Danfoss-EKE-1P-Stepper-Valve-Extension-Module-logo

Danfoss EKE 1P Stepper Valve Extension Module

Danfoss-EKE-1P-Stepper-Valve-Extension-Module-product-image

Identification

Danfoss-EKE-1P-Stepper-Valve-Extension-Module-(1)

Dimensions [mm]

Danfoss-EKE-1P-Stepper-Valve-Extension-Module-(2)

Application 1

Danfoss-EKE-1P-Stepper-Valve-Extension-Module-(3)

Application 2

Danfoss-EKE-1P-Stepper-Valve-Extension-Module-(4)

Danfoss-EKE-1P-Stepper-Valve-Extension-Module-(5)

Battery back-up

Danfoss-EKE-1P-Stepper-Valve-Extension-Module-(6)

Connection overview: EKE 1P

Danfoss-EKE-1P-Stepper-Valve-Extension-Module-(7)

Valve connection

CCMT/ETS/CCMETS 6EKE 1P
WhiteOrangeA1
BlackYellowA2
RedRedB1
GreenBlackB2

Application 1 driver configuration
AI4 open circuit or connected to 0V (COM): high-pressure valve driver
AI4 connected to 5V+: receiver valve driver

Recommended wire size and cable distance between EKE controller and stepper motor valve

Cable length1 – 15 m
Wire diameter0.52 / 0.33 mm2 (20 / 22 AWG)

Technical specifications

Power supply:
EKE has galvanic isolation by switch-mode power supply. 24 V AC ± 20 %, 50/60 Hz. Maximum power consumption: 18 VA. Input voltage rating (DC): 24 V DC ± 20%, 15 W.

I/OTypeNo.Specification
Analogue inputsMax. 15 V input voltage

Do not connect voltage sources to unpowered units without limiting the current to analogue inputs (overall 80 mA). Open circuit HW diagnostics available for voltage input on: AI4

 

Voltage

 

2

AI3*

0 – 5 V ratiometric

AI4

0 – 5 V, 0 – 10 V

PT10002AI1*, AI2*
Auxiliary Supplies 

1

5 V +

Sensor supply: 5 V DC / 15 mA, overload protection approximately 150 mA

Digital inputs 

Voltage free contacts

 

 

2

DI1*, DI2

Steady current minimum 1 mA Cleaning current 100 mA at 15 V DC On: RIL < = 300 Ω

Off: RIH > = 3.5 k Ω

 

Digital output

 

 

Relay

 

 

1

C1-NO1*

Normally Open: 3 A General purpose, 250 V AC, 100 k cycle Normally Open: 3 A Inductive (AC-15), 250 V AC, 100 k cycle Normally Closed: 2 A General purpose, 250 V AC, 100 k cycle

 

Stepper motor

 

 

 

Bipolar / unipolar

 

 

 

 

1

Stepper valves: A1, A2, B1, B2

Bipolar and unipolar stepper motor output:

  • Danfoss CCMT 3L – CCMT 8L / CCMT 0 – CCMT 42 / CCM 10 – CCM 40 / ETS 6 – ETS 400 / CTR 20
    Other valves:
  • speed 10 – 400 pps
  •  drive mode 1/8 microstep
  • max. peak phase current: 1.2 A (848 mA RMS)
  • max. drive voltage 40 V
  • max. output power 12 W
Battery backup 

1

VBATT: 18 – 24 V DC (24 V DC recommended):
  • max. battery current: 850 mA at 18 V
  • battery alarm will be activated below 16 V DC and above 27 V DC
Communication 

RS-485 RTU

 

1

RS-485*

Galvanic isolation

No built-in termination

 

CAN

 

1

CAN – RJ

Application 1: Connect directly to AK-PC

Application 2: Connect directly to graphical display, MMIGRS2. Activate the termination on the graphical display.

* Only used in application 1

LED indication:
Two sets of Light Emitting Diodes make it possible to follow the operation status of the valve and the controller.

Danfoss-EKE-1P-Stepper-Valve-Extension-Module-(8)

LED A: Two status LEDs indicate power and controller operation

Power-up:

Danfoss-EKE-1P-Stepper-Valve-Extension-Module-(9)

Normal operation:

Danfoss-EKE-1P-Stepper-Valve-Extension-Module-(10)

LED B: Two status LEDs to indicate valve operation

Danfoss-EKE-1P-Stepper-Valve-Extension-Module-(11)

Commonly used parameter identification in application 2

Note: In application 1, the most commonly used parameters are conÿgured in the AK-PC. Default commissioning password: “300”

ParameterDefaultDescription
Main switch00 = Off, 1 = ON
Mode00=Application 1 – selection by AI4

1=Application 1 – High Pressure expansion module 2=Application 1 – Receiver Expansion module 3=Application 2 – Valve Driver

Note: changing this setting also changes the EKE 1P address, causing communication with the graphical display to stop. Communication will resume after a power cycle.

AI valve input scale20 = 0 – 5 V
1 = 1 – 5 V
2 = 0 – 10 V
3 = 2 – 10 V
4 = 5 – 0 V
5 = 5 – 1 V
6 =10 – 0 V
7 =10 – 2 V
8 = User Defined
Valve configuration0Application mode 1: Set from AK-PC except if the valve type is set to User Defined in AK-PC then it is
according to below list (see Application mode 2)
Application mode 2:
0 = no valve, 1 = UserDef
2 = ETS 12C, 3 = ETS 24C, 4 = ETS 25C, 5 = ETS 50C, 6 = ETS 100C
7 = ETS 6, 8 = ETS 12.5, 9 = ETS 25, 10 = ETS 50, 11 = ETS 100
12 = ETS 250, 13 = ETS 400
14 = KVS 2C, 15 = KVS 3C, 16 = KVS 5C
17 = KVS 15, 18 = KVS 42
19 = CCMT 0, 20 = CCMT 1
21 = CCMT 2, 22 = CCMT 4, 23 = CCMT 8, 24 = CCMT 16, 25 = CCMT 24
26 = CCMT 30, 27 = CCMT 42
28 = CCM 10, 29 = CCM 20, 30 = CCM 30, 31 = CCM 40
32 = CTR 20
33 = CCMT 3L, 34 = CCMT 5L, 35 = CCMT 8L

Documents / Resources

Danfoss EKE 1P Stepper Valve Extension Module [pdf] Installation Guide
EKE 1P Stepper Valve Extension Module, Stepper Valve Extension Module, Extension Module, Module
Danfoss EKE 1P Stepper Valve Extension Module [pdf] User Guide
EKE 1P, 80G395, 80G396, EKE 1P Stepper Valve Extension Module, EKE 1P, Stepper Valve Extension Module, Valve Extension Module, Extension Module
Danfoss EKE 1P Stepper Valve Extension Module [pdf] Installation Guide
EKE 1P, 080R9344, 80G393, 80G394, 80G395, 80G396, 80G397, 80G398, EKE 1P Stepper Valve Extension Module, EKE 1P, Stepper Valve Extension Module, Valve Extension Module, Extension Module, Module
Danfoss EKE 1P Stepper Valve Extension Module [pdf] Installation Guide
EKE 1P, 080R9344, AN31542506734401-000201, EKE 1P Stepper Valve Extension Module, EKE 1P, Stepper Valve Extension Module, Valve Extension Module, Extension Module

References

Leave a comment

Your email address will not be published. Required fields are marked *