Answer
Oct 27, 2025 - 03:18 PM
The CERBERUS PYROTRONICS CZM-1 Remote Conventional Zone Module can power up to 15 Series 3 two-wire ionization or photoelectric smoke detectors. Additionally, it can support various initiating devices such as waterflow switches, thermal detectors, and manual stations. The CZM-1 can monitor an unlimited number of listed alarm causing shorting devices. It is designed to provide distributed conventional zoning by connecting to an ALD loop and offering one remote conventional initiating device circuit. The module supports both Class A (Style D) and Class B (Style B) wiring configurations.