Answer
Oct 21, 2025 - 01:08 PM
To wire the Unitronics IO-AO6X Input-Output Expansion Module for analog outputs, follow these steps based on the user guide:
1. **Wiring Procedures:**
- Use crimp terminals for wiring with 26-12 AWG wire.
- Strip the wire to a length of 7±0.5mm (0.250–0.300 inches).
- Unscrew the terminal before inserting a wire.
- Insert the wire completely into the terminal.
- Tighten the terminal to secure the wire without exceeding a maximum torque of 0.5 N·m (5 kgf·m).
- Do not use tin, solder, or any other substance on stripped wire that might cause the wire strand to break.
- Install the wiring at a maximum distance from high-voltage cables and power equipment.
2. **Analog Outputs:**
- Shields should be earthed, connected to the earth of the cabinet.
- Do not connect unused outputs.
- An output can be wired to either current or voltage.
- Do not use current and voltage from the same source channel.
- The outputs’ COM signals are internally shorted.
3. **General I/O Wiring:**
- Input or output cables should not run through the same multi-core cable or share the same wire.
- Allow for voltage drop and noise interference with input lines used over an extended distance. Use properly sized wire for the load.
By following these wiring procedures and guidelines, you can ensure safe and proper wiring of the Unitronics IO-AO6X Input-Output Expansion Module for analog outputs. Always refer to the user guide for detailed instructions and specifications.
User Manual Q&A

Add New Comment