Instruction Manual for HILTI models including: CFS-CID 50, CFS-CID 75, CFS-CID 110, CFS-CID 160, CFS-CID 50 Firestop Cast In Device, Firestop Cast In Device, Cast In Device, In Device, Device
Feb 3, 2023 — Advantages. • One-step firestop solution for a variety of pipe materials and diameters – no additional backfilling required.
File Info : application/pdf, 8 Pages, 6.74MB
DocumentDocumentFIRESTOP CAST-IN DEVICE CFS-CID Technical Manual European Technical Assessment ETA-20/1233 Issue 12/2020 Firestop Cast-in Device CFS-CID FIRESTOP CAST-IN DEVICE CFS-CID Applications · Concrete slabs built with traditional formwork · New building construction · Sealing combustible and non-combustible pipe penetrations · Tested with pipe elbows, which allows reduced service zone Advantages · One-step firestop solution for a variety of pipe materials and diameters no additional backfilling required · Modular connection allows close placement of multiple penetrations · Quicker and simpler installation · Integrated moisture and smoke seal · Lid strong enough to carry foot traffic and light access equipment Technical Data Base materials Concrete Approvals EN 13501-2: 2007+A1:2009, EN 1366-3:2009 Height 250 mm Application temperature range 5 50 °C Temperature resistance range 20 100 °C Color Red Re-penetration Reaction to fire class (EN 13501-1) Easy E Ordering description CFS-CID 50 CFS-CID 75 CFS-CID 110 CFS-CID 160 Pipe diameter range 4063 mm 5075 mm 80110 mm 125160 mm 10/21 Sales pack quantity 1 pc 1 pc 1 pc 1 pc Item number 2124523 2124524 2124525 2124526 2 Firestop Cast-in Device CFS-CID MANIFOLD ADAPTER CFS-CID Applications · Creation of a 70 mm deep recess in a slab · For use in conjunction with the appropriate cast-in device · Creates an underside void for the installation of an elbow- connector system Technical Data Base materials Concrete Height 77 mm Application temperature range 5 50 °C Color Red Advantages · Allows a manifold to be accommodated and thus simplifies plumbing installations · Accommodates manifold connections and shower traps for walk-in showers and wet rooms · Reduces final ceiling depth by creating a 70 mm recess in the slab · Pipes can be installed closer to the ceiling, thus reducing spacing Ordering description CFS-CID Manifold Adapter Sales pack quantity 1 pc Item number 2124527 HEIGHT EXTENSIONS CFS-CID Applications · For use with CFS-CID cast-in devices Advantages · "Screw on" feature promotes a secure connection to the device and cover cap · Adds 150 mm of height to pre-formed firestop devices Technical Data Base materials Concrete Height 150 mm Application temperature range 5 50 °C Color Red Ordering description Extension tube 6" CP 680-P 2" Extension tube 6" CP 680-P 3" Extension tube 6" CP 680-P 4" Extension tube 6" CP 680-P 6" Pipe diameter range 4063 mm 5075 mm 90110 mm 125160 mm Sales pack quantity 1 pc 1 pc 1 pc 1 pc Item number 244252 244253 244254 244255 10/21 3 GENERAL INSTRUCTIONS FOR USE 1 2 3 Firestop Cast-in Device CFS-CID 4 5 6 7 1 2 10/21 4 GENERAL INFORMATION Firestop Cast-in Device CFS-CID Partition Base material thickness (tE) Distance between devices Fixing to formwork Gap filling Penetrant Rigid Floor 150 mm Zero for all pipe types Wood nails No backfilling required Combustible and non-combustible Pipes MAIN APPROVED APPLICATIONS Application Waste water, Roof drainage Drinking water Heating Pipe material Pipe Ø mm PE/PE-HD EN 1519-1, EN 12666-1 (covers EN 12201-2, EN 1519-1, EN 12666-1, EN 1455-1 (ABS), EN 1565-1 (SAN+PVC) EN ISO 15494 (Industrial), DIN 8074 PVC-U EN 1329-1 or EN 1453-1 or EN 1452-1 (covers EN 1329-1, EN 1453-1, EN 1452-1, EN 1566-1), EN ISO 15493 (Industrial, equivalent EN 1452) PE S2 Geberit db20 (Non-regulated) PP (EN 1451-1, DIN 4102)* PP-R DIN 8077/8078 (e.g. Aquatherm) PE-Xa Rehau Rautitan Flex AL-composite pipes with elastomeric insulation (e.g Geberit Mepla, etc) 40160 63160 50160 56160 40160 32160 3263 40 Copper, steel, stainless steel and cast iron with elastomeric, glass or mineral wool insulation 1889 Classification in rigid floor EI 180 U/U EI 180 U/U EI 120 U/U EI 180 U/U EI 180 U/U EI 180 U/C EI 180 U/U EI 180 U/C EI 180 C/U * Coes "Blue Power", Coes "PhoNoFire", "Geberit Silent PP", Marley Silent, Ostendorf "Skolan-dB", Pipelife "Master 3", POLOPLAST "Polokal NG", POLOPLAST "Polokal 3S", "POLOPLAST Polokal XS", Rehau "Raupiano Plus", Wavin "AS", KeKelit "Phonex AS", Wavin "SiTech", Valsire "Triplus", Valsire "Silere" Excerpt of ETA document. Check the exact field of application for each pipe (type, diameter and pipe wall thickness) in the ETA-20/1233 document. 10/21 5 Firestop Cast-in Device CFS-CID OTHER APPROVED APPLICATIONS CFS-CID Manifold Adapter Recess for pipe junctions Dimensions: 280×280×75 mm 1 2 3 4 To use with Firestop Cast-in Device CFS-CID 110 mm 5 6 7 8 1 2 Recess for pipe elbow couplers EI 180 U/U for PVC and HD-PE pipes Ø = 110 mm 1 2 3 4 3 2 1 5 6 7 8 Firestop Cast-in Extensions Adds an extra 150 mm to the Cast-in Device with a strong and stable connection. Coupler and extensions available for all CFS-CID diameters. Firestop Cast-in CFS-CID without pipe penetrations All sizes tested and approved only with the lid on top. Zero distance between Cast-in Devices It is possible to assemble Firestop Cast-in Devices with zero separation between them. See ETA-20/1233 for details of approved pipes See ETA-20/1233 for details of approved pipes 10/21 6 Firestop Cast-in Device CFS-CID CHARACTERISTICS OF CFS-CID Characteristics Health and the environment Emission test Protection against noise Airborne sound insulation Durability and serviceability Reaction to fire Assessment of characteristics CFS-CID was tested for VOC emissions according to ISO 16000 and was deemed compliant to the AgBB regulations (version 2010). The concentration of SVOC after 3 and 28 days was < 5 g/m³. The concentration of the total emission of VOC after 3 and 28 days was 25 g/m³ Hilti CFS-CID 50 D n,w = 55 dB Hilti CFS-CID 75 D n,w = 51 dB Hilti CFS-CID 110 D n,w = 48 dB Hilti CFS-CID 160 D n,w = 46 dB Category Y2 (suitable for penetration seals for use in dry indoor conditions at temperature below 0 °C with with no exposure to rain nor UV Class E Norm, standard, test Material safety data sheet EN ISO 10140-1 EN ISO 10140-2 EN ISO717-1 EAD 350454-00-1104 EN 13501-1 10/21 7 Hilti Corporation 9494 Schaan, Liechtenstein P +423-234 2965 www.facebook.com/hiltigroup www.hilti.group Hilti = registered trademark of Hilti Corp., Schaan W4561 1021 0-en 2 Printed in Liechtenstein © 2021 Right of technical and programme changes reserved S. E. & O.