TECHNICAL SPECIFICATIONS

SENECA ZE-4DI Digital Output Modbus 01

PRELIMINARY WARNINGS

  • The word WARNING preceded by the symbol indicates conditions or actions that put the user’s safety at risk.
  •  The word ATTENTION preceded by the symbol indicates conditions or actions that might damage the instrument or the connected equipment. The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.
    SENECA ZE-4DI Digital Output Modbus 02WARNING: The full content of this manual must be read before any operation. The module must only be used by qualified electricians. Specific documentation is available via QR-CODE shown on page 1.
    SENECA ZE-4DI Digital Output Modbus 03The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during any operation.
    SENECA ZE-4DI Digital Output Modbus 04Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to recycle electrical and electronic waste.

     

SETTING THE DIP-SWITCHES

The position of the DIP-switches defines the Modbus communication parameters of the module: Address and Baud Rate The following table shows the values of the Baud Rate and the Address according to the setting of the DIP-switches:

DIP-Switch status
SW1 POSITIONBAUD RATESW1 POSITIONADDRESSPOSITIONTERMINATOR
1 2 3 4 5 6 7 83 4 5 6 7 810
SENECA ZE-4DI Digital Output Modbus 059600#1SENECA ZE-4DI Digital Output Modbus 15Disabled
SENECA ZE-4DI Digital Output Modbus 0619200#2SENECA ZE-4DI Digital Output Modbus 16Enabled
SENECA ZE-4DI Digital Output Modbus 0738400 

SENECA ZE-4DI Digital Output Modbus 12

#…SENECA ZE-4DI Digital Output Modbus 16

 

SENECA ZE-4DI Digital Output Modbus 0857600#63
SENECA ZE-4DI Digital Output Modbus 09

From

EEPROM

SENECA ZE-4DI Digital Output Modbus 14

From

EEPROM

Note:
When DIP switches 1 to 8 are OFF, the communication settings are taken from programming (EEPROM). ؔ
Note 2:
The RS485 line must be terminated only at the ends of the communication line.

DIP-SWITCHES
SW1

All DIP switches in OFF position.

For further information, refer to the USER MANUAL.

 

 

 

SW2

 

RS232 or RS485 settings on terminals 10-11-12 (COM2 serial port)

RS232ONSENECA ZE-4DI Digital Output Modbus 16
RS485OFFSENECA ZE-4DI Digital Output Modbus 19

CONFIGURATION OF FACTORY SETTINGS

All DIP-switches inOFFSENECA ZE-4DI Digital Output Modbus 20
Communication parameters of ModBUS protocol: RS485 and RS482/232 ports38400, 8, N, 1 Address 1
Communication parameters of micro USB port115200, 8, N, 1 Address 1
Analogue Input 1-2VOLTAGE

ModBUS CONNECTION RULES

  1. Install the modules in the DIN rail (120 max)
  2. Connect the remote modules using cables of an appropriate length. The following table shows cable length data:
  • Bus length: maximum length of the Modbus network according to the Baud Rate. This is the length of the cables that connect the two farthest modules (see Diagram 1).
  • Derivation length: maximum length of a derivation 2 m (see Diagram 1).
    SENECA ZE-4DI Digital Output Modbus 31

For maximum performance, it is recommended to use special shielded cables, such as BELDEN 9841.

Bus lengthDerivation length
1200 m2 m

INSTALLATION REGULATIONS

The module has been designed for vertical installation on a DIN 46277 rail. For optimal operation and long life, adequate ventilation must be provided. Avoid positioning ducting or other objects that obstruct the ventilation slots. Avoid mounting modules over heat-generating equipment. Installation in the bottom part of the electrical panel is recommended.SENECA ZE-4DI Digital Output Modbus 32Insertion in the DIN rail As shown in figure:

  1.  Insert the IDC10 rear connector of the module on a free slot of the DIN rail (the insertion is univocal since the connectors are polarized).
  2. To secure the module to the DIN rail, tighten the two hooks on the sides of the IDC10 rear connector.

Power supply and Modbus interface are available using the Seneca DIN rail bus, via the IDC10 rear connector, or the Z-PC-DINAL-17.5 accessory.
SENECA ZE-4DI Digital Output Modbus 33USB PORT
The module is designed to exchange data according to the modes defined by the MODBUS protocol. It has a micro USB connector and can be configured using applications and/or software programs. The USB serial port uses the following communication parameters: 115200,8,N,1 The USB communication port responds exactly like the RS485 or RS232 ports with the exception of the communication parameters. EASY SETUP is the software to use for the configuration. For further information go to the following website: www.seneca.it/products/ze-4di-2ai-2dowww.seneca.it/products/z-4di-2ai-2dowww.seneca.it/products/ze-2aiSENECA ZE-4DI Digital Output Modbus 34

  • Check that the device in question is included in the list of products supported by the Easy Setup APP in the store. Check that the device in question is included in the list of products supported by the Easy Setup APP in the store.

ELECTRICAL CONNECTIONS
Attention:
the upper power supply limits must not be exceeded, as this might cause serious damage to the module.
To meet the electromagnetic immunity requirements:

  • use shielded signal cables;
  • connect the shield to a preferential instrumentation earth system;
  •  separate shielded cables from other cables used for power installations (transformers, inverters, motors, induction ovens, etc…).

POWER SUPPLY
SENECA ZE-4DI Digital Output Modbus 22ANALOGUE INPUTS

Voltage

Active sensor current (4 wires)

Passive sensor current (2 wires)

The module has two analogue inputs that can be configured via software as voltage or current. For the configuration software, see the user manual
 

 

SENECA ZE-4DI Digital Output Modbus 25

DIGITAL INPUTS (ONLY ZE-4DI-2AI-2DO and Z-4DI-2AI-2DO)SENECA ZE-4DI Digital Output Modbus 26DIGITAL OUTPUTS (ONLY ZE-4DI-2AI-2DO and Z4DI-2AI-2DO)

N.A.1=19 CO.1=20 N.C.1=21SENECA ZE-4DI Digital Output Modbus 27N.A.2=22 CO.2=23 N.C.2=24SENECA ZE-4DI Digital Output Modbus 28The has two digital outputs with free contacts. The two figures show the internal relay contacts available.

COM2 SERIAL PORT

SENECA ZE-4DI Digital Output Modbus 29SENECA ZE-4DI Digital Output Modbus 30The module has a COM2 port
configurable via the SW2 switch
on terminals 10 -11-12

MODULE LAYOUT
SENECA ZE-4DI Digital Output Modbus 35
SENECA ZE-4DI Digital Output Modbus 36Single module dimensions LxHxD: 17.5 x 102.5 x 111 mm;
Weight: 110 g;
Enclosure: PA6, black
Double module dimensions LxHxD: 35 x 102.5 x 111 mm;
Weight: 110 g;
Enclosure: PA6, black
LED SIGNALS ON THE FRONT PANEL (ZE-4DI-2AI-2DO)

LED

STATUSMEANING
IP/ PWR (Green)ON

Module powered and IP address acquired

IP/ PWR (Green)

FlashingPowered module. Waiting for IP address from DHCP server
Tx/ Rx (Red)Flashing

Transmission and reception of data on at least

one Modbus port: port COM 1, port COM 2

ETH TRF (Green)

FlashingPacket transmission on Ethernet port
ETH LNK (Yellow)ON

Ethernet port connected

DI1, DI2, DI3, DI4 (Red)

On / OffStatus of digital input 1, 2, 3, 4
DO1, DO2 (Red)On / Off

Status of output 1, 2

FAIL (Red)

Flashing

Outputs in fail condition

LED SIGNALS ON THE FRONT PANEL (Z-4DI-2AI-2DO)

LED

STATUSMEANING
PWR (Green)ON

Module powered

Tx/ RX (Red)

FlashingTransmission and reception of data on at least

one Modbus port: port COM 1, port COM 2

DI1, DI2, DI3, DI4 (Red)

On / Off

Status of digital input 1, 2, 3, 4

DO1, DO2 (Red)

On / OffStatus of output 1, 2
FAIL (Red)Flashing

Outputs in fail condition

LED SIGNALS ON THE FRONT PANEL (ZE-2AI)

LED

STATUSMEANING
IP/ PWR (Green)ON

Module powered and IP address acquired

IP/ PWR (Green)

FlashingPowered module. Waiting for IP address from DHCP server
FAIL (Red)ON

At least one of the two analogue inputs is out of scale (underscale-overscale)

ETH TRF (Green)

FlashingPacket transmission on Ethernet port
ETH LNK (Yellow)ON

Ethernet port connected

Tx1 (Red)

FlashingModbus packet transmission from device to port COM 1
Rx1 (Red)Flashing

Modbus packet transmission to port COM 1

Tx2 (Red)

FlashingModbus packet transmission from device to port COM 2
Rx2 (Red)Flashing

Modbus packet transmission to port COM 2

CONTACT INFORMATION

Technical support