Instructions

Type AIT-U


Danfoss AIT-U Actuator For Temperature Control - 1

Danfoss AIT-U Actuator For Temperature Control - 2 Danfoss AIT-U Actuator For Temperature Control - 3
AIT-U / VIG 2               AIT-U / VIS 2

Actuator for temperature control AIT-U

www.danfoss.com


7369189-0                                VI.GB.A2.81

Safety Notes

Prior to assembly and commissioning, these Assembly, Start-up, and Maintenance Instructions must be read carefully and observed.

Necessary assembly, start-up, and maintenance work must only be performed by qualified, trained, and authorized personnel.

Prior to assembly and maintenance work at the temperature sensor without immersion pocket or at the immersion pocket, the system must be depressurized, cooled down and emptied.

Please comply with the instructions of the system manufacturer or system operator.

Warning Icon 197

Definition of Application

The actuator AIT-U is used for temperature control in combination with Danfoss valves and Danfoss controller combinations.

The controllers with the actuator AIT-U are type-tested acc. to DIN 3440 and comply with the safety requirements for temperature control and temperature limiting units in heat systems.

Mounting

Application system examples

Danfoss AIT-U Actuator For Temperature Control - 4     Danfoss AIT-U Actuator For Temperature Control - 5

Permissible Installation Positions

Danfoss AIT-U Actuator For Temperature Control - 6

AIT-U / VIG 2

—————————————————————

Danfoss AIT-U Actuator For Temperature Control - 7

AIT-U / VIS 2

Installation

1. Install strainer (1) before controller.

Danfoss AIT-U Actuator For Temperature Control - 8

2. Observe flow direction (2) on rating plate or valve.

Danfoss AIT-U Actuator For Temperature Control - 9

Design with welded end

(3) pin only
(4) weld

Danfoss AIT-U Actuator For Temperature Control - 10 Danfoss AIT-U Actuator For Temperature Control - 11

Danfoss AIT-U Actuator For Temperature Control - 12

3. Rinse system.

Actuator AIT-U Mounting

Before mounting the actuator, carry out the filling of the system and pressure tests, see page 9

Place actuator AIT-U at the valve or combination pise and tighten union nut with wrench SW36.

Torque 35 Nm

Danfoss AIT-U Actuator For Temperature Control - 13

Temperature Sensor Installation
  • The temperature sensor must be installed as shown on the picture.
  • The capillary tube may not be twisted or buckled. The minimum bending radius is 50 mm.
  • The place of installation must be chosen in such a way that the temperature of the medium is directly taken without any delay. Avoid overheating of temperature sensor
  • The temperature sensor must be immerged into the medium in its full length.

Danfoss AIT-U Actuator For Temperature Control - 14 Danfoss AIT-U Actuator For Temperature Control - 15 Danfoss AIT-U Actuator For Temperature Control - 16 Danfoss AIT-U Actuator For Temperature Control - 17

Application examples

Danfoss AIT-U Actuator For Temperature Control - 18

Dimensions

Danfoss AIT-U Actuator For Temperature Control - 19

ValveL by DN
TypeConnection152025324050
VIG 2Flange174180180210214214
VIG 2Thread174180180
VIS 2Thread247247247
Filling the System, Pressure Test

Valves VIG 2, VIS 2

Without actuator the valve is opened, therefore carry out filling the system and pressure tests only without mounted actuator.

Warning Icon 197

Danfoss AIT-U Actuator For Temperature Control - 20VIG 2, VIS 2

Danfoss AIT-U Actuator For Temperature Control - 21

Temperature Setting

The setpoint range is marked on the scale carrier.

Pre-conditions

  • The system must be open and the flow of the medium guaranteed.

Danfoss AIT-U Actuator For Temperature Control - 22

AIT-U
10-4535-7060-10085-125
Min10356085
114386491
2234978103
3325887113
4396595122
54671102129
Max4873129131
Procedure
  • Adjust to the desired setpoint by turning the setpoint adjuster (1).
    Turning to the left increases the setpoint (4).
    Turning to the right reduces the setpoint (5).
    The position of the setpoint adjuster on a scale value (2) means:
    1 lowest setpoint
    5 maximum setpoint
  • Observe temperature indicator.
  • Wait for about 3 to 5 Min. until the temperature indicator shows the final value.
  • If the device is used as a temperature monitor, the setpoint adjuster (1) must be secured by a sealing wire (3).

Danfoss AIT-U Actuator For Temperature Control - 23

Technical Data

Thermostat AIT-U

Setpoint range Xs°C10 – 45, 35 – 70, 60 – 100, 85 – 125
Time constant T 1)max. 30
Transmission coefficient Ksmm/°C 0.7
Max. perm. temperature at sensor°K50°K above adjusted setpoint
Perm ambient temperature at actuator and sensor°C-10 – 70
Nominal pressure on temperature sensorPN25
Connection pipe lengthm4
Temperature sensor materialCopper / Brass
Setpoint adjuster materialPolyamide glass fiber reinforced
Scale materialPolyamide
Massca. kg0,9

1) acc. to DIN 3440

Help
FaultPossible causeRemedy
Temperature too highValve does not close:
valve seat, plug or trim  is dirty or damaged
  1. Dismount actuator AIT-U
  2. Unscrew trim
  3. Clean seat and plug
  4. Replace trim or valve if damaged
Actuator, temperature sensor or connection stem does not extend
  1. Loosen union nut SW36 and remove actuator AIT-U
  2. Unscrew temperature sensor
  3. Replace actuator AIT-U sensor
Temperature too lowValve does not open:
trim dirty or damaged
  1. Dismount actuator AIT-U
  2. Unscrew trim
  3. Clean seat and plug 4.Replace trim or valve if damaged