To set the desired temperature values for both channels on the LAE AC1-5 Two Channel Universal Controller, follow these steps:
1. **Channel 1 Setpoint:**
- Press and release the "Modify Setpoint 1" button. The LED L1 will blink, and the display will show "1SP" for 1 second followed by the setpoint associated value.
- Use the "Decrease" or "Increase/Modify Setpoint 2" button to adjust the desired value within the minimum and maximum limits.
- To store the new value, press the "Info/Enter" button or wait for 10 seconds.
- To exit without saving, press the "Exit/Stand-by" button.
2. **Channel 2 Setpoint:**
- If the auxiliary output is set as thermostat control (OAU=THR), you can modify setpoint 2 during normal operation.
- Press and release the "Increase/Modify Setpoint 2" button. The LED L2 will blink, and the display will show "2SP" for 1 second if setpoint 2 is an absolute threshold (2SM=ABS). Alternatively, it will display "2DF" if setpoint 2 is relative to setpoint 1 (2SM=REL), followed by the value associated with the parameter.
- Use the "Decrease" or "Increase/Modify Setpoint 2" button to set the desired value.
- To store the new value, press the "Info/Enter" button or wait for 10 seconds.
- To exit without saving, press the "Exit/Stand-by" button.
By following these steps, you can easily set the desired temperature values for both channels on the LAE AC1-5 Two Channel Universal Controller as per the product manual instructions.