TruGroove recessed micro T-Grid Installation Sheet

Signify

Install instructions

TruGroove recessed micro - Recessed | Ledalite - Signify


File Info : application/pdf, 8 Pages, 1.91MB

PDF preview unavailable. Download the PDF instead.

TruGroove-recessed-micro-T-Grid-Installation-Sheet
Linear

TruGroove Recessed Micro

ID-23 T-Grid

Installation Instructions Standalone or Continuous Run in T-Grid Ceiling
These instructions review how to install TruGroove recessed micro fixtures in T-Grid ceilings. For continuous run lengths, Please refer to layout drawings supplied by Ledalite in conjunction with these installation instructions. The graphics below show the components required to install a run of TruGroove fixtures in T-Grid ceilings.
IMPORTANT: Read all instructions including fixture/sensor wiring AND mechanical details before beginning installation

Drop Lens Endcap Kit(s)*
· Drop Lens Endcap (x1)
· Screws (x2)

*Optional

NOTE: One kit required for each end.

Module 1

Module 2 Flush Lens

Asymmetric direction of light Symmetric direction of light

1" Drop Lens

· Exterior flush and drop lens kits -variable lengths (shipped separately)
Note: Louver optics ship factory installed.

i Hanger Kit(s)

ii Joint Kit(s)

· Bracket (x4) · Screws (x8)
NOTE: One kit required for each module.
Tools required: Phillips screwdriver, 5/16" nut driver.

· Joiner Aligners (x2) · Joiner Brackets (x2) · Hex Bolts (x4) · Screw(s)
( x1 symmetric, x2 for asymmetric ) · LED pan connectors (x1)
NOTE: Image shown is a symmetric connector. Asymmetric has two pieces.
NOTE: One (1) kit required for each module joint in continuous runs

!

ATTENTION: Install in accordance with local and national building and electric codes.

10/31/2023 page 1 Rev E. www.ledalite.com

ID-23 TruGroove Recessed Micro T-Grid Installation Instructions

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interreference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.

Important Notes
Warning, Shock Hazard
Fixture must be connected to building ground via the provided ground wire before connecting to mains power supply.
Disconnect or turn off power before attempting any installation, service or maintenance.

i Prepare Fixtures
Arrange boxed fixtures on floor in specified mounting locations, based on supplied layout drawings. Remove fixtures from boxes. Remove plastic from fixtures. Match up each fixture and lens based on the spec tag and ID number labelled on each fixture box for the specified run.

1 T-Grid

2.88" (73mm)

Install Fixtures
2 Install Mounting Brackets
9/16 Grid 1 3/4 Height 9/16 Grid 1 11/16 Height 9/16 Grid 1 1/2 Height

9/16 Grid 1 1/16 Height - 5/16 Tegular 9/16 Grid 1 1/2 Height - 5/16 15/16 Grid 1 11/16 Height 15/16 Grid 1 1/2 Height 15/16 Grid 1 3/8 Height 15/16 Grid 1 3/16 Height

Install main tees, 2.88" on center. For continuous row lengths, refer to supplied layout drawings. Add 1/4 " to the overall housing length indicated on your layout drawings. Position and secure the cross tees.
Install Fixture Above
3 T-Bar Grid

Important: Install T-Grid mounting brackets to required height.

Install the first fixture (or Standalone Unit) from above the T-Bar Grid.

!

ATTENTION: Install in accordance with local and national building and electric codes.

10/31/2023 page 2

ID-23 TruGroove Recessed Micro T-Grid Installation Instructions

NOTE: For Standalone fixtures skip to step 8

4 Install Joiner Aligners
Dimple engaged

Complete Wiring and
5 Connect Fixtures

Open Slots for Joiner
6 Brackets

In the joining fixtures install the joiner aligners in the trim extrusion just past the halfway point. Important: To insert aligners, tap gently with a hammer until middle dimple is fully inserted into the joiner channel. Be sure to engage the dimple as shown.
7 Install Joiner Brackets

Install the joiner fixture into the T-Bar Grid from above. Complete wiring and slide the fixtures together.
8 Secure Fixture on the Grid

Snap off the safety cover on joiner brackets slots with a flat head screw driver. This only needs to be done one sides that require joining.
9 Install Power Drop

Install supplied joiner brackets with 5/16" nut driver.

Secure the fixture to T-bar grid.
For continuous runs, finish installing run first and then secure to the T-bar grid.

Install power drop at desired location. At power location(s), remove factory installed wire cover. Feed power wires through. Complete all wiring connections using wire nuts supplied by others.

!

ATTENTION: Install in accordance with local and national building and electric codes.

10/31/2023 page 3

ID-23 TruGroove Recessed Micro T-Grid Installation Instructions

Install CAT6 Cables for
9a POE Option

10 Install Wire Access Cover

11 Install Seismic Restraints

Install CAT6 cables and desired location.

Install wire access cover to close the fixture.

Install seismic restraints according tolocal building code requirements.

12a LED Pan Joiner - Symmetric 12b LED Pan Joiner - Asymmetric 13 Install Drop Lens Endcap

Mount the LED pan connector with the supplied screw in the joiner kit. Note: This step is not required for louvers.

Mount the LED Pan connector with the supplied screw in the joiner kit. There are two pieces for asymmetric fixtures. Note: This step is not required for louvers.

Flush
Push up drop lens endcap flush to bottom of trim while hand tightening with supplied screws.(8-18 x 3/8 Pan)

!

ATTENTION: Install in accordance with local and national building and electric codes.

10/31/2023 page 4 www.ledalite.com

ID-23 TruGroove Recessed Micro T-Grid Installation Instructions

14

15 Fixture Lens Installation

16 Fixture Lens Installation

Snap in lens into fixture. Note: Flush lens and drop lens are installed the same way. Flush lens is shown for reference. Standalone Units: Lenses are supplied in 2', 3', 4', 5', 6' or 8' lengths.
Continuous Runs: Lenses are pre-cut to a maximum of 8' lengths and are specific to run lengths. Consult layout drawings for placement. Installed lenses are removed in step 1. Installation Tip: For easier installation, start at a housing end or a joint by placing lens at an angle and squeezing in slightly from the other side to guide inside housing.
Once lens is positioned inside housing, starting on one end or joint, push upwards gently and work outward to complete the run.

Partially installed

Fully installed

!

ATTENTION: Install in accordance with local and national building and electric codes.

10/31/2023 page 5 www.ledalite.com

ID-23 TruGroove Recessed Micro T-Grid Installation Instructions

!

ATTENTION: Install in accordance with local and national building and electric codes.

10/31/2023 page 6 www.ledalite.com

ID-23 TruGroove Recessed Micro T-Grid Installation Instructions

Sensors in Rows

Single Sensor Controlling Whole Row 1. Purple & brown (or purple & grey/pink) control wires MUST be connected between fixtures.
Note: · A maximum of 8 drivers can be wired to one sensor; confirm fixture driver count with factory.

Alternate

Integral Sensor

1

Remote Sensor

4ft

Bottom view of fixtures
8ft

Multiple Sensors Controlling Separate Zones in a Row 2. Purple & brown (or purple & grey/pink) control wires MUST NOT be connected between zones.
Notes: · A maximum of 8 drivers can be wired to one sensor; confirm fixture driver count with factory. · Only one sensor is allowed on a wired zone. (Sensors can be paired together wirelessly via a mobile app).

Alternate Remote Sensor

Integral Sensor

Zone 1
8ft

2

Integral Sensor

Zone 2

Bottom view of fixtures
4ft

Sensor Spacing
· For correct operation, sensors should be placed a minimum distance of 8ft apart. · Wireless sensors should be placed no further than 40ft apart for good wireless signal connection.

Alternate Remote Sensor

Integral Sensor
4ft

Integral Sensor

Bottom view of fixtures Sensors too close

8ft

for correct operation.

Alternate Remote Sensor
Integral Sensor

Sensor

Zone 1
8ft

Integral Sensor Zone 2

Bottom view of fixtures Sensors at minimum

4ft

required distance

for correct operation.

Integral Sensor

40ft Max.

Bottom view of fixtures Sensors at a maximum distance of 40ft apart.

Important Consideration When Using Sensors in a Row

Alternate Remote Sensor

· For fixtures with wireless sensors (CS, SB or RA options): DO NOT connect fixture purple & brown (or purple & grey/pink) control wires to an external dimming switch.

Fixture mains wiring should not be connected to a circuit with an external on/off switch.

· For best aesthetic condition, place sensors at ends of row only so as not to break the continuous lens. · For better occupancy coverage in longer rows, sensors may be placed mid run, but keep in mind this will
break the continuous lens into discrete sections. Alternatively, remote sensor may be used, note the same

wiring rules will apply.

! ATTENTION: Install in accordance with national and local building and electrical codes.

10/31/2023 page 7 www.ledalite.com

ID-23 TruGroove Recessed Micro T-Grid Installation Instructions
Occupancy Sensor Coverage:
Note: Longer dimension of detection area (Y1, Y2) is parallel to longer dimension of the luminaire.

The detection area for the movement sensor can be roughly divided into two parts:
· Minor movement (person moving 3ft/s or 0.9m/s). · Major movement (person moving 3ft/s or 0.9m/s).

Daylight sensor
The light sensor measures the total amount of light in a circular field of approximately 80% of the PIR detection area. The following aspects should be observed during installation:
· Minimum distance from the window 2ft (0.6m). · Prevent light reflections from outside entering the
sensor (for example sunlight reflection on a car hood) as this will lead to incorrect light regulation.
As a guideline the formula 0.72 x H can be used to calculate the minimum distance between the window and sensor whereby H is the height from the bottom of the window to the sensor.

Photosensor spatial response

!

ATTENTION: Install in accordance with local and national building and electric codes.

10/31/2023 page 8 www.ledalite.com