THE TECHNICAL DATA OF THE VACON® 20 X AC DRIVE

Technical item or functionTechnical data
Mains connectionInput voltage Uin3AC 208…240V1AC 208…240V3AC 380…480V
Input voltage tolerance-15%…+10% continuously
Input frequency50/60 Hz
Input frequency tolerance45…66 Hz
Protection classI
Connection to mainsOnce per minute or less
Starting delay4 s
Supply networkIT and TN-networks(cannot be used with corner earthed networks)
Short-circuit currentMaximum short-circuit current has to be <50kA
DC connectionAvailable as standard inMU2 single-phase frames and MU3
Motor connectionOutput voltage3AC 0…Uin
Rated output currentIN: Ambient temperature max. +40°C
Overload output current1.5 x IN (1 min/10 min)
Starting currentIS for 2 s every 20 s (IS = 2.0 * IN)
Output frequency0…320 Hz
Frequency resolution0.01 Hz
Protection classI
Motor characteristicsAC squirrel cage motors Permanent magnet motors
Cable typeScreened motor cable
Cable maximum length30 m
Control characteristicsSwitching frequencyProgrammable 2…16 kHz; Default 6 kHz. Automatic switching frequency derating in case of overheating
Frequency reference: Analogue input Panel referenceResolution ±0.05% (11-bit),accuracy ±1% Resolution 0.01 Hz
Field weakening point8…320 Hz
Acceleration time0.1…3000 sec
Deceleration time0.1…3000 sec
BrakingBrake chopper standard in all three-phase frames. External brake resistor optional.

CABLE AND FUSE SIZES, NORTH AMERICA

The recommended fuse types are class T (UL & CSA). The fuse voltage rating should be selected according to the supply network. The final selection should be made according to local regulations, cable installation conditions and cable specifications. Bigger fuses than those recommended below shall not be used.

Check that the fuse operating time is less than 0.4 seconds. Operating time depends on used fuse type and impedance of the supply circuit. Consult the factory about faster fuses. VACON® also recommends for high speed J (UL & CSA) fuse ranges.

UL STANDARDS ON CABLING

To obey the UL (Underwriters Laboratories) regulations, use a UL-approved Class 1 copper wire with a minimum heat resistance of +158 or +167 °F (+70 or +75°C).

You can use the drive on a circuit that gives a maximum of 50 000 rms symmetrical amperes, and a maximum of 500 V AC, when the drive is protected by Class T and J fuses.

The dimensions of the cables must agree with the requirements of the UL508C.

  • The cables must be PVC-isolated.
  • The maximum ambient temperature is +104 °F (+40°C).
  • The maximum temperature of the cable surface is +158 or +167 °F (+70 or +75°C).
  • Use only cables with a concentric copper shield.
  • The maximum number of parallel cables is 9.

When you use parallel cables, make sure that you obey the requirements of the cross-sectional area and the maximum number of cables.

For important information on the requirements of the grounding conductor, see the UL508C.

For the correction factors for each temperature, see the instructions of the UL508C.

THE CABLE AND FUSE SIZES FOR VACON® 20 X IN NORTH AMERICA, MAINS VOLTAGE 208-240 V AND 380-500 V

Frame

TypeIL [A]Fuse (class T) [A]Mains and motor cable CuTerminal cable sizeMain terminal          Earth terminal
MU20004 20003 4 – 0004 44.33.2 – 4.06AWG14AWG24-AWG12AWG17-AWG10
0005 2 – 0007 20005 4 – 0006 46.8 – 8.45.6 – 7.310AWG14AWG24-AWG12AWG17-AWG10
0008 49.615AWG14AWG24-AWG12AWG17-AWG10
MU21-phase0004 28.320AWG14AWG24-AWG12AWG17-AWG10
0005 211.220AWG14AWG24-AWG12AWG17-AWG10
0007 214.125AWG14AWG24-AWG12AWG17-AWG10
MU30011 20009 413.411.515AWG14AWG20-AWG6AWG17-AWG10
0012 20012 414.214.920AWG12AWG20-AWG6AWG17-AWG10
0017 20016 420.620.025AWG10AWG20-AWG6AWG17-AWG10

THE TIGHTENING TORQUES OF CABLE TERMINALS

FrameTypeTightening torque Power and motor terminals[Nm]             lb-in.Tightening torque EMC grounding clamps[Nm]                   lb-in.Tightening torque Grounding terminals[Nm]         lb-in.
MU20003 4—0008 40004 2—0007 20.5—0.64.5—5.31.513.32.017.7
MU30009 4—0016 40011 2—0017 21.2—1.510.6—13.31.513.32.017.7

CABLE ENTRIES, MU2 AND MU3 INSTALLATIONS

Installation
Installation

TIGHTENING TORQUE OF NPT ADAPTERS TO METRIC THREADS CABLE ENTRIES

FrameThread male metricThread male NPTTightening torque[Nm]                           lb-in.
MU2M201/2”2.017.7
M253/4”4.035.5
MU3M253/4”4.035.5

NPT adapter order information
M20: ADEC M20-T12
M25: ADEM M25-T34

Download and read VACON® 20 X Installation Manual, wall-mounted drives at:

http://drives.danfoss.com/knowledge-center/ technical-documentation/

Company Logo

Documents / Resources

Danfoss VACON 20 X AC Drives [pdf] User Guide
VACON 20 X AC Drives, 20 X AC Drives, AC Drives
Danfoss VACON 20 X AC Drives [pdf] User Guide
MU2, MU3, VACON 20 X AC Drives, 20 X AC Drives, AC Drives

References

Leave a comment

Your email address will not be published. Required fields are marked *