Answer
Dec 10, 2025 - 03:07 PM
To connect and set up the FIRVENA EO-BAC-IP EnOcean IP Gateway for your building automation system, follow these steps:
1. **Power Connection:**
- Connect the gateway to a power source that matches the rated supply voltage and supply voltage range. The device supports 24 V DC / 24 V AC with a range of 10–32 V DC / 24 V AC (± 10 %).
- Ensure the rated input current is 50 mA and the rated input power is 1.2 W.
2. **Network Connection:**
- Connect the gateway to your network using Ethernet (BACnet/IP) with a speed of 10/100 Mbit/s via an RJ45 connector (pins 4, 5, 7, 8).
- Consider using Power over Ethernet (PoE) for power supply if needed.
3. **EnOcean Devices Connection:**
- The gateway supports a maximum of 40 devices (max. 20 with SmartACK) at a frequency of 868 MHz (optional 902 MHz).
- Use pins 4, 5, 7, and 8 when connecting EnOcean devices to the gateway.
4. **Installation and Configuration:**
- Install the gateway in a suitable location, preferably in the ceilings of buildings for optimal coverage.
- Access the web interface for clear management and configuration of the gateway.
- Configure the gateway to act as a repeater, enabling two-way communication and connection of EnOcean devices.
5. **Additional Features:**
- The gateway can convert raw data from EnOcean devices to specific quantities for integration into the BACnet network.
- Ensure the gateway complies with EMC standards for residential and industrial environments.
- Consider using optional accessories like external antennas for better signal coverage.
6. **Support and Contact Information:**
- For further assistance or inquiries, you can contact FIRVENA S. R. O. at the provided contact details:
- Address: Zámecké namésti 26, 738 01 Frydek-Mistek, Ceská Republika
By following these steps and guidelines from the user manual, you can successfully connect and set up the FIRVENA EO-BAC-IP EnOcean IP Gateway for your building automation system.
User Manual Q&A