ICM CONTROLS ICM493 Programmable Single-Phase Voltage Monitor Installation Guide
INSTALLATION
- Remove cover by extracting the screw from the bottom of the enclosure.
- Remove desired size knock-outs for conduit from the enclosure (1/2” or 3/4”).
- Mount the enclosure to the desired surface.
- Attach input and output conduit, apply strain relief.
- Tilt front panel diagonally and insert the panel into the enclosure, as shown in Figure 1.
- Lay the front panel horizontally in the enclosure and align the holes on the side, as shown in Figure 2.
- Using the two larger screws, included in the kit, and a screwdriver, attach the front panel to the enclosure.
- Wire L1 and L2 directly to the contactor input and output, as shown in Figure 3.
- Close the hinged plate and secure the upper right corner into the bracket with the small screw provided in kit.
- Once settings have been configured, attach cover and secure with screw.
CALIBRATION FEATURE
The ICM493 can be calibrated to match the reading from a true RMS meter.
- Measure input voltage from T1 to T2 using a true RMS meter.
- Hold
buttons simultaneously until line voltage starts to flash.
- Adjust voltage using
buttons to match measured voltage from step 1.
- Push
button to lock values into memory.
SPECIFICATIONS
Input:
- 180-264 VAC
- 50/60 Hz
Contact Ratings:
- Voltage: 240 VAC
- FLA: 40A
- LRA: 240A
Control Operating Temperature:
- Operating Temperature: -40°F to 167°F (-40°C to 75°C)
- Storage Temperature: -40°F to 185°F (-40°C to 85°C)
- LCD Operating Temperature: -4°F to 167°F (-20°C to 75°C)
Mechanical:
- Mounting: Four mounting holes in back of enclosure
- Enclosure: NEMA/Type 3R, rain-tight enclosure rated for outdoor installation
- Dimensions: 8”L x 8.25”W x 4.37”H
Parameters:
- Line Voltage: 200-240 VAC, adjustable
- Over/under voltage setting: 5%-10%, adjustable
- Anti-short cycle time delay: 0.5-10 minutes
- Number of trials: 1-5, Auto
- Number of movistors: 0-5
SETTING THE PARAMETERS
- Press the
button to scroll through various user-configurable settings.
- Use the
buttons to change the set point.
- When the last parameter has been set, you will return to the read screen.
Press to enter setup mode, and to toggle through user-configurable settings.
Press at any time to return to the Read screen, which will display any faults, the current line voltage, and the number of remaining MOVs.
Press to scroll through past recorded faults. Hold for 5 seconds to clear fault memory.
Press to adjust settings & . Hold for 2 seconds to enter line voltage calibration.
Hold for 2 seconds to reset unit.
Parameter | Description | Range | Default | Recommended |
Line Voltage | The expected line voltage | 200-240 | 240 | Nameplate Voltage** |
Over/Under Voltage | The allowed percentage over and under the set line voltage | 5% to 10% | 10% | 10% Over/Under |
Anti-Short Delay | The amount of time delay between the end of a fault, and closing of the contactor | 0:30 to 10:00 | 0:30 | 4 minutes |
Reset Mode Retries | The number of retries after a fault has occurred. Auto has unlimited retries. | 1 to 5, Auto | Auto | Auto |
Allowed MOV Fail | The number of surge devices allowed to fail while maintaining operation. Setting to “5” will allow operation, even when surge protection has been exhausted. | 0 to 5 | 5 | Set to “5” for ensured operation. Set to “4” for max. operation while ensuring surge protection. |
7313 William Barry Blvd., North Syracuse, NY 13212
Phone: 315-233-5266
Fax: 315-233-5276
www.icmcontrols.com
800.365.5525 LIAF209-6