Danfoss 134N3195 Automation Drive
Specifications
- Voltage: 3×400 V
- Power range: kW (hp)
Installation Instructions
Make sure to follow the specific installation instructions provided for your supplied variant of the FC 302 frequency converter.
Safety Instructions
WARNING:
Ensure to wait the specified minimum waiting time after power has been removed before performing any service or repair work to prevent serious injury or death due to residual voltage in the capacitors. Always use an appropriate voltage measuring device to confirm that capacitors are fully discharged.
Items Supplied
Depending on the ordering number, you will receive the FC 302 with either 2 or 4 motor connectors as specified in the illustrations.
Connectors Overview
The frequency converter comes with various connectors, including mains, motor, PROFIBUS, and I/O box connectors. Refer to Table 4.1 for detailed descriptions.
Wire/Connector Assignment
Refer to Tables 4.2 and 4.3 for wire/connector assignments for plug X1 and plug X2, respectively. Make sure to use the correct mating parts for connections.
Motor Connection Variants
- 2 Motor Connection Variant (134N3195): Keep blind plugs installed to maintain the protection rating. Refer to Table 4.4 for specific connections.
- 4 Motor Connection Variant (134N3196): Internal terminal connections are involved. Refer to Table 4.5 for detailed connections.
Introduction
NOTICE
- VLT® AutomationDrive FC 302 with connectors is not UL approved.
- The ETR functionality is not guaranteed.
- Enclosure protection rating: IP55.
Safety Instructions
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not powered. High voltage can be present even when the warning LED indicator lights are off. Failure to wait the specified time after power has been removed before performing service or repair work can result in death or serious injury.
- Stop the motor.
- Disconnect AC mains and remote DC-link power supplies, including battery back-ups, UPS, and DC-link connections to other frequency converters.
- Disconnect or lock the PM motor.
- Wait for the capacitors to discharge fully. The minimum duration of waiting time is specified in Table 2.1.
- Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors are fully discharged.
Voltage [V] | Power range [kW (hp)] | Minimum waiting time (minutes) |
3×400 | 0.55–7.5 (0.75–10) | 4 |
Items Supplied
Depending on the ordering number, the following is supplied:
FC 302 with 2 motor connectors (134N3195)
FC 302 with 4 motor connectors (134N3196)
FC 302 with MCO – mains connectors and 4 cable glands (134N8410)
FC 302 with connectors – side view
NOTICE
See the VLT® AutomationDrive FC 301/FC 302 Design Guide for dimensions and further information.
Connectors
Overview
The frequency converter has 7 connectors plus 2 or 4 motor connectors.
Label | Connector | Description |
X1 | Mains | Mains in M23 (in M25) Male |
X2.1-X2.4 | Motor | Motor connection M23 Female |
X51 | PROFIBUS – Male | PROFIBUS M12 |
X52 | PROFIBUS – Female | PROFIBUS M12 |
X11-X14 | I/O box connector | Phoenix I/O box |
Table 4.1 Connectors
X1- Mains M23 (in M25) Male
General ratings
- Pins 1, 2, 3, and 4: 480 V AC, maximum 15 A.
- Pins C and D: 30 V DC, maximum 3 A.
- Tightening torque: 1.5–2.0 Nm (13.3–17.7 in-lb)
Pin | Label | Connected to the frequency converter wiring schematic | Minimum wire [mm2 (AWG)] |
1 | T1 | 91 (L1) | 2.5 (14) |
4 | T2 | 92 (L2) | 2.5 (14) |
3 | T3 | 93 (L3) | 2.5 (14) |
2 | PE | 95 (PE) | 2.5 (14) |
D | 0 V DC | 35 | 0.75 (18) |
C | 24 V DC | 36 | 0.75 (18) |
Table 4.2 Wire/Connector Assignment for Plug X1
- Mating part: Mains X1 (female)
- Phoenix ordering number: KK-0885/XX,XX
X2.1–X2.4 Motor Connectors M23 (in M25) Female
General ratings
- Pins 1, 2, 3, and 4: 480 V AC, maximum 15 A.
- Pins C and D: 30 V DC, maximum 3 A.
- Tightening torque: 1.5–2.0 Nm (13.3–17.7 in-lb).
Pin | Label | Connected to the frequency converter wiring schematic | Minimum wire [mm2 (AWG)] |
1 | U | 96 (U) | 2.5 (14) |
3 | V | 97 (V) | 2.5 (14) |
4 | W | 98 (W) | 2.5 (14) |
2 | PE | 99 (PE) | 2.5 (14) |
Table 4.3 Wire/Connector Assignment for Plug X2
- Mating part: Motor X2 (male)
- Phoenix ordering number: KCX-K0341/XX, XX Maximum cable length: 7.0 m (23 ft)
2 Motor Connection Variant (134N3195)
To meet the protection rating, always keep blind plugs installed.
Label | Connected to the frequency converter wiring schematic |
X2.1-B | 53 |
X2.2-A | 50 |
X2.1-A and X2.2-B | Connected to a common terminal |
X2.1-C and X2.2-C | Connected to an open terminal available in the frequency converter |
X2.1-D and X2.2-D | Connected to an open terminal available in the frequency converter |
Table 4.4 2 Motor Connection
4 Motor Connection Variant (134N3196)
Label | Connected to the frequency converter wiring schematic |
X2.1-B | 53 |
X2.4-A | 50 |
X2.1-A and X2.2-B | Connected via an internal terminal |
X2.2-A and X2.3-B | Connected via an internal terminal |
X2.3-A and X2.4-B | Connected via an internal terminal |
Table 4.5 4 Motor Connection
X51 PROFIBUS M12 Male, X52 PROFIBUS M12 Female
General ratings
- 30 V DC, maximum 1 A.
- Tightening torque: 0.2–0.3 Nm (1.8–2.7 in-lb)
Label | Connected to the frequency converter PROFIBUS connector | |
1 | 5 V DC | 67 |
2 | – | 63 |
3 | 0 V DC | 66 |
4 | – | 62 |
Table 4.6 PROFIBUS Connection
- Mating part: PROFIBUS X52 and X51 (female/male)
- Phoenix ordering number: SAC-2P-MSB/ XX,XX-910/FSB SCO CT
X11–X14 I/O Connector Box (134N3195–134N3196)
Phoenix sensor/actuator box – SACB-4/4-L-0,57HPUR CDA -1531426.
Tightening torque sensor/actuator cable: 0.4 Nm (3.5 in-lb).
Label | Wire | Connected to the frequency converter wiring schematic | |
X11-X14 1 | Brown | 12 | +24 V Out |
X11-X14 2 | |||
X11-X14 3 | Blue | 20 | COM D IN |
X14-4 | Gray | 33 | D IN |
X13-4 | Yellow | 29 | D IN/OUT |
X12-4 | Green | 19 | D IN |
X11-4 | White | 18 | D IN |
Table 4.7 Connector Box (134N3195–134N3196)
X11–X14 I/O Connector Box (134N8410)
Phoenix sensor/actuator box – SACB-4/4-L-0,57HPUR CDA -1531426.
Tightening torque sensor/actuator cable: 0.4 Nm (3.5 in-lb)
Label | Wire | Connected to the wiring schematic | ||
X11-X14 1 | Brown | Connected to the frequency converter wiring schematic | 12 | +24 V Out |
X11-X14 2 | ||||
X11-X14 3 | Blue | 20 | COM D IN | |
X14-4 | Gray | Connected to the C- option, MCO 305 wiring schematic | X57-4 | – |
X13-4 | Yellow | X57-3 | – | |
X12-4 | Green | X57-2 | – | |
X11-4 | White | X57-1 | – |
Table 4.8 Connector Box (134N8410)
Overview of Marking and Cable Glands (134N8410)
Marking | Type of cable gland | Allowed cable diameter [mm (in)] |
Encoder | EMC M20x1,5 7.5–14.0 | 7.5–14.0 (0.3–0.55) |
Motor | EMC M25x1,5 10.0–18.0 | 10.0–18.0 (0.4–0.7) |
Brake | EMC M20x1,5 7.5–14.0 | 7.5–14.0 (0.3–0.55) |
I/O | M25x1.5 50.625 (plastic RAL 7035) | 11–16 (0.45–0.6) |
Table 4.9 Cable Glands (134N8410)
Installation
- NOTICE
For installation, refer to the VLT® AutomationDrive FC 301/FC 302 Operating Instructions. - NOTICE
For installation of 134N8410 FC 302 with MCO, also refer to the VLT® Motion Control Option MCO 305 Operating Instructions.
FAQ
Q: How long should I wait after removing power before servicing the frequency converter?
A: The minimum waiting time specified is 4 minutes, as indicated in Table 2.1.