BANNER logoR95C 8-Port Analog In to IO-Link
Hub Instruction Manual

Features

BANNER R95C 8 Port Analog In to IO Link Hub - Features

  • Compact analog to IO-Link device converter that connects to an analog source and outputs the value to the IO-Link master
  • Ability to represent one of the eight analog inputs as a PFM output
  • Rugged over-molded design meets IP65, IP67, and IP68
  • Connects directly to a sensor or anywhere in-line for ease of use
  • R95C IO-Link hubs are a quick, easy, and economical way to integrate non-IOLink devices into an IO-Link system

Models

BANNER R95C 8 Port Analog In to IO Link Hub - Models

Overview

When an analog input value is received by the R95C-8UI-KQ hub, the numerical representational value is sent to an IO-Link Master via Process Data In (PDI).

PDI Analog Ranges
Voltage = 0 mV to 10,000 mV
Current = 4,000 µA to 20,000 µA

PFM Out
Enables a PFM representation of an analog input as an output

PFM Input Source Channel
Selects the analog input value from Port 1..8 as the PFM out-put source

Pulse Frequency Configuration
Sets the near and far frequency values

Configuration

For more information, see P/N 232874 R95C-8UI-KQ IO-Link Data Reference Guide and P/N 232873 R95C-8UI-KQ IODD Files.
IO-Link®
IO-Link® is a point-to-point communication link between a master device and a sensor and/or light. It can be used to automatically parameterize sensors or lights and to transmit process data. For the latest IO-ink protocol and specifications, please visit www.io-link.com.

For the latest IODD files, please refer to the Banner Engineering Corp website at: www.bannerengineering.com.

Mechanical Installation

Install the R95C to allow access for functional checks, maintenance, and service or replacement. Do not install the R95C in such a way to allow for intentional defeat.
Fasteners must be of sufficient strength to guard against breakage. The use of permanent fasteners or locking hardware is recommended to prevent the loosening or displacement of the device. The mounting hole (4.5 mm) in the R95C accepts M4 (#8) hardware.
See the figure below to help in determining the minimum screw length.

BANNER R95C 8 Port Analog In to IO Link Hub - MOUNTING SCREW

warning 2 CAUTION: Do not overtighten the R95C’s mounting screw during installation. Overtightening can affect the performance of the R95C.

Wiring

Port 1-Port 8 — FemalePinSignal Description
BANNER R95C 8 Port Analog In to IO Link Hub - Wiring 1118 V DC to 30 V DC
2Analog In
3Ground
4Not Used
MalePinSignal Description
BANNER R95C 8 Port Analog In to IO Link Hub - Wiring 2118 V DC to 30 V DC
2Banner-specific/PFM out
3Ground
4IO-Link

Status Indicators

The R95C 8-Port Analog In to IO-Link Hub has matching amber LED indicators on both sides for each analog in port to allow for installation needs and still provide adequate indication visibility. There is also an additional amber LED indicator on both sides of the converter, which is specific to the IO-Link communication.

BANNER R95C 8 Port Analog In to IO Link Hub - Status Indicators

Power Indicator Green LED
IndicationStatus
OffPower off
Solid GreenPower on
Power Indicator Green LED
IndicationStatus
OffPower off
Solid GreenPower on
Analog In Amber LED
IndicationStatus
OffAnalog current value is less than setpoint SP1 OR analog value is greater than setpoint SP2
Solid AmberAnalog current value is between setpoint SP1 AND setpoint SP2
Default Current Values:
• SP1 = 0.004 A
• SP2 = 0.02 A
Default Voltage Values:
• SP1 = 0 V
• SP2 = 10 V

Specifications

Supply Voltage
18 V DC to 30 V DC at 400 mA maximum
Power Pass-Through Current
500 mA per port maximum
Analog Input Impedance
Current version: Approximately 250 ohms
Voltage version: Approximately 14.3K ohms
Supply Protection Circuitry
Protected against reverse polarity and transient voltages
Leakage Current Immunity
400 µA
Indicators
Green: Power
Amber: IO-Link communications
Amber: Analog In status
Connections
(8) Integral 4-pin M12 female quick-disconnect connector
(1) Integral 4-pin M12 male quick-disconnect connector
Construction
Coupling Material: Nickel-plated brass
Connector Body: PVC translucent black
Vibration and Mechanical Shock 
Meets IEC 60068-2-6 requirements (Vibration: 10 Hz to 55
Hz, 0.5 mm amplitude, 5 minutes sweep, 30 minutes dwell)
Meets IEC 60068-2-27 requirements (Shock: 15G 11 ms duration, half sine wave)

Certifications

CE SYMBOLBanner Engineering BV
Park Lane, Culliganlaan 2F bus 3
1831 Diegem, BELGIUM
Uk CA SymbolTurck Banner LTD Blenheim House
Blenheim Court
Wickford, Essex $S11 8YT
GREAT BRITAIN

BANNER R95C 8 Port Analog In to IO Link Hub - Symbol 1

Product Identification

BANNER R95C 8 Port Analog In to IO Link Hub - logo 2

Environmental Rating
IP65, IP67, IP68
NEMA/UL Type 1
Operating Conditions
Temperature: –40 °C to +70 °C (–40 °F to +158 °F)
90% at +70 °C maximum relative humidity (non-condensing)
Storage Temperature: –40 °C to +80 °C (–40 °F to +176 °F)
Required Overcurrent Protection

warning 2 WARNING: Electrical connections must be made by qualified personnel in accordance with local and national electrical codes and regulations.

Overcurrent protection is required to be provided by end product application per the supplied table.
Overcurrent protection may be provided with external fusing or via Current Limiting, Class 2 Power Supply.
Supply wiring leads < 24 AWG shall not be spliced.
For additional product support, go to www.bannerengineering.com.

Supply Wiring (AWG)Required Overcurrent Protection (A)Supply Wiring (AWG)Required Overcurrent Protection (A)
205.0261.0
223.0280.8
241.0300.5

FCC Part 15 Class B
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

Industry Canada ICES-003(B)
This device complies with CAN ICES-3 (B)/NMB-3(B). Operation is subject to the following two conditions: 1) This device may not cause harmful interference; and 2) This device must accept any interference received, including interference that may cause undesired operation.

Dimensions

All measurements are listed in millimeters [inches], unless noted otherwise.

BANNER R95C 8 Port Analog In to IO Link Hub - Dimensions

Accessories

Cordsets

4-Pin Threaded M12 Cordsets—Double Ended 
Model  Length  Style  Dimensions  Pinout 
 MQDEC-401SS0.31 m (1 ft)Male Straight/Female
Straight
BANNER R95C 8 Port Analog In to IO Link Hub - Dimensions 2FemaleBANNER R95C 8 Port Analog In to IO Link Hub - FemaleMale
BANNER R95C 8 Port Analog In to IO Link Hub - Male1 = Brown
2 = White
3 = Blue
4 = Black
 MQDEC-403SS0.91 m (2.99 ft)
 MQDEC-406SS1.83 m (6 ft)
 MQDEC-412SS3.66 m (12 ft)
 MQDEC-420SS6.10 m (20 ft)
 MQDEC-430SS9.14 m (30.2 ft)
 MQDEC-450SS15.2 m (49.9 ft)

Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment.
Banner Engineering Corp. will repair or replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period. This warranty does not cover damage or liability for misuse, abuse, or the improper application or installation of the Banner product.

THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement.  IN NO EVENT SHALL BANNER ENGINEERING CORP. BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product previously manufactured by Banner Engineering Corp. Any misuse, abuse, or improper application or installation of this product or use of the product for personal protection applications when the product is identified as not intended for such purposes will void the product warranty. Any modifications to this product without prior express approval by Banner Engineering Corp will void the product warranties. All specifications published in this document are subject to change; Banner reserves the right to modify product specifications or update documentation at any time. Specifications and product information in English supersede that which is provided in any other language. For the most recent version of any documentation, refer to: www.bannerengineering.com.

For patent information, see www.bannerengineering.com/patents.

November 2, 2023
© Banner Engineering Corp. All rights reserved.BANNER logo

Documents / Resources

BANNER R95C 8 Port Analog In to IO Link Hub [pdf] Instruction Manual
R95C 8 Port Analog In to IO Link Hub, R95C, 8 Port Analog In to IO Link Hub, Analog In to IO Link Hub, IO Link Hub
BANNER R95C 8-Port Analog In to IO-Link Hub [pdf] Instruction Manual
R95C 8-Port Analog In to IO-Link Hub, R95C, 8-Port Analog In to IO-Link Hub, Analog In to IO-Link Hub, IO-Link Hub, Hub

References

Leave a comment

Your email address will not be published. Required fields are marked *