Answer

Sep 18, 2025 - 02:39 PM
According to the manual for the IOTA ILBHI CP 2H HE SD HV Emergency LED Driver, here are the steps to verify the correct operation of the emergency LED driver:
1. **Normal Mode:** In normal operation, when AC power is present, the AC Driver operates the LED Module as intended. The ILBHI CP 2H HE SD HV is in standby charging mode, and the TBTS will be lit, indicating that the battery is being charged.
2. **Emergency Mode:** In case of an AC power failure, the ILBHI CP 2H HE SD HV will automatically switch to Emergency Mode. The LED Module will illuminate at a reduced output for a minimum of 120 minutes. When AC power is restored, the system will switch back to Normal Mode and resume battery charging.
3. **TBTS Light Indicators:** Verify that the TBTS light is on. The light will be Red while the battery is charging and Green when the battery is fully charged.
4. **Manual Test:** Press and hold the TBTS button for two seconds. The pilot light will blink, indicating the start of the test mode. Within five seconds, the LED Module should operate at a reduced light output. The test mode runs for 60 seconds. If the LED Module returns to normal operation after the test, the unit is ready for normal and emergency service.
5. **TBTS Status Indicators:** The TBTS provides various status indications through different colored lights. For example, a steady Green light indicates a fully charged battery, a steady Red light indicates the battery is charging, and flashing Green indicates the unit is performing a test.
By following these steps and observing the mentioned indicators, you can ensure that the emergency LED driver is functioning correctly and ready for both normal and emergency operation.