PROTRONIX ADS-RH-D Duct Mounted Relative Humidity Sensor User Manual
PROTRONIX ADS-RH-D Duct Mounted Relative Humidity Sensor

ADS-RH-D is used to control ventilation, heat recovery and air conditioning systems by measuring relative humidity in the air duct.

  • relative humidity measuring
  • analog voltage / current output
  • output relay
  • fully calibrated
  • long-term stability

Description

ADS-RH-D is a capacitive relative humidity (RH) sensor.
It is equipped with an output relay with adjustable switching level and with analog 0-10V voltage / 0- 20mA (4-20mA) current output. The measurement is performed periodically after about 8s.

Based on these measurements it is possible to directly control the ventilation, air conditioning and heat recovery units.

Table of parameters

ParameterValueUnit
Supply voltage range14 – 30
18 – 30
V DC V AC
Power consumption1VA
Operating range0 – 100 %RH
Accuracy 20 – 80 %±4 %RH
Accuracy 0 – 100 %±6 %RH
Measuring period8s
Voltage output0 – 10V DC
Current output 10 – 20mA
Current output 24 – 20mA
Max. switching voltagemax. 250V AC
Max. switching currentmax. 5A
Working temperature0 to +40°C
Storage temperature-20 to +60°C
Storage humidity5 to 90 %RH
ProtectionIP20
Dimensions257x100x60mm

Explanation of abbreviations and technical terms can be found on our website in the Glossary section.

Output voltage/current dependence graph

Output voltage/current dependence graph

Internal layout

Internal layout

Relay switching level adjustment trimmer

  • turn to the left to decrease the relay switching level of RH, the relay will switch at lower RH level
  • turn to the right to increase the relay switching level of RH, the relay will switch at higher RH level

To avoid fast relay switching around the adjusted level the hysteresis of 15% is added automatically.

Voltage / current output petting – jumper JP1

  • Jumper in position U = voltage output.
    Voltage / current output petting - jumper JP1
  • Jumper in position I = current output.
    Voltage / current output petting - jumper JP1

Current output petting – jumper JP2

  • Jumper fitted = output 4-20mA.
    Current output petting - jumper JP2
  • Jumper not fitted = output 0-20mA.
    Current output petting - jumper JP2

LED indication

Blue

  • relay contacts closed = indication is on
  • relay contacts opened = indication is off

LED indication setting – jumper JP5:

  • Jumper fitted = LED enabled.
    LED indication setting - jumper JP5
  • Jumper not fitted = LED disabled.
    LED indication setting - jumper JP5

Connection example

Connection example

Installation

Installation Induction

If you connect other devices to the same AC power source as the ADS sensor, it is necessary to meet GND wiring of all analog inputs and outputs, as well as power wires.

Connection  Induction

Dimensions (mm)

Product Dimensions

Way to use

The product is intended for indoor use only.

What to do at the end of lifetime of this product

Discard the product in according to the electronic waste law and the EU directives.

The producer reserves the right of technical changes in order to product improvements its properties and functions without previous notice.

Support

Protronix s.r.o., Pardubická 177, Chrudim 537 01, Czech Republic www.protronix.cz/en/
www.careforair.eu/en/

 

Documents / Resources

PROTRONIX ADS-RH-D Duct Mounted Relative Humidity Sensor [pdf] User Manual
ADS-RH-D, Duct Mounted Relative Humidity Sensor

References

Leave a comment

Your email address will not be published. Required fields are marked *