NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below.
Program feature or

option

Permitted in UL 864?

(Y/N)

Possible settingsSettings permitted in

UL 864

PERIODIC TEST,

PROGRAMMING RANGE

 

Y

 

1 – 24 Hours

 

1 – 6 Hours

Digital Communication

format

YSIA DCS, Ademco

Contact ID, 3/1, 4/2

SIA DCS, Ademco

Contact ID

 

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLDED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in CAN/ULC-S527, Standard for Control Units and Accessories for Fire Alarm Systems, certain programming features or options must be limited to specific values or not used at

all as indicated below.

Program feature or optionPermitted in

CAN/ULC-S527? (Y/N)

 

Possible settings

Settings permitted in CAN/ULC-S527
PERIODIC TEST, PROGRAMMING RANGE 

Y

 

1 – 24 Hours

 

1 – 24 Hours

Digital Communication formatYCID, SIA DCSSIA DCS, Ademco Contact ID

OVERVIEW

The FCA2015-U1 Digital Alarm Communicator Transmitter (DACT) Board is an optional module for the Desigo FC2025/2050, FV2025/2050, Cerberus PRO FC922/924, FV922/924, and XLS/Desigo Fire Safety Modular/Cerberus PRO Modular Fire Alarm System Control Panels. The DACT provides telephone line connections for communication with a DACR (Digital Alarm Communicator Receiver). The DACT Board is mounted inside the Fire Alarm cabinet. The DACT Board options are set through the control panel programming sequence.

INSTALLATION ON DESIGO AND CERBERUS PRO PANELS

Dialer FCA2015-U1 mounted on 2HU EnclosureSIEMENS-FCA2015-U1-Serial-Digital-Alarm-Communicator-Transmitter-FIG-1

  1. Installation should be performed by qualified personnel who have thoroughly read and understood this instruction sheet.
  2. Disconnect BATTERY and AC on the cabinet prior to working on the equipment.
  3. Mount FCA2015-U1 as shown using the four screws that are supplied.
  4. Attach conduit and run wires as required. Wire Size: 12-22AWG
  5. Connect the Serial Communication Cable to the fire system control unit as required.
  6. Apply power to system.
  7. Program for proper operation.
    • NOTE: See the Desigo FC2025/2050, FV2025/2050 Configuration manual, Document ID A6V10315023, and Cerberus PRO FC922/924, FV922/924 Fire Detection System Configuration manual, Document ID A6V10333423, for details on programming.
  8. Check for proper operation.

Dialer FCA2015-U1 mounted on the back of the inner door (when used with a 3HU Enclosure)SIEMENS-FCA2015-U1-Serial-Digital-Alarm-Communicator-Transmitter-FIG-2

PARTS SUPPLIED

  • 1 DACT Board
  • 4 Screws
  • 1 Instruction Sheet
  • 1 Serial Communication Cable
    • 4 1 ¾” x ¼” Hex Male to Female Standoff
    • Used for FCM2019-U2/-U3 or FCM2035-U2/-U3 only.

INSTALLATION ON XLS/DESIGO FIRE SAFETY MODULAR/CERBERUS PRO MODULAR

For instructions on installing and wiring the FCA2015-U1 DACT to the XLS/Desigo Fire Safety Modular/Cerberus PRO Modular panel, refer to the XDACT-ASSY Installation Instructions, Document ID A6V10807278. If a message indicating an XDACT firmware mismatch is displayed on the Operator Interface (OI), upgrade the XDACT firmware as follows.

FIRMWARE UPDATE ON XLS/DESIGO FIRE SAFETY MODULAR/CERBERUS PRO MODULAR SYSTEMS

To update the firmware on an FCA2015-U1 that is installed on a XLS/Desigo Fire Safety Modular/Cerberus PRO Modular system, establish an Ethernet connection between the PC and the OI, then select the XDACT module in the Zeus configuration. Next, select Build > Transfer > Module Firmware To Panel… in Zeus. Select the XDACT firmware file under Firmware File, then set the Connection Settings as needed and click Start Transfer to begin the update. Transfer Completed will be displayed in Zeus after the firmware update has completed.

FCA2015-U1 WIRING

SIEMENS-FCA2015-U1-Serial-Digital-Alarm-Communicator-Transmitter-FIG-3

NOTE

  • The RJ31X provides a convenient connection allowing the DACT to be installed and removed without requiring re-wiring and can be installed by the telephone installer.
  • If installed in Canada, the signal receiving centre must not share a common communication channel with the protected premises. A dedicated line must be installed for use only by the FCA2015-U1.
  • Either of the two lines at X300 or X301 can be disabled using the Engineering Configuration tool for the case where the dialer is connected to an alarm communicator that is capable of transmitting with two separate technologies (ex. GSM and POTS). Consult the installation instructions for the communicator to determine if it supports this capability.

FCA2015-U1 FORMAT DESCRIPTION

FormatDescription
SIA DCS 8Security Industry Association – Digital Communications Standard (DCS). Format may send up to eight events per call. SIA 1997 Level 1 compatibility with support for O (old) blocks and 300 Baud (FAST) operation.

Sends an account number (up to 6 digits), a 2-character code and 3-digit identifier up to four times with FSK frequency encoding.

SIA DCS 20See SIA DCS 8, except format may send up to twenty events per call.
Ademco Contact IDSends a 4-digit account number, a 3-digit code and 3-digit identifier up to four rounds of dual tone multiple frequency with 1400 and 2300 Hz handshake frequency.
3/1 1400HZSends a 3-digit account number and a 1-digit code up to four rounds at 20 pps with 1400 Hz handshake frequency.
3/1 2300HZSends a 3-digit account number and a 1-digit code up to four rounds at 20 pps with 2300 Hz handshake frequency.
4/2 1400HZSends a 4-digit account number and a 2-digit code up to four rounds at 20 pps with 1400 Hz handshake frequency.
4/2 2300HZSends a 4-digit account number and a 2-digit code up to four rounds at 20 pps with 2300 Hz handshake frequency.

COMPATIBLE RECEIVERS/FORMATS

Receiver ManufacturerCompatible ReceiversSIA DCS 8SIA DCS 20Ademco Contact ID3/1

1400HZ

3/1

2300HZ

4/2

1400HZ

4/2

2300HZ

HoneywellM8000SIA DCS 8SIA20Ademco Contact IDSK 3/1SK 3/1SK 4/2SK 4/2
BoschD6100i, D6100IPV6

, or D6600

SIA DCS 8SIA20Ademco Contact IDSK 3/1SK 3/1SK 4/2SK 4/2
Silent Knight Security Corp.9800XXAdemco Contact IDSK 3/1SK 3/1SK 4/2SK 4/2
Sur-GardSystem I through VSIA DCS 8SIA20Ademco Contact IDSK 3/1SK 3/1SK 4/2SK 4/2
Sur-GardSystem III*SIA DCS 8SIA20Ademco Contact IDSK 3/1SK 3/1SK 4/2SK 4/2
  • For FM use only

The FCA2015-U1 is also compatible with alarm communicators that utilize different communication technologies (IP and GSM technologies) to connect to compatible receivers using compatible protocols listed within this document.

COMPATIBLE ALARM COMMUNICATORS

ManufacturerModel #Comm TechUL

Approved

ULC

Approved

Dialer capture protocolULC

Communication Type

Telguard (Telular)TG-7FSGSMUL864

(10th Ed.)

Yessupport Contact ID (CID)

 

SIA DCS

ACTIVE

communication only

BoschB465IP/GSMUL864

(10th Ed.)

YesCID

and SIA

Active communication only
BoschC900V2

(Discontinued)

IPUL864

(9th Ed.)

No Model discontinued
DSCLE4010-CFGSMUL864

(10th Ed.)

YesCID

or SIA

Active                or

Passive communication

DSCTL300CFIPUL864

(10th Ed.)

YesCIDActive                or

Passive communication

DSC3G3070-CF

(Discontinued)

GSMUL864

(9th Ed.)

Yes Model discontinued
NAPCO

Starlink

SLE-LTEVI- FIREIP/GSMUL864

(10th Ed.)

NoCID 
NAPCO

Starlink

SLE-LTEVI- CFBIP/GSMUL864

(10th Ed.)

NoCID 
NAPCO

Starlink

SLE-LTEVI- CFBPSIP/GSMUL864

(10th Ed.)

NoCID 

NOTES

  • The DACT can be used with alarm communicators that also employ other transmission technologies for off-premises signaling for UL and ULC.
  • When using these alarm communicators, the DACT shall be configured for Contact ID or SIA DCS. Please refer to the Compatible Alarm Communicators table.
  • Refer to the Alarm Communicator Installation Instruction for compatible receivers.
  • The use of a 3rd Party communicator may require Aux 24VDC from the FACP.

Use of 3rd party communicator for UL:

  1. As sole communication path, maximum supervision window is 60 min.
  2. As 2nd path for DACT, maximum supervision window is six hours.

Use of 3rd party communicator for ULC:

  1. As sole Active Communication path, maximum supervision window is 180 seconds.
  2. Work with DACT as 2nd Passive Communication path, maximum supervision window is 24 hours.

Refer to the installation instructions for the external communicator for specific power requirements and include with the system battery calculations to ensure adequate secondary power.

  • Wiring between the DACT and the alarm communicator shall be within 20 feet, and in conduit for US, and within 18 meters in metallic conduit for Canada.
  • All compatible Alarm Communicators shall be installed in accordance with their installation instructions.
  • A means must be provided for detection of faults on the communicator by the fire alarm panel, as described in the installation instructions for the communicator. This is typically done by connecting a trouble-activated relay or PGM output on the communicator to an input switch module (i.e. HTRI).
  • For ULC Passive Communication, the TL300CF and LE4010-CF communicators must be wired as shown in the following diagrams.

ULC Passive Configuration

SIEMENS-FCA2015-U1-Serial-Digital-Alarm-Communicator-Transmitter-FIG-4

Reference to Installation Guide of DSC
TL300CF or LE4010CF

(PS4085 board contacts in RED)

Main communication board contact in BLUE

ContactsDescription
TestCharger Trouble Output
LBTLow Batt Output Trouble
ACT“ACT” must be connected to input #1 of TL300CF or LE4010CF

Note: AC trouble delay must be configured via CONNECT 24

Utilize PGM1 (TL300CF) or PGM4

(LE4010CF)

Communicator PATH DOWN Utilize PGM1 (TL300CF) or PGM4

LE4010-CF Configuration

(Reference from DSC Installation Manual)

SIEMENS-FCA2015-U1-Serial-Digital-Alarm-Communicator-Transmitter-FIG-5

TL300-CF Configuration

(Reference from DSC Installation Manual)SIEMENS-FCA2015-U1-Serial-Digital-Alarm-Communicator-Transmitter-FIG-6

NOTE: Wiring between the control panel and the T-Link TL250/TL300 must be enclosed in metal conduit.

  • Wire the panel’s Tip and Ring terminals to the TI and RI terminals of TL.300

LE4010-CF &TL300-CF Power Supply Wiring Configuration

(Reference from DSC Installation Manual)SIEMENS-FCA2015-U1-Serial-Digital-Alarm-Communicator-Transmitter-FIG-7

The ACT shall be connected to Input 1 of the transmitter and transmission delay is to be configured via CONNECT 24. The LBT and TEST shall be connected to FACP’s trouble inputs. The outputs are active model: DSc RM2 ground) and shall be connected via listed supervision relay (suggested).

FCA2015-U1 EVENT CODES

 

 

Event Type

SIA DCS

(8 or 20)* 5

Ademco Contact ID*53/1 1400 Hz or

2300HZ

4/2 1400 Hz or

2300HZ

Fire AlarmFA pppp1 110 0p ppp001
Fire Alarm Restore (Through Reset)FH pppp3 110 0p ppp221
Smoke AlarmFA pppp1 111 0p ppp001
Smoke Alarm RestoreFH pppp3 111 0p ppp221
Heat AlarmFA pppp1 114 0p ppp001
Heat Alarm RestoreFH pppp3 114 0p ppp221
Pull Station AlarmFA pppp1 115 0p ppp001
Pull Station Alarm RestoreFH pppp3 115 0p ppp221
Waterflow AlarmSA pppp1 113 0p ppp002
Waterflow Alarm RestoreSH pppp3 113 0p ppp222
SupervisorySS pppp1 200 0p ppp666
Supervisory RestoreSR pppp3 200 0p ppp776
AC TroubleAT1 301 00 000880
AC Trouble RestoreAR3 301 00 000770
TroubleFT pppp1 373 0p ppp883
Trouble RestoreFJ pppp3 373 0p ppp773
System Battery TroubleYT1 302 00 000887
System Battery Trouble RestoreYR3 302 00 000777
Phone Line 1 TroubleLT 11 351 00 000881
Phone Line 1 Trouble RestoreLR 13 351 00 000771
Phone Line 2 TroubleLT 21 352 00 000882
Phone Line 2 Trouble RestoreLR 23 352 00 000772
Data LostRT 01 354 00 000888
Automatic Test (Normal)RP1 602 00 000930
Automatic Test (Off Normal)RY1 608 00 000939
Manual TestRX 01 601 00 000999
Test ActivationFX pppp1 611 0p ppp991
Gas AlarmGA pppp1 151 0p ppp003
Gas Alarm RestoreGH pppp3 151 0p ppp223
Communications FailYC1 350 00 000884
System ResetOR 01 305 00 000779
Test BeginFI pppp1 604 0p ppp990
Test EndFK pppp3 604 0p ppp992
Mass Notification Alarm4PA pppp1 120 0p ppp111
Mass Notification Alarm Restore4PH pppp3 120 0p ppp331
Mass Notification Trouble4PT pppp1 375 0p ppp883
Mass Notification Trouble Restore4PJ pppp3 375 0p ppp773
MNS11XB pppp1 789 0p ppp111
MNS1 Restore1XC pppp3 789 0p ppp331
MNS21XN pppp1 788 0p ppp666
MNS2 Restore1XP pppp3 788 0p ppp776
MNS Trouble1XU pppp1 787 0p ppp883
MNS Trouble Restore1XV pppp3 787 0p ppp773
Security3TA pppp1 137 0p ppp668
Security Restore3TH pppp3 137 0p ppp778
Emergency2, 4EB pppp1 785 0p ppp665
Emergency Restore2, 4EC pppp3 785 0p ppp775
Building2ZA pppp1 152 0p ppp665
Building Event Restore2ZH pppp3 152 0p ppp775
“Other”2XY pppp1 786 0p ppp440
“Other” Restore2XZ pppp3 786 0p ppp550
  • pppp is the dialer group or zone number
  1. XLS/Desigo Fire Safety Modular/Cerberus PRO Modular only, if set to either “US/Other” or “Canada”
  2. XLS/Desigo Fire Safety Modular/Cerberus PRO Modular only, if set to “Canada”
  3. XLS/Desigo Fire Safety Modular/Cerberus PRO Modular only, if set to “US/Other”
  4. Desigo FC2025/FC2050, FV2025/FV2050, Cerberus PRO FC922/FC924, FV922/FV924 only
  5. Only SIA DCS and Ademco Contact ID can be used for UL 864 10th Edition off-premises signaling
ELECTRICAL RATINGS
Standby 24DC Module Current33.5mA
Active 24VDC Module Current43.5mA

 

INDICATORS
LEDFunctionDescription
H100“OK LED”Hardware is functionally good
H200“L1 FLT”Red LED on Solid – Line Connection error while dialing out, Line 1, Red LED Flashing DACT Dialing out on Line 1
H201“L2 FLT”Red LED on Solid – Line Connection error while dialing out, Line 2, Red LED Flashing DACT Dialing out on Line 2
H202“RX”DACT receiving information in
H203“TX”DACT Transmitting information out
H204“UP RUN”Green Flashing DACT has heartbeat

FCC Statement

WARNING: Installation and usage of equipment not in accordance with instructions manual may result in:

Radiation of radio frequency energy Interference to radio communications

  • Install and use equipment in accordance with instructions manual
  • Read the following information.

This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instructions manual, may cause interference to radio communications.
It has been tested and found to comply with the limits for a Class A computing device pursuant to Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference in which case the user at his own expense will be required to take whatever measures may be required to correct the interference.

As per ULC S559, the FCA2015-U1 is classified as an Active Communication System.

Legal Notice

Technical specifications and availability subject to change without notice.
© 2020 Copyright by Siemens Industry, Inc.

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders will be held liable for payment of damages. All rights created by patent grant or registration of a utility model or design patent are reserved.

Issued by

  • Siemens Industry, Inc.
  • Smart Infrastructure
  • 8 Fernwood Road Florham Park, NJ 07932
  • Tel: + 1 973- 593-2600
  • www.downloads.siemens.com/dlc
  • Edition: 2020-10-14
  • Document ID: A6V10334254_en–_h

Cyber security disclaimer

Siemens provides a portfolio of products, solutions, systems and services that includes security functions that support the secure operation of plants, systems, machines and networks. In the field of Building Technologies, this includes building automation and control, fire safety, security management as well as physical security systems.

In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art security concept. Siemens’ portfolio only forms one element of such a concept. You are responsible for preventing unauthorized access to your plants, systems, machines and networks which should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. Additionally, Siemens’ guidance on appropriate security measures should be taken into account. For additional information, please contact your Siemens sales representative or visit https://www.siemens.com/global/en/home/company/topicareas/future-of-manufacturing/industrial-security.html.

Siemens’ portfolio undergoes continuous development to make it more secure. Siemens strongly recommends that updates are applied as soon as they are available and that the latest versions are used. Use of versions that are no longer supported, and failure to apply the latest updates may increase your exposure to cyber threats. Siemens strongly recommends to comply with security advisories on the latest security threats, patches and other related measures, published, among others, under https://www.siemens.com/cert/en/cert-security-advisories.htm.

ADDRESS

Siemens Industry, Inc.

  • Smart Infrastructure
  • 8 Fernwood Rd Florham Park, NJ 07932

Siemens Canada, Ltd.

  • 1577 North Service Road East
  • Oakville, Ontario L6H 0H6 Canada

Document ID A6V10334254_en–_h
P/N A5Q00050827