SCT013G
SCT013G Split Core Current Transformer
Characteristic:
Safety lock buckle, easy installation, cable output
Technical index:
Mounting type: Free hanging (In-Line)
Material of core: Ferrite
Applicable standards: GB20840-2014
Operating temperature: -25℃ ~ +70℃
Storage temperature: -30℃ ~ +90℃
Frequency range: 50Hz-1KHz
Dielectric strength: Input (bare conductor)/Output AC 3.5KV/1min 50Hz
Output/Housing AC 3.5KV/1min 50Hz
Electrical parameters:The following parameters are typical values. The actual values shall be subject to the actual measurement of the product
Product picture printing is for reference only, subject to the actual product
SCT013 -005 | SCT013 -010 | SCT013 -015 | SCT013 -020 | SCT013 -025 | SCT013 -030 | SCT013 -050 | SCT013 -060 | SCT013 -100 | Secification of cable: 2 x 0.2mm² two core shielded cable Length of cable:100cm~105cm ![]() | ||
Rated input | 5A | 10A | 15A | 20A | 25A | 30A | 50A | 60A | 100A | A | |
Rated output | 1 | V | |||||||||
Accuracy | 1 | % | |||||||||
Weight | 50g | g |
Rated input | 5A | 10A | 15A | 20A | 25A | 30A | 50A | 60A | 100A | A | Secification of cable: 2 x 0.2mm² two core shielded cable Length of cable:100cm~105cm ![]() The secondary is not allowed to short circuits |
Rated output | 0.333 | V | |||||||||
Accuracy | 1 | % | |||||||||
Weight | 50g | g |
SCT013-000 | Secification of cable: 2 x 0.2mm² two core shielded cable Length of cable:100cm~105cm ![]() The secondary is not allowed to open circuit | ||
Rated input | 100A | A | |
Rated output | 50 | mA | |
Turns ratio | 1:2000 | – | |
Sampling resistance | 10 | Ω | |
Accuracy | 1 | % | |
Weight | 50g | g |
Dimensions(in mm±0.5) :
Documents / Resources
![]() | PowerUC SCT013G Split Core Current Transformer [pdf] Owner's Manual SCT013G Split Core Current Transformer, SCT013G, Split Core Current Transformer, Core Current Transformer, Current Transformer, Transformer |