Danfoss logo

Danfoss 084B4082 AK-CC55 Single Coil Case Controller

Danfoss 084B4082 AK-CC55 Single Coil Case Controller

Identification

Danfoss 084B4082 AK-CC55 Single Coil Case Controller 1

Dimensions

Danfoss 084B4082 AK-CC55 Single Coil Case Controller 2

Principle

Danfoss 084B4082 AK-CC55 Single Coil Case Controller 3

The controller is provided with labels from the factory indicating a generic application. When selecting the required application, specific labels are provided so that you can mount the relevant one.

Danfoss 084B4082 AK-CC55 Single Coil Case Controller 4

Danfoss 084B4082 AK-CC55 Single Coil Case Controller 5 Danfoss 084B4082 AK-CC55 Single Coil Case Controller 6 Danfoss 084B4082 AK-CC55 Single Coil Case Controller 7

Data communication

Danfoss 084B4082 AK-CC55 Single Coil Case Controller 8

It is important that the installation of the data communication cable is performed correctly with sufficient distance to high voltage cables.

AKV info

Danfoss 084B4082 AK-CC55 Single Coil Case Controller 9

AKS 32R info

Danfoss 084B4082 AK-CC55 Single Coil Case Controller 10

The signal from one pressure transmitter can be received by up to 10 controllers. There must not be a significant pressure drop from the pressure transmitter’s position in the suction line to the individual evaporators.

Coordinated defrost via cable connections

Danfoss 084B4082 AK-CC55 Single Coil Case Controller 11

Max. 10 The following controllers can be connected in this way: EKC 204A, AK-CC 210, AK-CC 250, AK-CC 450, AK-CC 550 and AK-CC55. Refrigeration is resumed at the same time when all controllers have terminated defrost.

External display AK-UI55

Danfoss 084B4082 AK-CC55 Single Coil Case Controller 12

Display: 084B4075 / 084B4076 / 084B4077
Cable 3 m: 084B4078 Cable 6 m: 084B4079

Technical data

Electrical specifications

Electrical dataValue
Supply voltage AC [V]115 V / 230 V, 50/60 Hz
Power consumption [VA]5 VA
Power ON indicatorGreen LED
Electrical cable dimensioning [mm2]Max. 1.5 mm2 multi-core cable

Sensor and measuring data

Sensor and measuring dataValue
Sensor S2, S6Pt 1000 AKS11
Sensor S3, S4, S5Pt 1000 AKS11

PTC 1000 EKS111 NTC5K EKS211

NTC10K EKS221 sensor

(All 3 must be of the same type)

Temperature measuring accuracyPt1000: -60 – 120 °C. ±0.5 K

PTC1000: -60 – 80 °C. ±0.5 K

NTC5K: -40 – 80 °C. ±1.0 K

NTC10K: -40 – 120 °C. ±1.0 K

Pt1000 sensor specification±0.3 K at 0 °C

±0.005 K per degree

Pe measuringAKS 32R Ratiometric pressure transmitter: 10 – 90%
RH measuring0 – 10 V

Ri > 10K ohm Accuracy +/- 0,3% FS

Input and output relay specifications

Input and output relay specificationsInput/ outputDescription
Digital inputDI1 DI2Signal from dry contact functions Requirements to contacts: Gold plating Cable length must be max. 15 m

Use auxiliary relays when the cable is longer Open loop: 12 V (SELV)

Contact 3.5 mA

Digital inputDI3115 V / 230 V AC
Solid state outputDO1 (for AKV coil)115V / 230 V AC Max. 0.5 A

Max. 1 x 20 W AKV for 115 V AC 2 x 20 W AKV for 230 V AC

Note: 2 EC coils are not supported.

RelaysDO2 DO3 DO4 DO5 DO6115 V / 230 V AC

Load max.: CE. 8 (6)A UL. 8A res. 3FLA 18LRA

Load min.: 1VA

Inrush: DO5 DO6 TV-5 80A

Analogue output/ PWMAO10 / 10 V Pulse Width Modulated (PWM) max. 15 mA.

0 – 10 V variable, max. 2 mA

NOTE:

  •  DO2 to DO6 are 16 A relays.
  • Max. load must be observed.
  •  DO5 / DO6 is recommended for load with high inrush current e.g. EC Fan and LED light.
  •  All relays are sealed for use with flammable refrigerant like Propane R290.
  • Compliance with EN 60 335-2-89: 2010 Annex BB.

Function data

Function dataValue
DisplayLED 3 digit
External display, AK-CC55 Single Coil UI1 external display
External display, AK-CC55 Single Coil2 external displays
External display connectionRJ12
Max. display cable length [m]100 m
Data communication built-inMODBUS
Data communication optionAK-OB55 Lon RS485 module (Not AK-CC55 Compact)
Clock battery backup power reserve4 days
MountingDIN rail

Environmental conditions

Environmental conditionsValue
Ambient temperature range, operating [°C]0 – 55 °C
Ambient temperature range, transport [°C]-40 – 70 °C
Enclosure rating IPIP20
Relative humidity range [%]20 – 80%, non-condensing
Shocks/VibrationsNo shocks and vibrations allowed

Electric noise

Cables for sensors, low voltage DI inputs and data communication must be kept separate from other electric cables:

  • Use separate cable trays
  • Keep a distance between cables of at least 10 cm
  • Long cables at the low voltage DI input should be avoided

Installation considerations

Accidental damage, poor installation, or site conditions, can give rise to malfunctions of the control system, and ultimately lead to a plant breakdown. Every possible safeguard is incorporated into our products to prevent this. However, a wrong installation could still present problems. Electronic controls are no substitute for normal, good engineering practice. Danfoss will not be responsible for any goods, or plant components, damaged as a result of the above defects. It is the installer’s responsibility to check the installation thoroughly, and to fit the necessary safety devices. Special reference is made to the necessity of signals to the controller when the compressor is stopped and to the need of liquid receivers before the compressors. Your local Danfoss agent will be pleased to assist with further advice, etc.

Replacing AK-CC 550A with AK-CC55

Be aware when exchanging an AK-CC 550A controller with a new AK-CC55 controller – new wiring principles!

  • Pressure sensor has new connection – signal and ground are switchedDanfoss 084B4082 AK-CC55 Single Coil Case Controller 13
  • SPDT relays have a new wiring scheme – NO and NC terminals are switched (e.g. defrost heater on when it should be off)Danfoss 084B4082 AK-CC55 Single Coil Case Controller 14
  • Modbus has new connection scheme (A,B and screen)Danfoss 084B4082 AK-CC55 Single Coil Case Controller 15
  • New AK-UI55 displays and cables with 6 wires vs. 4 wires for EKA 16xDanfoss 084B4082 AK-CC55 Single Coil Case Controller 16

AK-CC55 does not support two EEC coils connected to one AKV output. Pressure transmitter can be shared between AK-CC 550 and AK-CC55. DI2 defrost coordination can be wired between AK-CC 550 and AK-CC55.

Operation with setting display

Display AK-UI55 Set
The values will be shown with three digits, and with a setting you can determine whether the temperature is to be shown in °C or in °F.

Danfoss 084B4082 AK-CC55 Single Coil Case Controller 17

The display can give the following messages:

  • Defrost is in progress
  • The temperature cannot be displayed due to a sensor error
  • The display cannot load data from the controller. Disconnect and then reconnect the display
  • Lost display communication
  • The alarm button is activated. The first alarm code is then shown
  • At top position of the menu or when max. value has been reached, the three dashes are shown in the top of the display At bottom position of menu or when min. value has
  • been reached, the three dashes are shown in the bottom of the display The configuration is locked. Unlock by pressing (for 3 seconds) on the ‘up arrow’ and ‘down arrow’
  • simultaneously
  • The configuration is unlocked
  • The parameter has reached min. or max. limit
  • A password is required for access to the menu
  • Appliance cleaning has been initiated. The fans are running
  • Appliance cleaning is activated and the appliance can now be cleaned
  • The main switch is set to Off
  • The main switch is set to service / manual operation
  • Flashes: Will display in event of a refrigerant leakage alarm, but only if the refrigerant is set up for CO2

Factory setting

If you need to return to the factory-set values, do the following:

  • Cut off the supply voltage to the controller
  • Keep up “∧” and down “∨” arrow buttons depressed at the same time as you reconnect the supply voltage
  • When FAc is shown in the display, select “yes”.

Parameter grouping at display operation

 SET 
Set
(PS)<
 cFgSET
< 
r–Menu groups

See also the following pages.

A–
c–
d–
n–
F–
t–
h–
o–
p–
q–
u–
< 
r12Main switch
o61Application
o03MODBUS address
r89Food type
r00Cut-out temperature
r15Ther. sensor S4 %
r61Ther. sensor S4% night
A36Alarm sensor S4%
o17Display air S4%
o30Refrigerant type
o20Min. transmitter range
o21Max. transmitter range
d01Defrost method
d03Defrost interval
d10Defrost sensor
d04Max. defrost time
d02Defrost stop temperature
< 
<Info button,

3 s: Information for service use

Inf
StASETSee control state message

See selected application

AppSET
inSET di1/ AI7**Read input status
outSET do1AkvRead output status di2**
buSSETMODBUS quality

See SW version

do2*di3**
SoFSETdo3*AI1PE
< do4*AI2S2
(Return)

 

Output status

When you want info on a relay

do5*AI3S3
do6*AI4S4
Ao1*AI5S5
output, the dot will show                                       (Return)

whether the relay is activated

(energized) for, e.g.:

AI6**
< 

Get a good start

With the following procedure you can start regulation very quickly:

  1. Open parameter r12 and stop the regulation (in a new and not previously set unit, r12 will already be set to 0 which means stopped regulation)
  2.  Select application based on the wiring diagrams on pages 2-4
  3. Open parameter o61 and set the application number
  4. For network. Set the address in o03
  5. Then select a set of presets from the “Food type” help table
  6. Open parameter r89 and set the number for the array of presettings. The few selected settings will now be transferred to the menu
  7. Set the desired cut-out temperature r00
  8. Set the weighted thermostat air temperature between S4 and S3 sensor r15
  9. Set the weighted thermostat air temperature between S4 and S3 during night operation r61
  10. Set the weighted alarm air temperature between S4 and S3 A36
  11. Set the weighted display readout between S4 and S3 o17
  12. Select refrigerant via parameter o30
  13. Set the pressure transmitter min. and max. range via parameter o20 and o21
  14. Set the desired defrost method in d01
  15.  Set the interval time between defrost starts in d03
  16. Set the desired defrost sensor in d10
  17. Set the maximum defrost time in d04
  18. Set the defrost stop temperature in d02
  19. Open parameter r12 and start the regulation
  20.  Go through the parameter list and change the factory values where needed.
  21. Get the controller up and running on network:
    • MODBUS: Activate scan function in system unit
    • If another data communication card is used in the controller:
      • Lon RS485: Activate the function o04
      • Ethernet: Use the MAC address

Food type

Setting of presettings (r89). After setting 1-5,

setting is returned to 0.

Food type =

1

 

Vege- tables

2

 

Milk

3

 

Meat/ fish

4

 

Frozen food

5

 

Ice cream

Temperature (r00)8 °C0 °C-2 °C-20 °C-24 °C
Max. temp. setting (r02)10 °C4 °C2 °C-16 °C-20 °C
Min. temp. setting (r03)4 °C-4 °C-6 °C-24 °C-28 °C
Upper alarm limit (A13)14 °C8 °C8 °C-15 °C-15 °C
Lower alarm limit (A14)0 °C-5 °C-5 °C-30 °C-30 °C
Upper alarm limit for S6 (A22)14 °C8 °C8 °C-15 °C-15 °C
Lower alarm limit for S6 (A23)0 °C-5 °C-5 °C-30 °C-30 °C

Fault message

Fault message
In an error situation the alarm LED on the front will be on and the alarm relay will be activated (depending on priority).

If you push the alarm button for 3 seconds you can see the alarm report in the display. (Alarm priorities can be changed. See the User Guide.) Here are the messages that may appear:

CodeAlarm textDescription
E01Hardware failureThe controller has a hardware failure
E06Clock lost timeClock has lost valid time
E20Pe Evap. pressure A – Sensor errorSensor signal is out of range. Please check the sensor for correct operation
E24S2 Gas outlet A – Sensor errorSensor signal is out of range. Please check the sensor for correct operation
E25S3 Air ON evap. A – Sensor errorSensor signal is out of range. Please check the sensor for correct operation
E26S4 Air OFF evap. A – Sensor errorSensor signal is out of range. Please check the sensor for correct operation
E27S5 Evaporator A – Sensor errorSensor signal is out of range. Please check the sensor for correct operation
E28S6 product temp. A – Sensor errorSensor signal is out of range. Please check the sensor for correct operation
E34S3 Air ON evap. B – Sensor errorSensor signal is out of range. Please check the sensor for correct operation
E37S5 Evaporator B – Sensor errorSensor signal is out of range. Please check the sensor for correct operation
E59Humidity sensor – Sensor errorSensor signal is out of range. Please check the sensor for correct operation
A01High temperature alarm AThe alarm temperature has been above the max alarm limit for a longer time period than the set alarm delay.
A02Low temperature alarm AThe alarm temperature has been below the min alarm limit for a longer time period than the set alarm delay.
A04Door open alarmThe door has been open for a too long time
A05Max defrost hold time exceededThe controller has been waiting longer time than permitted after a co-ordinated defrost.
A11Refrigerant not selectedThe refrigerant has not been selected hence control can not be initiated
A13S6 high product temperature AThe S6 Product temperature has been above the max alarm limit for a longer time period than the set alarm delay.
A14S6 low product temperature AThe S6 Product temperature has been below the min alarm limit for a longer time period than the set alarm delay.
A15DI alarm 1Alarm signal from digital input signal
A16DI alarm 2Alarm signal from digital input signal
A45Main switch set OFFThe controller manin switch has been set to either Stop or Manaual control. Alternatively a digital input set up for “main switch” function, has stopped control
A59Case in cleaning modeA case cleaning operation has been started on a case
A70High temperature alarm BThe alarm temperature has been above the max alarm limit for a longer time period than the set alarm delay.
A71Low temperature alarm BThe alarm temperature has been below the min alarm limit for a longer time period than the set alarm delay.
AA2CO2 leak detectedCO2 is leaking from the refrigerantion system
AA3Refrigerant leak detectedRefrigerant is leaking from the refrigeration system
a02High humidity alarmThe humidity level is too high
a03Low humidity alarmThe humidity level is too low
a04Wrong IO configurationInputs and outputs have not been configured correctly
X02Evaporator is icing upThe adaptive defrost function has detected heavy ice formation on evaporator.
X03Flash gas detectedThe adaptive defrost function has detected heavy flash gas in front of injection valve
Z01Max defrost time exceeded AThe last defrost cycle has stopped on time instead of set temperature
A34Fan alarmAlarm from digital input monitoring function
A43Valve driver alarmAlarm from digital input monitoring function
Data communication: The importance of individual alarms can be defined with a setting. The setting must be carried out in the group “Alarm destinations”

Documents / Resources

Danfoss 084B4082 AK-CC55 Single Coil Case Controller [pdf] Installation Guide
084B4082, AK-CC55 Single Coil Case Controller, Single Coil Case Controller, Coil Case Controller, 084B4082, Case Controller

References

Leave a comment

Your email address will not be published. Required fields are marked *