SmartGen MGC100 Genset Controller

SmartGen MGC100 Genset Controller-FIG1

SmartGen — make your generator smart
SmartGen Technology Co., Ltd.
No.28 Jinsuo Road
Zhengzhou
Henan Province
P. R. China
Tel: +86-371-67988888/67981888/67992951 +86-371-67981000 (overseas)
Fax: +86-371-67992952
Web: www.smartgen.com.cn/ www.smartgen.cn/
Email: sales@smartgen.cn

All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder.
Applications for the copyright holder’s written permission to reproduce any part of this publication should be addressed to SmartGen Technology at the address above.
Any reference to trademarked product names used within this publication is owned by their respective companies.
SmartGen Technology reserves the right to change the contents of this document without prior notice.

Table 1 Version Hsitory

DateVersionContent
2015-06-291.0Original release.
 

 

 

2016-12-12

 

 

 

1.1

1.  Modify AC default, over speed threshold, crank disconnect conditions, crank disconnect speed, safety running delay and programmable outputs default ;

2.  Add gen under/over frequency protection functions;

3.   Add gen under/over frequency threshold and under/over frequency shutdown delay parameter.

4.  Programmable output ports add “Air Flap Choke” function

2022-07-221.2Update company logo and manual format.
   

Table 2 Notation Clarification

SignInstruction
NOTEHighlights an essential element of a procedure to ensure correctness.
 

CAUTION!

Indicates a procedure or practice, which, if not strictly observed, could result in

damage or destruction of equipment.

 

 

WARNING!

Indicates a procedure or practice, which could result in injury to personnel or loss of life if not followed correctly.

OVERVIEW

MGC100 Genset Controller is designed for start and protection of single genset. It allows manual and remote start/stop, data measurement, alarm indication, shutdown protection functions. The controller fit with LED display, button-press operation, and it achieves precise measurement of various parameters, protection and control of genset. All of parameters can be configured from front panel. The controller which can be widely used in data display and fault protection of a number of small diesel and petrol genset with easy operation, reliable work, compact structure and simple connections.

PERFORMANCE AND CHARACTERS

  • Multifunctional Nixie tube display, press button to operate;
  • Switchable displayed battery:
    • Generate voltage V
    • Generate frequency Hz
    • Accumulated running time (maximum is 9999h) H
    • Battery voltage V
  • There is a red LED on the panel for displaying working and alarm status;
  • Chose to control Petrol Genset or Diesel Genset via connection;
  • Suitable for 3-phase 4-wire, 3-phase 3-wire, 2-phase 3-wire, single phase 2-wire (120V/240V)
  • systems with frequency 50/60/Hz;
  • Protection function for gen under/over volt, over speed, fail to stop, emergency stop, high water temp, low oil pressure; when in protection, LED indicates alarm, and goes shutdown protection;
  • Generator rotate speed can derive from gen frequency or speed sensor;
  • 4-way digital input (high water temperature input, low oil pressure input, remote input, urgency stop input;
  • 2 relay output (start output, fuel output) and the fuel output is programmable output port; ——1 flexible transistor output can be set to preheat output, alarm output, energize to stop output and idle output, etc;
  • Three start success conditions (speed sensor, generator, speed sensor+ generator) can be chosen;
  • Parameter setting: parameters can be modified and stored in internal EEPROM memory and cannot be lost even in case of power outage; all of them can be adjusted using front panel of the controller;
  • Modular design, anti-flaming ABS plastic enclosure, embedded installation way; compact structure with easy mounting.

SPECIFICATION

Table 3 Technical Parameters

ItemContents
Working VoltageDC9.0V to 18.0V, continuous power supply (suitable for DC12V

system)

Overall ConsumptionRegular working:<1W (Standby mode:<0.4W)
AC Volt Input: 3-phase 4-wire 3-phase 3-wire 2-phase 3-wire

Single phase 2-wire

 

AC 30V – AC 360V (ph-N) AC 50V – AC 620V (ph-ph) AC 30V – AC 360V (ph-N) AC 30V – AC 360V (ph-N)

AC Frequency50Hz/60Hz
Speed Sensor Voltage1.0V to 24V(effective value)
Speed Sensor Frequency10000Hz(Max)
Start Relay7A    DC12V power supply
Fuel Relay7A    DC12V power supply
Flexible Transistor1A    DC12V connect to (B+)
Overall Dimensions105.8mm x 61mm x 36.6mm
Panel Cutout92mm x 44mm
Working Temperature(-25~+70)°C
Working Humidity(20~93)%RH
Storage Temperature(-25~+70)°C
Protection LevelIP55 Gasket
 

Insulation

Apply AC2.2kV voltage between high voltage terminal and low voltage terminal; The leakage current is not more than 3mA within

1min.

Weight94g

OPERATION

PUSHBUTTONS

Table 4 Keys Description

IconDefinitionExplain
 

 

 

SmartGen MGC100 Genset Controller-FIG2

 

 

 

 

Stop/-

Stop the running genset.

In stop status, press it to stop generator immediately. In stop status, press it to reset any shutdown alarm.

In stop status, press it for more than 2s to test if the nixie tube and panel indicator are normal.

In setting menu, upturn or decrease parameter value (it can be double-clicked).

In setting menu, press it for more than 3s to exit this menu.

 

SmartGen MGC100 Genset Controller-FIG3

 

 

Page/Confirm

Switch display contents of nixie tube in normal status.

Pressing it for more than 3 seconds entry the parameter configuration menu.

In setting menu, press this button to modify and save value.

SmartGen MGC100 Genset Controller-FIG4 

Run/+

Manual start in stop status.

In setting menu, downturn or increase parameter value (it can be double-clicked).

CONTROL PANEL AND ICON DECRIPTION

CONTROLLER PANEL

SmartGen MGC100 Genset Controller-FIG5

ALARM ICON INDICATION

Table 5 Alarm Icon Indication

IconDescripitonIconDescripiton
SmartGen MGC100 Genset Controller-FIG6Emergency Stop AlarmSmartGen MGC100 Genset Controller-FIG9Over Speed Alarm
SmartGen MGC100 Genset Controller-FIG7High Temp AlarmSmartGen MGC100 Genset Controller-FIG10Low Oil Pressure Alarm
SmartGen MGC100 Genset Controller-FIG8Fail to Start AlarmSmartGen MGC100 Genset Controller-FIG11Over/Under Volt Alarm

PANEL INDICATOR
Working status indicator: in start delay duration, start indicator will blink; in other working duration, the indicator will always light; in stop status, the indicator will extinguish.
Stop status indicator: in stop process, stop indicator will blink; in stop duration, the indicator will always light; in start status, the indicator will extinguish.

OPERATION

REMOTE START SEQUENCE

  • When remote start signal is active, “Start Delay” timer is initiated;
  • When start delay is over, preheat relay energizes (if configured), “Preheat delay” is initiated;
  • After the above delay, the Fuel Relay is energized, and then one second later (if configured), the Start Relay is engaged and the Preheat Relay switch off. If genset fails to fire during this cranking attempt then the fuel relay and start relay are disengaged for the pre-set rest period; “Crank Rest Time” begins and wait for the next crank attempt (after the “Crank Rest Time” delay start for 3s, preheat and ETS start to output; after “Crank Rest Time” finished, ETS switch off, and after fuel output for 1s, preheat switch off);
  • Should this start sequence continue beyond the set number of attempts, the fail to start indicator will be illuminated;
  • In case of successful crank attempt, the “Safety On” timer is activated, allowing Low Oil Pressure Input and Under Pressure are inhibited. As soon as this delay is over, “start idle” delay is initiated (if configured);
  • During “Start Idle” delay, under pressure alarm is inhibited. When this delay is over, “Warming Up” delay is initiated (if configured);
  • After the “Warming Up” delay, genset will enter into Normal Running status.

REMOTE STOP SEQUENCE

  • After remote start, when remote start signal is invalid, “Stop Delay” timer is initiated;
  • Once this “stop delay” has expired, the “Cooling Delay” is then initiated;
  • During “Stop Idle” Delay (if configured), idle relay is energized;
  • “ETS Solenoid Hold” begins, ETS relay is energized while fuel relay is de-energized;
  • “Fail to Stop Delay” begins, complete stop is detected automatically;
  • Genset is placed into standby mode after its “After Stop Time”.

MANUAL START/STOP

  • Press SmartGen MGC100 Genset Controller-FIG4 to start genset. It will detect complete start and accelerate to high-speed running automatically. With high temperature, low oil pressure, over speed and volt abnormal during genset running, controller can protect it to stop quickly (Please refer to Start Sequence b-g).
  • Press SmartGen MGC100 Genset Controller-FIG2 to stop the running genset (Please refer to Stop Sequence b-f).

NOTE

  • The genset can be stopped manually in remote start status; at this time, remote input is inhibited and it will be active when remote input is closed again.
  • After start conditions are satisfied, accumulative running timer will be initiated; at the same time, the last blinking decimal of nixie tube indicates that genset works normally.

PROTECTION

  1. Low Oil Pressure: detect after Safety On, Alarm Stop when Low Oil Pressure input is active and lasts for 2s.
  2. High Temperature: detect when start, Alarm Stop when High Temperature is active and lasts for 2s.
  3. Over Speed: detect when start, Alarm Stop after duration exceeds Over Speed Stop Delay.
  4. Gen Over Volt: Alarm Stop when the controller detects genset voltage exceeds overvoltage value and delay exceeds abnormal delay.
  5. Gen Under Volt: Alarm Stop when the controller detects genset voltage less than under voltage value and delay less than abnormal delay.
  6. Emergency Stop: ETS output immediately when Emergency Stop is active, in the meanwhile fuel, preheat and start signal are cut off and Emergency Shutdown Alarm Signal is sent.
  7. Fail to Start: Alarm Stop when start failed in preset start times.
  8. Gen Under Frequency: When genset is normal running, controller detects gen frequency falls below under frequency value and the “under frequency” delay has expired, under frequency shutdown alarm will be sent.
  9. Gen Over Frequency: Detection when start genset, if gen frequency exceeds over frequency value and the “over frequency” delay has expired, over frequency shutdown alarm will be sent.

CONNECTION

SmartGen MGC100 Genset Controller-FIG12

Table 6 Terminal Connection Description

No.FunctionCable SizeNote
1B-1.0mm2Connected with negative of starter battery.
 

2

 

B+

 

1.0mm2

Connected with negative of starter battery. If wire length is over 30m, better to double wires in parallel. Max. 10A

fuse is recommended.

3Start Relay Output1.0mm2B+ power is supplied by terminal 2, rated 7A.

Connected with start coil of starter.

4Fuel Relay Output1.0mm2B+ power is supplied by terminal 2, rated 7A.
 

 

5

 

 

Controller Types

 

 

1.0mm2

When this terminal short connected with (B+), it used as diesel genset controller.

When this terminal connected with nothing, it used as

petrol genset controller.

6High Temperature1.0mm2Ground connected is active (B-).
7Low Oil Pressure1.0mm2Ground connected is active (B-).
8Emergency Stop1.0mm2Ground connected is active (B-).
9Remote Start1.0mm2Ground connected is active (B-).
10Aux. Transistor1.0mm2B- power is supplied by terminal 1, rated 1A.
 

11

Magnetic Pickup 2

(B-) has already connected with controller innerly.

 

0.5mm2

 

Connected with Rotate Speed Sensor, shielding line is recommended.

12Magnetic Pickup 10.5mm2
13N1.0mm2Connected with N wire.
14W phase voltage monitor1.0mm2Connected with W phase (2A fuse is recommended).
15V phase voltage monitor1.0mm2Connected with V phase (2A fuse is recommended).
16U phase voltage monitor1.0mm2Connected with U phase (2A fuse is recommended).

DEFINITION AND RANGE OF PARAMETERS

Table 7 Parameter Content and Range

No.ContentParameter RangeDefaultDescription
 

 

P00

 

 

AC

 

 

(0-3)

 

 

0

0: Single phase 2-wire 1: 2-phase 3-wire

2: 3-phase 3-wire

3: 3-phase 4-wire

 

 

P01

 

 

Over Volt Threshold

 

 

(30-620)V

 

 

264

When generate voltage exceed this value and last for “Abnormal Delay”, then it is regarded as over voltage and at the same time “Gen Abnormal” signal will be sent. When set value

is 620V, it won’t detect over voltage signal.

 

 

P02

 

 

Under               Volt Threshold

 

 

(30-620)V

 

 

196

When generate voltage is under this value and last for “Abnormal Delay”, then it is regarded as under voltage and at the same time “Gen Abnormal” signal will be sent. When set value

is 30V, it won’t detect under voltage signal.

P03Gen         Abnormal

Delay

(0-20)s10Alarm delay value of generate over or under

voltage.

P04Start Delay(0-3600)s1Time from remote start signal is active to start

the genset.

P05Stop Delay(0-3600)s1Time from remote stop signal is deactivated to

stop the genset.

 

P06

 

Start Attempts

 

(1-10)times

 

3

It is maximum of start attempts when starter failed to start. When reach set attempts the fail

to start alarm will be initiated.

P07Preheat Delay(0-300)s0Time of pre-powering heat plug before starter

is powered up.

P08Crank Time(3-60)s8Time of starter power up.
P09Crank Rest Time(3-60)s10The waiting time before second power up when

engine start fail.

P10Safety On Time(1-60)s5Alarms for low oil pressure and under voltage

are inactive.

P11Start Idle Time(0-3600)s0Idle running time of genset when starting.
P12Warming Up Time(3-3600)s10Warming time between genset close and high

speed running.

P13Cooling Time(3-3600)s10Radiating time before stop genset, after it

unloads.

P14Stop Idle Time(0-3600)s0dle running time when pump unit stop.
P15ETS Hold Time(0-120)s20Stop electromagnet’s power on time when

pump unit is stopping.

 

P16

 

Stop Time

 

(0-120)s

 

0

Time between ending of pump unit idle delay and stopped when “ETS Time” is set as 0;

Time between ending of ETS hold delay and

No.ContentParameter RangeDefaultDescription
    stopped when “ETS Time” is not 0.
 

 

P17

 

 

Flywheel Teeth

 

 

(10-300)

 

 

118

Teeth number of the engine, for judging of starter separation conditions and inspecting of engine speed. See the following Installation

Instruction.

 

 

P18

 

 

Over             Speed Threshold

 

 

(0-6000)r/min

 

 

3500

When rotate speed exceed this threshold and last over the delay value, over speed shutdown alarm signal will be sent.

(No detection for over speed signals if it is set

as 0).

 

P19

 

Over Speed Delay

 

(0-20)s

 

2

When    rotate    speed     exceed     over    speed

threshold and last over the delay value, over speed alarm signal will be sent.

P20Poles(2-16)2Set genset poles.
 

 

P21

 

 

Disc. Condition

 

 

(0-2)

 

 

1

Disconnected condition. Separate condition of starter and engine are gen sensor and magnetic sensor, in order that separate stater

motor and engine as soon as possible.

 

P22

 

Disc. Speed

 

(0-6000)r/min

 

840

In starting process, if genset rotate speed exceed this value, it is regarded as genset start

success, starter will separate.

 

P23

 

Disc. Freq

 

(10-30)Hz

 

14

In starting process, if genset frequency exceed

this value, that is genset start success, starter will separate.

P24Fuel Output Select(0-1)00: Fuel output;       1: Stop output (ETS Output).
P25Aux. Output 1(0-9)5Configuration       see      form     “Aux.     Output

Defination”

 

 

P26

 

 

Gen    Under    Freq Threshold

 

 

(0-75.0)Hz

 

 

45.0

When gen frequency falls below this threshold and last over the delay value, under frequency shutdown alarm signal will be sent.

(No detection for under frequency signals if it

is set as 0).

P27Under              Freq

Shutdown Delay

(0-60)s10Gen under frequency delay value.
 

 

P28

 

 

Gen     Over    Freq Threshold

 

 

(0-75.0)Hz

 

 

57.0

When gen frequency exceeds this threshold and last over the delay value, over frequency shutdown alarm signal will be sent.

(No detection for over frequency signals if it is

set as 0)

P29Over                Freq

Shutdown Delay

(0-60)s2Gen over frequency delay value.
CLb1Ua  Correct A phase voltage value.
CLb2Ub  Correct B phase voltage value.
CLb3Uc  Correct C phase voltage value.
No.ContentParameter RangeDefaultDescription
CLb4Uab  Correct AB wire voltage.
CLb5Ubc  Correct BC wire voltage.
CLb6Uca  Correct CA wire voltage.

Table 8 Defined Contents of Aux. Output Ports

No.ContentDescription
0Not UsedWhen this is chosen, output port won’t output.
1Preheat OutputClose before start, open before energize.
2Common AlarmWhen stop alarm is initiated, this alarm will self-lock untill alarm reset.
 

3

 

Idle Output

Used for engine which has idles. Close before starting and open in warming up delay; Close during stopping idle process and open when stop

is completed.

4ETS OutputUsed for some genset which has stop electromagnet. Close before

stoping idle ended. Open when “ETS Delay” ended.

5Air Flap ChokeUsed for genset with choke valve electromagnet. Close when gen start

and open when safety running delay is over.

6Reserved 
7Reserved 
8Reserved 
9Reserved 

Table 9 Crank Disconnect Conditions Selection

No.Content
0Magnetic Sensor
1Generator
2Magnetic Sensor + Generator

NOTE:

  1. Magnetic sensor is magnetic device that detects number of flywheel teeth installed in generator.
  2. If magnetic sensor is selected, please insure numbers of flywheel teeth is same with set value, otherwise, “Over Speed Shutdown” may be caused.
  3. If genset without magnetic sensor, please don’t select corresponding items, otherwise, “Start Failure” may be caused.
  4. If generate isn’t selected, the controller won’t detect over/under voltage; if magnetic sensor isn’t selected, speed of genset is converted via generate signal.

PARAMETERS SETTING

PARAMETERS REGULATION

When the controller is running, press SmartGen MGC100 Genset Controller-FIG3 for 3s, it will enter into parameter number menu and LED will display SmartGen MGC100 Genset Controller-FIG13

  1. Press SmartGen MGC100 Genset Controller-FIG4 and SmartGen MGC100 Genset Controller-FIG2 to downturn/upturn parameter number;
  2. After parameter number is selected, press SmartGen MGC100 Genset Controller-FIG3 to enter into parameter setting menu; press SmartGen MGC100 Genset Controller-FIG4 and SmartGen MGC100 Genset Controller-FIG2 to increase/decrease parameter value (it can be double-clicked);
  3. Press SmartGen MGC100 Genset Controller-FIG3 to confirm modification and save value;
  4. For multiple parameters, step (1-3) can be repeat done for setting;
  5. After parameter setting, press SmartGen MGC100 Genset Controller-FIG2 for 3s to exit parameter setting status.

RESTORE FACTORY SETTINGS
In emergency stop input status, press SmartGen MGC100 Genset Controller-FIG2 and SmartGen MGC100 Genset Controller-FIG3 for 5s at the same time, it can restore to default and “reset” will be displayed on LED.

ELIMINATE ACCUMULATED TIME
Press SmartGen MGC100 Genset Controller-FIG2 and SmartGen MGC100 Genset Controller-FIG3for 5s at the same time, accumulated running time will be reset an “hclr” will be displayed on LED.

NOTE

  • Overvoltage threshold must be greater than under-voltage threshold.
  • When start successfully, generator frequency need to be set lower as soon as possible in order to starter separate sooner.
  • Number of setting contents refers to “Parameter Content and Range (Table 7)”.
  • Only in parameter number menu can exit from parameter setting status. If there is no press operation in parameter number menu, it will exit in 30s automatically

CASE DIMENSIONS

Controller is panel built-in design; it is fixed by clips when installed

SmartGen MGC100 Genset Controller-FIG14

Battery Voltage Input

NOTE
MGC100 controller can suit for widely range of battery voltage DC( 9~18 )V. Negative of battery must be connected with the engine shell soun dly. The diameter of wire which from power supply to battery must be over 1.0 mm 2. If floating charge configured, please firstly connect output wires of charger to battery’s positive and negative directly,
then, connect wires from battery’s positive and neg ative to controller’s corresponding input ports in order to prevent
charge disturbing the controller’s normal working.
WARN: In running process, removing start battery is strictly prohibited

Speed Sensor Input

NOTE: Speed sensor is magnetic equipment which is installed on engine body for testing flywheel teeth number. 2
core shielding wire is used for the connection of the sensor and controller. The wire is supposed to be connected to 11 terminal of controller with one end and the other end hanging in the air. The other two signal lines connect separately to 11 , 12 terminal. Speed sensor output voltage is supposed to be at AC (1 1-24)V (virtual value) when it is in full speed range, and AC12V (when in rated rotate speed) is recommended. When install the s peed sensor, screw it to contact the flywheel firstly, inverse it with 1/3 circle, and then tighten the nut finally.

Withstand Voltage Test

CAUTION
CAUTION: When controller has been installed in control panel, if the high voltage test is need needed, please disconnec con troller’s all terminals in order to prevent high voltage into controller and damage it.

TYPICAL APPLICATION

SmartGen MGC100 Genset Controller-FIG15

NOTE: When it controls petrol genset, terminal 4 connects with ignition control; when it controls diesel genset, terminal 5 needs to short connect with B+, terminal 4 needs to connect with fuel output

FAULT FINDING

Table 10 Fault Finding

SymptomsPossible Solutions
Controller no response with powerCheck starting batteries;

Check controller connection wirings; Check DC fuse.

 

 

Crank not disconnect

Check fuel oil circuit and its connections; Check starting batteries;

Check speed sensor and its connections;

Refer to engine manual.

Shutdown alarm in runningCheck  related  switch  and  its  connections  according  to  the

information on LED.

Starter no responseCheck starter connections;

Check starting batteries.

Documents / Resources

SmartGen MGC100 Genset Controller [pdf] User Manual
MGC100 Genset Controller, MGC100, Genset Controller, MGC100 Controller, Controller
SmartGen MGC100 Genset Controller [pdf] User Manual
MGC100 Genset Controller, MGC100, MGC100 Controller, Genset Controller, Controller