Answer
Oct 07, 2025 - 01:43 PM
To set the module address for the Aspar RS485 MODBUS Module 6RO 6 Temperature Inputs, you can use the switches on the module itself. The module address can be set within the range of 0 to 31 using the switches. Addresses from 32 to 255 can be set via RS485 or USB.
Here is a breakdown of how to set the module address using the switches:
- **Switch 1:** Represents the module address +1
- **Switch 2:** Represents the module address +2
- **Switch 3:** Represents the module address +4
- **Switch 4:** Represents the module address +8
- **Switch 5:** Represents the module address +16
You can refer to the table provided in the user manual to determine the appropriate switch settings for the desired module address. Make sure to set the switches accordingly before powering on the module.
If you need to set an address beyond 31, you can do so via RS485 or USB communication methods as outlined in the manual.
Always ensure that the module address is correctly set to avoid communication conflicts within the Modbus network.