Answer

Sep 29, 2025 - 03:45 PM
To configure the MOD-1AO module for communication over a Modbus network, you can use the Modbus Configurator software provided. Here are the steps to configure the communication settings and the default parameters:
1. **Accessing Communication Registers:**
- The communication registers can be accessed via the Modbus Configurator software using a USB connection to the module.
2. **Default Communication Settings:**
- **Address:** 1
- **Baud Rate:** 19200
- **Parity:** No
- **Data Bits:** 8
- **Stop Bits:** 1
- **Reply Delay [ms]:** 0
- **Modbus Type:** RTU
3. **Configuration Registers:**
- The configuration registers allow you to set and modify various communication parameters such as address, baud rate, parity, etc.
4. **Watchdog Function:**
- The watchdog function is a safety feature that resets the module if no valid message is received within a specified time. The default value is 0 milliseconds, which means the watchdog function is disabled.
5. **Indicators:**
- The LEDs on the module indicate different statuses such as power, communication activity, output voltage, and output current.
6. **Using Modbus Configurator:**
- The Modbus Configurator software is a universal program that allows you to configure all available modules, including the MOD-1AO. It enables you to set communication parameters, read/write registers, and observe real-time changes.
By following these steps and utilizing the Modbus Configurator software, you can easily configure the MOD-1AO module for communication over a Modbus network with the specified default settings.