Danfoss KP 98 Thermostat Type
Specifications:
- Thermostat Type: KP 98 (Cross ambient)
- Enclosure and Tightness: IP30 in accordance with EN 60529 / IEC 529
- Application: UL-requirements – 120 V a.c.: 16 FLA, 96 LRA; 240 V a.c.: 8 FLA, 48 LRA; 240 V d.c.: 12 W pilot duty
Product Usage Instructions
Thermostat (Cross Ambient = Adsorption Charged)
Fig. 1 – Component Identification
- Setting spindle, “OIL” (LT) – Setting of max. oil temperature
- Main arm
- Setting spindle, “HT” – Setting of max. high-pressure gas temperature
- Locking plate
Technical Data
- Function
The function at a rise or drop in temperature appears in Figs. 8 and 9. - Permissible Ambient Temperature (Thermostat Housing) -40 to 65 °C (up to 80 °C for a maximum of 2 hours)
- Max. Permissible Bulb Temperatures
- “OIL” sensor (060L113166): 150 °C
- “HT” bulb: 250 °C
- Enclosure and Tightness
- IP30 in accordance with EN 60529 / IEC 529
- This is achieved when the unit is mounted on a flat panel or a bracket that covers all open holes.
- Contact Load
Refer to the unit’s scale. - UL Application Requirements:
- 120 V a.c.: 16 FLA, 96 LRA
- 240 V a.c.: 8 FLA, 48 LRA
- 240 V d.c.: 12 W pilot duty
Mounting Instructions
- Bulb Placement
- Refer to Figs. 3, 4, and 6 for correct positioning.
- Mounting Brackets (Fig. 2)
- Two types of brackets with screws and washers (ordered separately).
- If using different screws, ensure they do not project more than 1.5 mm into the unit.
- Compressor Installation
- Fig. 3: Compressor with KP 98
- Fig. 4: Sensor fitted to tube
- Fig. 5: Clamp (ordered separately)
- Fig. 6: Bulb in pocket
- Fig. 7: Sensor pocket (ordered separately)
- Tip: Use heat-conducting paste (Code No. 041E0110) to improve heat transfer between bulb and pocket.
Electrical Connections
Fig. 8 – Wiring Warning
CAUTION: Disconnect power supply before wiring or servicing. Do not touch live parts with fingers or tools.
Cable Entry Options
- Fig. 9: Plastic entry (6–14 mm cable)
- Fig. 10: Pg 13.5 screwed cable connection with special nut (6–14 mm cable, ordered separately)
For 8–16 mm cable, use a standard Pg 16 connection.
Testing Procedure
Fig. 11 – Testing
- Tilt the main arm (3)
- Simultaneously press the “RESET” knobs
- Note: Only use the described testing method
Setting Instructions
Fig. 8 and 12 – Scale Definitions
- START: Starting temperature
- STOP: Stop temperature
- DIFF: Differential
Setting Max Temperatures
- Use “OIL” and “HT” scales
- “OIL” Differential: Fixed at 14 °C
- “HT” Differential: Fixed at 25 °C
Restart After Shutdown
- Press the “RESET” buttons
- Restart only occurs once the temperature drops by the set differential value
Locking and Sealing
- Fig. 13 and 14 – Locking Plate
Lock both “OIL” and “HT” spindles using the locking plate - Fig. 15 – Sealing Screw
Use sealing screw (ordered separately) if sealing is required
Danfoss A/S
- Climate Solutions
- danfoss.com
- +45 7488 2222
Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered, provided that such alterations can be made without changes to form, fit or function of the product.
All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.
FAQ
Q: How do I improve heat transfer from the sensor pocket to the bulb?
A: To improve heat transfer, use a heat conducting paste (Code No. 041E0110) when installing the sensor pocket.
Documents / Resources
![]() | Danfoss KP 98 Thermostat Type [pdf] Installation Guide KP 98 Thermostat Type, KP 98, Thermostat Type, Type |