Answer
Oct 16, 2025 - 02:26 PM
To set the address and configure the features of the Mircom RAM-300LCD Series Remote Annunciator, follow these steps:
1. **Address Setup:**
- Use DIP switch SW30 to select the annunciator address. Valid addresses are 1 to 6 for FA-300 Series and 1 to 7 for FX-350/351 Series.
- Set the address as per the following table:
- Address 1: SW30-1 ON, SW30-2 OFF, SW30-3 OFF
- Address 2: SW30-1 OFF, SW30-2 ON, SW30-3 OFF
- Address 3: SW30-1 ON, SW30-2 ON, SW30-3 OFF
- Address 4: SW30-1 OFF, SW30-2 OFF, SW30-3 ON
- Address 5: SW30-1 ON, SW30-2 OFF, SW30-3 ON
- Address 6: SW30-1 OFF, SW30-2 ON, SW30-3 ON
- Address 7 (FX-350/351): SW30-1 ON, SW30-2 ON, SW30-3 ON
2. **Feature Configuration:**
- Use DIP switch SW31 to select various features. Each position of SW31 corresponds to a specific function. Refer to the table provided in the manual for detailed settings.
- For example, to disable the System Reset Button, set SW31-1 to ON. To enable it, set it to OFF.
- Similarly, configure other features like Signal Silence, Fire Drill, Lamp Test, and Buzzer Silence based on your requirements.
3. **Wiring:**
- Wire the RAM-300LCD using Twisted Shielded Pair for RS-485 connection.
- Follow the wiring guidelines provided in the manual based on the number of annunciators and total wiring run length.
- Ensure proper gauge and type of cable (FPL, FPLR, or FPLP) are used for power and data connections.