To test the Potter PFC-200RC Fire Alarm Control Panel, follow these steps as per the owner's manual:
1. **One Man Test Feature:** The panel has a "One Man Test" feature that allows for easy testing. Activate this mode to automatically reset the panel after testing.
2. **Test Switch:** Use the Test Switch on the panel to turn on all Alarm and Trouble indicators and outputs. This will simulate an alarm condition for testing purposes.
3. **Zone Disable Switch:** If needed, you can disable specific zones using the Zone Disable Switch for targeted testing.
4. **Releasing Circuit Disable Switch:** Similarly, the Releasing Circuit Disable Switch can be used to isolate the releasing circuit for testing.
5. **Pre-discharge Timer:** The panel features a pre-discharge timer that can be set from 0 to 60 seconds. Test this timer by activating it and observing the system's response.
6. **Discharge Timer:** Test the discharge timer by setting it to either 2 minutes or continuous mode and observing the system's behavior during this period.
7. **Visual Indicators:** While testing, monitor the visual indicators on the panel, including AC ON, ALARM, SUPERVISORY, TROUBLE, and DISCHARGED LEDs. These indicators provide real-time feedback on the system's status.
8. **LCD Display Panel:** Check the 32 character alpha-numeric LCD display for detailed information on alarm, trouble, and supervisory conditions during the test.
9. **Trouble Buzzer:** Ensure that the Trouble Buzzer activates during the test to alert users of any issues.
10. **Reset Delay:** The panel has a 3-second reset delay to prevent accidental resets. Hold the Reset Switch for this duration to reset the system after testing.
By following these steps and utilizing the various features of the Potter PFC-200RC Fire Alarm Control Panel, you can effectively test the system to ensure its proper functionality and readiness in case of an emergency.