Answer
May 03, 2025 - 02:41 AM
To install and operate the STAHL 261440 Binary Output without Auxiliary Power Field Circuit, please follow the instructions provided in the manual. Here is a step-by-step guide:
1. Safety Precautions:
- Only qualified electricians should perform the installation, operation, and maintenance of the device.
- Do not open or modify the device. Repairs should only be done by the manufacturer.
- The device has an IP20 degree of protection and should be used in a clean and dry environment.
- The device complies with EMC regulations for industrial areas and may cause radio interference in residential areas.
2. Intrinsic Safety:
- The device is approved for intrinsically safe circuits up to zone 0 (gas) and zone 20 (dust) in the Ex area.
- Follow the relevant regulations for connecting intrinsically safe equipment and use approved measuring devices.
- If the device was previously used in non-intrinsically safe circuits, it should not be used in intrinsically safe circuits.
3. Installation in Ex Area (Zone 2):
- Install the device in a suitable, approved housing with at least IP54 protection.
- Only connect and disconnect non-intrinsically safe cables when the power is disconnected.
- If the device is damaged, subjected to an impermissible load, stored incorrectly, or malfunctions, it should be stopped and removed from the Ex area.
4. Potentially Dust-Explosive Areas:
- The device is not suitable for installation in zone 22.
- If you intend to use the device in zone 22, it must be installed in a housing according to IEC/EN 60079-31, following the maximum surface temperature limits.
5. Safety-Related Applications (SIL):
- For safety-related applications, refer to the safety manual available at r-stahl.com for specific instructions.
6. Operating and Indicating Elements:
- The device has a yellow "STAT" LED that indicates the switching state.
- There are connection terminal blocks for the safe area (black/green) and the Ex area (intrinsically safe Ex i, blue).
7. Installation:
- Take protective measures against electrostatic discharge before opening the front cover.
- Provide a switch/circuit-breaker near the device as a disconnect device.
- Install overcurrent protection (I ≤ 16 A) within the installation.
- Protect the device against mechanical or electrical damage by installing it in a suitable housing with the appropriate degree of protection.
- Disconnect the device from all power sources during installation, servicing, and maintenance, unless dealing with SELV or PELV circuits.
- Ensure proper insulation when installing multiple devices next to each other.
- The device can be snapped onto 35 mm DIN rails according to IEC/EN 60715.
8. Calculating a Valve Circuit:
- To connect a solenoid valve to the module, compare safety data and calculate the measurements.
- Consider the internal resistance, guaranteed voltage, current supply, maximum permissible cable resistance, effective coil resistance, current required by the solenoid coil, and voltage present at the coil with ISV.
- Use the provided formula to calculate the cable resistance (Rc) and ensure that all function requirements are met.
For more detailed information and technical specifications, please refer to the STAHL 261440 Binary Output without Auxiliary Power Field Circuit Instruction Manual.