 gauge twisted shielded pair (if extending sensor wires)
  • Cat5e (if adding communication)
  • foam insulation (if running wires outside the space)
  • silicone (for sealing any box penetrations)

Complete Instructions

Please visit:  
scroll down the page and click
Link to Literature
— OR —
use this QR code.KE2-Temp+Valve-Controller-FIG-5

Wiring Diagram

KE2-Temp+Valve-Controller-FIG-4

Alternate Wiring Method

KE2-Temp+Valve-Controller-FIG-6

Basic Menu: “Out of Box” or if Superheat (SHt)

SetpointDescriptionRangeDefault
CtLControl Type – EEV+Temp, EEV Only, EEPR, EHGBP, SubcoolSHt, SH, EPr, HGb, SUbSHt
Edt

(Expansion device type)

Valve Type: Mechanical (tHr), KE2- HSV (HS), KE2-RSV (rS), SEI, SER,

Carel (CrL), Custom (CUS)

tHr, HS, rS, SEi ,SEr CrL, CUS*rS
Only if CUS

is used for Edt

(valve type)

SrStep Rate30 – 40030
SFSSteps Full Stroke200- 6400500
UbMotor TypeUni-(unipolar), bi (bipolar)Unipolar
Only if inP (input) is

Pt under Advanced

Menu

rFgRefrigerant TypeSee Refrigerant List below404
SSPSuperheat Setpoint**5ºF (2.8K) to 50ºF (28K)8°F (4.4K)
tSTemperature Setpoint-50°F (-45°C) to 100°F (38°C)35°F (9.7°C)
AdFAir Temperature Differential1°F (0.5K) to 30°F (17K)2°F (1.1K)
CSHCompressor Starts/Hour Maximum5 (Off)*** to 106
dPdDefrost Per Day0 to 12, CUS*4
Only if dPd (Defrosts

per Day) is CUS

tOdTime of Day00:00 to 23:5912:00
d1 to d12Start time of Defrost #1 – #1200 – 23diS (disabled)
dFtDefrost Time6 min to 720 min45 min

* Selecting CUS (custom) unlocks additional Setpoints.
** Min. superheat in Subcool control.
*** Selecting fewer than 5 compressor starts per hour results in the starts per hour feature being turned off. The compressor will then function on temperature only.

Controller Navigation

The display will show room temp (rtp), superheat (SH), sution pressure (PrS) or leaving liquid temp (LLT) depending on control type and setup.

Indicator lights

KE2-Temp+Valve-Controller-FIG-7

  • Red light – Critical alarm (system is NOT running).
  • Yellow light – Non-critical alarm (system running).
  • Green light – Liquid Line Solenoid (LLS) relay energized.
  • Green blinking – Waiting on min. run or min. off timer to energize/de-energize LLS relay.
  1. Access Setpoint mode by pressing and holding KE2-Temp+Valve-Controller-FIG-10 until (CtL ontrol type) displays on the screen
  2. Use KE2-Temp+Valve-Controller-FIG-8 and KE2-Temp+Valve-Controller-FIG-9 to advance through available setpoints.
  3. Press KE2-Temp+Valve-Controller-FIG-10to view the current setting.
  4. PressKE2-Temp+Valve-Controller-FIG-10 to move between digits to accelerate the changes.
  5. Use KE2-Temp+Valve-Controller-FIG-8 and KE2-Temp+Valve-Controller-FIG-9to change the setpoint
  6. PressKE2-Temp+Valve-Controller-FIG-10 and hold to confirm each setpoint change
  7. Press back to escape.

Service Call Saver- Post Defrost Indicator
The display will switch between room temp and dEF after a defrost. The controller will refrigerate as normal, and dEF will clear automatically.

Accessing the Menus

For a complete list of setpoints and descriptions see Q.3.49.

Footnotes

  1. Not shown if in EEPR, EHGBP, SH, or SUb control, and input is pressure.
  2. Only shown if SUb control is selected.
  3. Only shown if SH, SHt, or SUb control is selected.
  4. Only if SH, SHt, or SUb and Pt control is selected .
  5. Only shown if input is pressure for EEPR or EHGBP
  6. Only shown if in SH, SHt, or SUB control and tt selected.
  7. P ress & hold ENTER for 3 seconds to activate.
  8. Press BACK button to return to normal operation.
  9. Press ENTER to enter manual valve control, & to adjust, and press BACK to exit.

Alarm List

KE2-Temp+Valve-Controller-FIG-11

Refrigerant List

RefrigerantAbbreviation
R-22R22
R-134a134
R-404A404
R-407A40A
R-407C40C
R-410A410
R-717717
R-422A42A
R-422D42d
R-507507
RefrigerantAbbreviation
R-448A448
R-449A449
R-450A450
R-438A438
R-408A408
R-409A409
R-407F407
R-744744
R-513A513
R-458A458

© Copyright 2021 KE2 Therm Solutions, Inc., Washington, Missouri 63090 Q.3.66 June 2021 supersedes all prior publications.
KE2 Therm Solutions