DELTA CMC-EC01 Ethercat Communication Card Instruction Manual

Send Quote Requests to info@automatedpt.com   Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com

DELTA logo

CMC-EC01

EtherCAT Communication Card
Operation Manual

DELTA A - 1 http://www.deltaww.com/

20170720

Warning-11-A Warning

Right Tick This operation manual provides information on specifications, installation, basic operation, setup and details of the communication protocol

Right Tick AC motor drive is a delicate electrical and electronic product. For the safety of operator and the mechanical equipment, please allow professional electrical mechanics to do the trial run and adjust parameters for you. Should there be any questions, please consult your local Delta distributors. Our professional staff will be happy to help you

Right Tick Please read this operation manual thoroughly and follow the instructions in case damage on the device or injury on the operation staff occur.

1 Introduction
1.1 EtherCAT Description

The application layer of the C2000’s EtherCAT communication interface uses the standard DS402 protocol and complies with the CoE (CAN Application Protocol over EtherCAT) definition. Therefore, all of C2000’s application layer protocols that comply with the CANopen DS402 standard can be used on top of EtherCAT.

1.2 Functionality

For the user’s convenience, C2000’s EtherCAT card currently supports standard DS402 Velocity (Index 6060 = 2). It should be noted, however, that this mode is asynchronous control mode. C2000 support EtherCAT communication card from v2.02, please make sure if the drive firmware is supported or not.

Specification

Item 

Specifications 
Connection RJ-45 
Ports 

2 Port 

Interface IEEE802.3, IEEE802.3u 
Cable Category 5e shielding 100 M 
Speed 10 / 100 Mbps Auto-Defect 
Protocol EtherCAT 

Environment

Item Specifications 
Noise Immunity ESD (IEC 61800-5-1, IEC 6100-4-2)
EFT (IEC 61800-5-1, IEC 6100-4-4)
Surge Teat (IEC 61800-5-1, IEC 6100-4-5)
Conducted Susceptibility Test (IEC 61800-5-1, IEC 6100-4-6) 
Operation Temperature -10 °C ~ 50 °C (Temperature), 90% (Humidity) 
Storage Temperature -25 °C ~ 70 °C (Temperature), 95% (Humidity) 
Vibration / Shock Immunity IEC 61800-5-1, IEC 60068-2-6 / IEC 61800-5-1, IEC 60068-2-27 

Electrical Specification

Item Specifications 
Power Supply 5 Vdc 
Power Consumption 0.8 W 
Insulation Voltage 500 Vdc 
Weight 27 (g) 
2 Product Profile and Outline
2.1 Dimension

DELTA CMC-EC01 Ethercat Communication Card - a1      DELTA CMC-EC01 Ethercat Communication Card - a2
Unit: mm [inch]

2.2 Parts

DELTA CMC-EC01 Ethercat Communication Card - a3 DELTA CMC-EC01 Ethercat Communication Card - a4

  1. Screw fixing hole
  2. Positioning hole
  3. RUN indicator
  4. ERR indicator
  5. POWER indicator
  6. OUT LINK indicator
  7. IN LINK indicator
  8. Fool-proof groove
  9. RJ-45 connection port
  10. RJ-45 connection port
  11. AC motor drive connection port
2.3 LED indicator

Name 

Status Indication 
POWER Green On Power supply in normal status 
Off No power supply 
LINK Green On Normal status 
Blink Pre-operation(on/off200ms) 
Safe mode (on 200ms/ off 1000ms) 
Off Initial 
ERROR Red Blink Basic configuration error (on/off 200ms) 
Status witch error (on200ms /off1000ms) 
Timeout(on 200ms twice /off1000ms) 
Off No error 
IN LINK Green On Network connected 
Blink Network in operation 
Off Network not connected 
OUT LINK Green On Network connected 
Blink Network in operation 
Off Network not connected 
2.4 RJ-45 PIN Definition

RJ-45 Sketch 

No. Signal Definition 

DELTA CMC-EC01 Ethercat Communication Card - a5

1 

Tx+ Positive pole for data transmission 

2 

Tx- Negative pole for data transmission 

3 

Rx+ Positive pole for data receiving 

4 

 N / C 

5 

 N / C 

6 

Rx- Negative pole for data receiving 

7 

 N / C 

8 

 N / C 
3 Installation and Wiring

In this section, we illustrate how to connect CMC-EC01 to VFD-C2000 and the network

3.1 How to Install

How to connect CMC-EIP01 to VFD-C2000 series AC motor drive:

  • Switch off the power supply of VFD-C2000
  • Open the front cover of VFD-C2000
  • Place the insulation spacer into the positioning pin at Slot 1 (see Figure 1) and aim the two holes on the PCB at the positioning pin. Press the pin to clip the holes with the PCB (see Figure 2).
  • Crew up at torque 6~8 kg-cm [5.2~6.9 lb-in.] [0.59~0.78 Nm ] after the PCB is clipped with the holes (see Figure3).

DELTA CMC-EC01 Ethercat Communication Card - Figure 1               DELTA CMC-EC01 Ethercat Communication Card - Figure 2
Figure 1                                                       Figure 2

DELTA CMC-EC01 Ethercat Communication Card - Figure 3
Figure 3

3.2 How to Disconnect

How to disconnect CMC-EIP01 from VFD-C2000

  • Switch off the power of VFD-C2000
  • Open the front cover of VFD-C2000
  • Remove the two screws (see Figure 4).
  • Twist open the card clip and insert the slot type screwdriver to the hollow to prize the PCB off the card clip (see Figure 5).
  • Twist and open the other card clip to remove the PCB (see Figure 6).

DELTA CMC-EC01 Ethercat Communication Card - Figure 4 DELTA CMC-EC01 Ethercat Communication Card - Figure 5
Figure 4                                                         Figure 5

DELTA CMC-EC01 Ethercat Communication Card - Figure 6
Figure 6

3.3 Wiring

The CMC-EC01 moves packets directionally from IN (left) to OUT (right), with the correct wiring method shown below:

DELTA CMC-EC01 Ethercat Communication Card - b1

After hardware installation is complete, turn on the power and look at parameter P9-60.
The value displayed should be “6”, and the word “EtherCAT” should also be displayed. If not, please check the version of the inverter and whether the card has been correctly connected. (C2000 of version v2.02 or above may support CMC-EC01)

DELTA CMC-EC01 Ethercat Communication Card - b2

4 VFD-C2000 Drive Configuration

To control the C2000 via EtherCAT, all you need to do is configure relative parameters so that the command input source is set to the EtherCAT communications interface.

Relative settings are as follows:

Parameter 

Value / Display Description 
Pr. 00-20 8 set the communications card as the frequency source if speed control is required 
Pr. 00-21 5 set the communications card as the control source 
Pr. 09-60 6 check whether P9-60 automatically displays EtherCAT as the communications card type 
[NOTE]:
  1. In order for the PLC or control PC to be able to recognize the C2000, the product description file (ESI file) of the C2000 must be loaded. The file name of the C2000 product description file is “CMC-EC01 with C2000.xml,” and this file can be obtained from Delta’s website.
  2. To have C2000 calculate correctly the output frequency by sending a target speed command, please enter motor pole number parameter based on the motor type set at Pr. 05-33. For example, set Pr. 05-04 if it is asynchronous motor, or set Pr. 05-37 if it is synchronous motor.
5 EtherCAT List and Description of supported Index

The C2000 currently supports the standard DS402 specification. Therefore, its state machine and control follow DS402 protocol definitions. These definitions are described in detail in the following sections.

5.1 Index related to the state machine:

In the DS402 definition, state machine state changes are conducted via the Index 6040 control word (bit0~3 and 7). The current state of the state machine is shown in the 6041 status word (bit0~6). Therefore, corresponding bit definitions are as follows:

Index 6040:

Bit 

Definition 

0 

Switch on 

1 

Enable voltage 

2 

Quick Stop 

3 

Enable operation 

7 

Fault Reset 

Index 6041:

Bit 

Definition 

0 

Ready to switch on 

1 

Switched on 

2 

Operation enable 

3 

Fault 

4 

Voltage enabled 

5 

Quick stop 

6 

Switch on disabled 

The relationships between the states of the state machine are as shown below:

DELTA CMC-EC01 Ethercat Communication Card - b3

DELTA CMC-EC01 Ethercat Communication Card - b4Control word (6040) DELTA CMC-EC01 Ethercat Communication Card - b6
DELTA CMC-EC01 Ethercat Communication Card - b5Status word (6041)

5.2 Index related to the control mode:

0x6060 

0 

Mode of operation 

2 

RW S8 2: Velocity Mode 
0x6061 

0 

Mode of operation display 

2 

RO S8 Same as above 
5.3 Index related to the speed:

When Index 6060 = 2 and the state machine is in the Operation Enable state, the speed of the drive can be controlled. The indexes and controls currently provided by the C2000 in speed mode are listed below:

Index Sub Define Initial 

R/W 

Size Unit 

PDO Map 

Note 
0x6042 

0 

vl target velocity 

0 

RW S16 rpm Yes 

 

0x6043 

0 

vl velocity demand 

0 

RO S16 rpm Yes 

 

0x604F 

0 

vl ramp function time 10000 RW U32 1ms Yes The unit must be 100ms 
0x6050 

0 

vl slow down time 10000 RW U32 1ms Yes 

The system architecture is as shown below:

DELTA CMC-EC01 Ethercat Communication Card - b7

Therefore, when the state machine is in the Operation state, the speed mode control word (bits 4~6 and 8) is defined as follows:

Bit 

Description 

8 

6 

5 

4 

Halt rfg use ref rfg unlock rfg enable 

0 

1 

1 

1 

Run to the target speed 

0 

1 

0 

1 

Pause at the current speed 

1 

X X X Decelerate to zero speed 
Other Decelerate to zero speed 
5.4 Index Related to Disconnections:

When EtherCAT is disconnected, the C2000 will switch states according to Index 6007.

Index Sub Define Initial R/W Size Note 

0x6007 

0 Abort connection option co 2 RW S16 0 : No action 
1 : malfunction 
2 : Switch on disable 
3 : Quick stop 
  • When 0 is selected for 6007, disconnection errors will be ignored, which means that no warnings will be issued and nothing will be done.
  • When 1 is selected for 6007 and there is a disconnection, the CAN open state will change to the Error State and the warning code ECto will be displayed. Once the communications connection is confirmed to be re-established and Bit 7 of 6040 changes from 0 to 1, the error code will be cleared and the state machine will enter the “Switch on Disable” state.
  • When 2 is selected for 6007 and a disconnection occurs, the CAN open state will change to “Switch On Disable,” EC to will be displayed, and the stop operation will be triggered according to the index 605A settings. When the cable is re-connected and communications are successfully restored, the error code will be automatically cleared.
  • When 3 is selected for 6007 and a disconnection occurs, the CAN open state will change to “Switch On Disable,” ECto will be displayed, and the stop operation will be triggered according to the index 605C settings. When the cable is re-connected and communications are successfully restored, the error code will be automatically cleared.

When the state machine is in the “Quick Stop” state, stopping of the system will be conducted in accordance with the settings of Index 605A

Index Sub Define Initial R/W Size Note 
0x605A 0 Quick stop option code 1 RW S16  0 : disable drive function 
1 : Slow down on slow down ramp and transit into Switch On Disabled 
3 : Slow down on current limit and transit into Switch On Disabled 
5 : slow down on slow down ramp and stay in QUICK STOP 
7 : slow down on the current limit and stay in QUICK STOP 

When the state machine is in the “Switch On Disable” state, stopping of the system will be conducted in accordance with the settings of Index 605C

Index Sub Define Initial R/W Size Unit PDO Map Note 
0x605C 0 Disable operation option code 1 RW S16  No 0: Disable drive function 
1: Slow down with slow down ramp; disable of the drive function 
6 Configuring the Connection with the Beckhoff PLC

Here introduce using TwinCAT V2.11 and Beckhoff PLC by EtherCAT communication with VFD-C2000。Hardware configuration as following figure, PC connects to Beckhoff PLC by Ethernet, PLC use EtherCAT Master connects to C2000 CMC-EC01

DELTA CMC-EC01 Ethercat Communication Card - b8

6.1 Basic Configuration

■ Basic Configurations

1. Select “automatically obtain IP address” for the PC’s network IP setting.

DELTA CMC-EC01 Ethercat Communication Card - b9

2. Place the CMC_EC01 with C2000.xml file into the corresponding folder: …\TwinCAT\Io\EtherCAT\

DELTA CMC-EC01 Ethercat Communication Card - b10

■ Open System Manager

DELTA CMC-EC01 Ethercat Communication Card - b11

1. Click “Choose Target System” (Since there are no target systems in the beginning, you must first scan for target systems)

DELTA CMC-EC01 Ethercat Communication Card - b12

2. Scan via IP broadcast

DELTA CMC-EC01 Ethercat Communication Card - b13

3. Select PLC module and click OK

DELTA CMC-EC01 Ethercat Communication Card - b14

Left-click and select “Scan Devices” (note that the system must be in Configuration Mode). From the scan results, select the “EtherCAT” communications option

DELTA CMC-EC01 Ethercat Communication Card - b15

4. Pop-up window “Scan for boxes”, select Yes

DELTA CMC-EC01 Ethercat Communication Card - b16

5. Pop-up window “New device type found C2000(CMC-EC01 Card)”, select Yes

DELTA CMC-EC01 Ethercat Communication Card - b17

6. CMC-EC01 will be shown in the list of devices

DELTA CMC-EC01 Ethercat Communication Card - b18

6.2 Speed Mode Demo

■ In Configure mode, select PDO1 for TX/RX and then start mapping

DELTA CMC-EC01 Ethercat Communication Card - b19

■ Start test and modify speed

DELTA CMC-EC01 Ethercat Communication Card - b20

  1. Set “target velocity” = 1200 so that the target speed of the drive is 1200rpm.
  2. Set Control Word = 0xE, state machine of drive enters to Power Enable.
  3. Set Control Word = 0xF, state machine of drive enters to Operation Enable.
  4. Set Control Word = 0x7F, allowing the drive to reach the target frequency.
  5. Set vl target velocity = -1200, drive begins operating in reverse.
  6. Set Control Word = 0x5F, the drive stops at the current frequency.

Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com

CMC-EC01 Operation Manual

Documents / Resources

DELTA CMC-EC01 Ethercat Communication Card [pdf] Instruction Manual
CMC-EC01 Ether Cat Communication Card, CMC-EC01, Ether Cat Communication Card, Cat Communication Card, Communication Card

References

Leave a comment

Your email address will not be published. Required fields are marked *