To acknowledge and reset events using the , follow these steps as outlined in the instruction manual:
1. **Acknowledging Events:**
- When an event occurs, the display enters Alert mode, showing the event details.
- An audible alarm sounds, and the appropriate LED blinks.
- Press the acknowledge button displayed at the bottom of the screen to acknowledge the event and silence the local audible.
- Once all events are acknowledged, a reset button becomes available in the lower right side of the display.
2. **Resetting the System:**
- If notification appliances were active during the event, two additional buttons appear at the bottom of the screen to silence or unsilence the notification appliances.
- The system can only be reset with the notification appliances silenced.
- Press the reset button to reset the system after acknowledging all events and silencing the notification appliances.
3. **Navigating Through Events:**
- If more events are present than can be displayed on a single screen, a scroll bar appears to the right of the event list.
- Use the up and down navigation buttons to move through the list.
- The selected event is highlighted in the display.
- Press the More Info button to view details related to the selected event.
- Use the ESC (-) button to return to the previous screen.
By following these steps, users can effectively acknowledge and reset events using the SIEMENS PMI Person-Machine Interface. For more detailed information on PMI operation, refer to the FireFinder-XLS Manual, P/N 315-033744.