Answer
Dec 03, 2025 - 04:24 PM
To wire an external device to the apollo RW1700-052APO REACH Output Module, follow these steps:
1. **For 100mA/12VDC or 50mA/24VDC External Device Driving Capability:**
- Refer to the wiring example provided in the user manual.
- Ensure that the 10KΩ EOL R resistor is correctly installed to monitor the cable connection status.
- Incorrect installation of the resistor may lead to the device not operating as intended.
2. **For Relay Switch Output:**
- Refer to the wiring example provided in the user manual.
- Ensure that the device connected to the unit does not draw more than 2A at 30V (no 220 VAC).
- Using mains voltage or drawing too much current through the output relay could damage the unit and void the warranty.
- Install a properly fire-rated cable between the third-party device and the output module according to the national code of practice.
It is crucial to follow the wiring instructions carefully to ensure proper functionality and to avoid damaging the unit. For more detailed information and illustrations, please refer to the user manual available on apollo-fire.co.uk or contact techsales@apollo-fire.com.
User Manual Q&A