Answer
Oct 14, 2025 - 08:49 AM
To install the Goodman BAYSPEK070 Single Point Entry Kit in your unit, follow these steps as outlined in the user manual:
1. **Check for Shipping Damage:** Before installation, inspect the kit for any shipping damage. If damage is found, report it to the carrier immediately.
2. **Verify Power Supply Compatibility:** Ensure that the power supply available complies with the specifications indicated on the single power entry kit nameplate, heater, and unit model being used.
3. **Field Electrical Connections:** All field electrical connections and wiring must be done in accordance with the National Electrical Code and local electrical codes.
4. **Mounting the SPEK:**
- Remove the Control/Heat panel.
- Mount the SPEK below the Heater Controls using the provided screws.
- Pass the unit power wires provided with the SPEK through the Control box base and route them up to the unit contactor.
5. **Electrical Connections:**
- Make all electrical connections to the unit and heater following the appropriate wiring diagram provided with the SPEK.
- Place the included SPEK wiring diagram on the inner surface of the Control/Heater access panel next to the unit wiring diagram.
6. **Nameplate Labels:**
- Attach the two nameplate labels included with the single power entry kit to the air conditioning unit or heat pump unit as illustrated in the manual.
- The smaller label should cover the unit's MCA and Fusing information.
7. **High Voltage Field Wiring:**
- Ensure all field wires are rated 75°C minimum.
- Connect the power supply to the terminal block on the SPEK and ground wire to the ground lug.
- Reinstall the Control/Heat access panels and apply power to the unit.
8. **Low Voltage Wiring (24 Volts):**
- All low voltage connections are made to the heater via polarized plugs.
- Connect the low voltage controls to the room thermostat following the field wiring diagram.
By following these installation steps and referring to the detailed instructions in the user manual, you can safely and correctly install the Goodman BAYSPEK070 Single Point Entry Kit in your unit.
User Manual Q&A

Add New Comment