Zenex 48X48 Universal PID Temperature Controller
User Manualv
This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net
Zenex 48X48 Universal PID Temperature Controller
I / O CONFIGURATION PARAMETERS
Parameters | Settings (Default Value) |
Input Type ![]() | Refer Table 1 (Default : Type K) |
Temperature Display Units ![]() | ![]() ![]() (Default : °C) |
Temperature Range ![]() | Min. to Max. specified for the selected Input Type (Refer Table 1) (Default : 1375) |
Control Output Type ![]() | Refer Table 2 (Default : Relay) |
Control Mode ![]() | ![]() ![]() (Default : PID) |
Control Logic ![]() | ![]() ![]() |
Hysteresis ![]() | 1 to 999°C or 0.1 to 99.9°C (Default : 2 or 0.2) |
Setpoint Low Limit ![]() | Min. Range to Setpoint High for the selected Input Type (Default : -200) |
Setpoint High Limit ![]() | Setpoint Low to Max. Range for the selected Input Type (Default : 1375) |
SUPERVISORY PARAMETERS
Parameters | Settings (Default Value) |
Tune / Optimize Command ![]() | ![]() ![]() (Default : No) |
Tune / Optimize Abort Command ![]() | ![]() ![]() |
Overshoot Inhibit ![]() | ![]() ![]() |
Overshoot Inhibit Factor ![]() | 1.0 to 2.0 (Default : 1.2) |
Self-tune on Setpoint Change ![]() | ![]() ![]() |
Offset for PV ![]() | -1999 to 9999 or -199.9 to 999.9 (Default : 0) |
PV Digital Filter for PV ![]() | 0.5 to 25.0 Seconds in steps of 0.5 Seconds (Default : 1.0) |
Permission for OP2/OP3 Setpoint Editing on Operator Page ![]() | ![]() ![]() |
Soak Abort Command on Operator Page ![]() | ![]() ![]() |
Soak Time Adjustment on Operator Page ![]() | ![]() ![]() |
Parameters | Settings (Default Value) |
Utility Option ![]() | ![]() ![]() ![]() |
Slave ID ![]() | 1 to 127 (Default : 1) |
Baud Rate ![]() | 1200, 2400, 4800, 9600 (Default : 9600) |
Communication Write Enable ![]() | ![]() ![]() |
PID CONTROL PARAMETERS
Parameters | Settings (Default Value) |
% Output Power ![]() | Not Applicable (Default : Not Applicable) |
Cycle Time ![]() | 0.5 to 120.0 Seconds (in steps of 0.5 secs.) (Default : 0.5) |
Proportional Band ![]() | 0.1 to 999.9 (Default : 10.0) |
Integral Time ![]() | 0 to 1000 Seconds (Default : 100) |
Derivative Time ![]() | 0 to 250 Seconds (Default : 25) |
OP2 FUNCTION PARAMETERS
Parameters | Settings (Default Value) |
Output-2 Function Selection ![]() | ![]() |
OP2 Function : Alarm-1
Type ![]() | ![]() |
Setpoint ![]() | Min. to Max. Range for the selected Input type (Default : 0) |
Deviation Band ![]() | -1999 to 9999 or -199.9 to 999.9 (Default : 0) |
Window Band ![]() | 3 to 999 or 0.3 to 99.9 (Default : 3) |
Logic ![]() | ![]() ![]() |
Inhibit ![]() | ![]() ![]() |
Alarm Timer ![]() | 5 to 250 Seconds (Default : 10) |
OP2 Function : Auxiliary Control
Parameters | Settings (Default Value) |
Offset Value ![]() | (Min. Range – SP) to (Max. Range – SP) specified for the selected Input Type (Default : 0) |
Hysteresis ![]() | 1 to 999 or 0.1 to 99.9 (Default : 2 or 0.2) |
Control Logic ![]() | ![]() ![]() |
OP2 Function : Blower / Compressor Control
Offset Value ![]() | 0 to 250 or 0.0 to 25.0 (Default : 0) |
Hysteresis ![]() | 1 to 250 or 0.1 to 25.0 (Default : 2 or 0.2) |
Time Delay ![]() | 00.00 to 10.00 Min. Sec (in steps of 5 Seconds) (Default : 00.00) |
OP3 FUNCTION PARAMETERS
Parameters | Settings (Default Value) |
Output-3 Function Selection ![]() | ![]() |
OP3 Function : Alarm-2
Type ![]() | ![]() |
Setpoint ![]() | Min. to Max. Range for the selected Input type (Default : 0) |
Deviation Band ![]() | -1999 to 9999 or -199.9 to 999.9 (Default : 0) |
Window Band ![]() | 3 to 999 or 0.3 to 99.9 (Default : 3) |
Logic ![]() | ![]() ![]() |
Inhibit ![]() | ![]() ![]() |
Alarm Timer ![]() | 5 to 250 Seconds (Default : 10) |
OP3 Function : Auxiliary Control
Offset Value ![]() | (Min. Range – SP) to (Max. Range – SP) specified for the selected Input Type (Default : 0) |
Hysteresis ![]() | 1 to 999 or 0.1 to 99.9 (Default : 2 or 0.2) |
Control Logic ![]() | ![]() ![]() |
SOAK TIMER PARAMETERS
Parameters | Settings (Default Value) |
Timer Enable ![]() | ![]() ![]() |
Time Units ![]() | ![]() |
Time Duration ![]() | 00.05 to 60:00 Min: Sec 00.05 to 99:55 Hrs: Min 1 to 999 Hours (Default : 00.10 Min: Sec) |
Timer-Start Band ![]() | 0 to 9999 or 0.0 to 999.9 (Default : 5 or 0.5) |
Holdback Strategy ![]() | ![]() |
Hold Band![]() | 1 to 9999 or 0.1 to 999.9 (Default : 5 or 0.5) |
Switch-Off Control Output at Timer End ![]() | ![]() ![]() |
Power-fail Recovery Method ![]() | ![]() |
OPERATOR PAGE AND PARAMETERS
Parameters | Settings |
Timer Start Command ![]() | ![]() ![]() |
Timer Abort Command ![]() | ![]() ![]() |
Time Duration ![]() | 00.05 to 60.00 M:S or 00.05 to 99.55 H:M or 1 to 999 Hours |
OP2 Function : Alarm-1
Alarm-1 Setpoint ![]() | Min. to Max. Range for the Input Type |
Alarm-1 Deviation Band ![]() | -1999 to 9999 or -199.9 to 999.9 |
Alarm-1 Window Band ![]() | 3 to 999 or 0.3 to 99.9 |
OP2 Function : Auxiliary Control
Auxiliary Control Setpoint ![]() | (Min. Range – SP) to (Max. Range – SP) for selected Input |
OP2 Function : Blower / Compressor Control | |
Blower / Compressor Setpoint ![]() | 0 to 250 or 0.0 to 25.0 |
OP3 Function : Alarm-2
Parameters | Settings |
Alarm-2 Setpoint ![]() | Min. to Max. Range for the Input Type |
Alarm-2 Deviation Band ![]() | -1999 to 9999 or -199.9 to 999.9 |
Alarm-2 Window Band ![]() | 3 to 999 or 0.3 to 99.9 |
OP3 Function : Auxiliary Control | |
Auxiliary Control Setpoint ![]() | (Min. Range SP) to (Max. Range SP) for selected Input |
Control Setpoint (SP) Locking | |
Setpoint Locking ![]() | ![]() ![]() |
TABLE- 1
Option | Range (Min. to Max.) | Resolution |
J Type T/C![]() | 0 to +960°C / +32 to +1760°F | Fixed 1°C / 1°F |
K Type T/C ![]() | -200 to +1375°C / -328 to +2508°F | |
T Type T/C ![]() | -200 to +385°C / -328 to +725°F | |
R Type T/C ![]() | 0 to +1770°C / +32 to +3218°F | |
S Type T/C ![]() | 0 to +1765°C / +32 to +3209°F | |
B Type T/C ![]() | 0 to +1825°C / +32 to +3092°F | |
N Type T/C ![]() | 0 to +1300°C / +32 to +2372°F | |
3-wire, RTD Pt100 ![]() | -199 to +600°C / -328 to +1112°F | |
3-wire, RTD Pt100 ![]() | -199.9 to 600.0°C / -199.9 to 999.9°F | 0.1°C / 0.1°F |
TABLE- 2
Option | What it means | Remarks |
![]() | Relay SSR (Solid State Relay) | Applicable for OP1 as Relay / SSR |
NOTE : Applicable Only For Zenex DC Linear Version
Option | What it means | Remarks |
![]() | 0 to 20mA current 4 to 20mA current | Applicable for OP1 as DC Linear Current |
![]() | 0 to 5 Volts 0 to 10 Volts | Applicable for OP1 as DC Linear Voltage |
FRONT PANEL LAYOUTKeys Operation
Symbol | Key | Function |
![]() | PAGE | Press to enter or exit set-up mode. |
![]() | DOWN | Press to decrease the parameter value. Pressing once decreases the value by one count; keeping pressed speeds up the change. |
![]() | UP | Press to increase the parameter value. Pressing once increases the value by one count; keeping pressed speeds up the change. |
![]() | ENTER | Press to store the set parameter value and to scroll to the next parameter on the PAGE. |
PV Error Indications
Message | PV Error Type |
![]() | Over-range (PV above Max. Range) |
![]() | Under-range (PV below Min. Range) |
![]() | Open (Sensor open / broken) |
ELECTRICAL CONNECTIONS
ENCLOSURE ASSEMBLY
MOUNTING DETAILS OUTPUT-2 MODULE
JUMPER SETTINGS OUTPUT-2 & OUTPUT-3
Output Type | Jumper Setting – A | Jumper Setting – B |
Relay | ![]() | ![]() |
SSR | ![]() | ![]() |
MOUNTING DETAILS SERIAL COMM. MODULEELECTRICAL CONNECTIONS
OUTPUT-2 & OUTPUT-3 : HARDWARE JUMPER SETTINGSSERIAL COMMUNICATION MODULE