Answer

Oct 16, 2025 - 03:56 PM
To test the Mircom MIX-FC351APA sensor, you can follow the testing procedures outlined in the instruction manual:
1. **Functional Magnet Test:** Use a test magnet to simulate smoke in the sensing chamber. Hold the test magnet in the designated area on the sensor. The sensor should alarm the panel.
2. **Smoke Entry Test:** Use canned aerosol simulated smoke to test the smoke detector. The sensor uses algorithms to process signals received from multiple sensors to determine alarm conditions and reduce false alarms.
3. **Direct Heat Method:** Use a hair dryer of 1000-1500 watts to test the thermistors. Direct the heat toward the thermistor, holding the heat source approximately 12 inches away from the detector.
4. **Multi-Criteria Testing:** Testifire® by SDi provides testing of the smoke, heat, and CO sensors. Follow the manufacturer's instructions for complete usage instructions.
5. **Functional Gas Test:** Use a tested and approved canned CO testing agent to verify the detector's ability to sense CO. Spray the CO agent into the top of the detector near the CO sensor opening for at least 1 second.
6. **Cleaning:** If the sensor needs cleaning, follow the steps outlined in the manual to remove dust and debris from the sensing chamber. Ensure the sensor is reinstalled properly before testing.
By following these testing procedures, you can ensure that your Mircom MIX-FC351APA sensor is functioning correctly and effectively detecting smoke, carbon monoxide, and heat as intended.
Add New Comment