User Guide for SALUS models including: RT310, RT310TX, RT310RF, RT310TX Wireless Programmable Thermostat, RT310TX, Wireless Programmable Thermostat, Programmable Thermostat, Thermostat
Thermostats – Salus
RT310RF Wireless non-programmable thermostat - Salus
File Info : application/pdf, 2 Pages, 3.30MB
DocumentDocumentRT310, RT310TX, RT310RF Button functions RT310 / RT310TX Thermostat 1 3 2 4 RXRT510 Receiver 5 6 7 8 Quick Guide Introduction RT310 / RT310TX / RT310RF is a digital room thermosat used to control room temperature. Device launching heating system by shorting terminal blocks, simultaneously informing the action and showing this information on the LCD display. Before use please read this manual carefully. Use only AA 1.5 V alkaline batteries in the thermostat. Place the batteries into the battery slot located under the cover. Do not use rechargeable batteries. Product compliance This product complies with the essential requirements and other relevant provisions of the following EU Directives: EMC 2014/30/EU, LVD 2014/35/EU, RED 2014/53/EU and RoHS 2011/65/EU. Full text of the EU Declaration of Conformity is available on www.saluslegal.com 868.0-868.6MHz; <13dBm Safety Information Use in accordance to national and EU regulations. Use the device as intended, keeping it in dry condition. Product for indoor use only. Installation must be carried out by a qualified person in accordance to national and EU regulations. Technical specification Thermostat supply Receiver supply Thermostat rating max Receiver rating max Outputs Temperature range RT310 2 x AA alkaline batteries 3 (1) A Voltage free NO / COM /NC terminals 5 - 35°C RT310TX 2 x AA alkaline batteries 230 V AC 16 (5) A Voltage free NO / COM terminals 5 - 35°C 1. Turn on the LCD backlight 2. Turn On/Off the Frost Mode 3. Increase button 4. Decrease button 5. When in Manual Mode, ON will turn the boiler on. 6. When in Manual Mode, OFF will turn the boiler off. 7. Receiver operates in automatic mode according to the thermostat 8. Receiver output is controlled by the On/Off slide switch. LCD Icon description 1 2 3 4 1. Heating Mode ON 5 2. Frost Protection Mode ON 6 3. RF signal indicator (only in RT310RF) 4. Low battery status 5. Temperature unit 6. Room / setpoint temperature RT310 Terminals description Terminal 1 - COM 2 - NC 3 - NO Description Common Terminal Switched Live OFF Switched Live ON RXRT510 Receiver terminals description Terminal NO COM L, N Description Switch Terminal Common Switch Terminal Supply (230 V AC) NO COM L N DIP Switch Settings The DIP Switches can be found on the rear of your thermostat. ON ON Span 9CPH ±0.25°C 6CPH TPI 12 Control feature TPI Span Operation When TPI is selected on DIP switch 2, the DIP switch 1 is functional. You can choose the Cycles Per Hour between a lower comfort level (6CPH) and a higher comfort level (9CPH). When Span is selected on DIP switch 2, the DIP switch 1 is not functional. The temperature accuracy of your thermostat is set to ± 0.25 °C. RT310 Wiring diagram AC 230 V L MAX 3 (1) A RT310 Thermostat COM NC NO RT310 Thermostat COM NC NO OR N RT310RF Wiring diagram Note: If you are using the RT310RF pack, the pairing between the thermostat and the receiver is already done. RT310TX Thermostat RXRT510 Receiver AC 230 V N L COM NO NL RT310TX Thermostat RXRT510 Receiver AC 230 V N L COM NO MAX 16 (5) A OR NL M M Change the Setpoint temperature Actual room temperature. Press or to set the temperature. 2 seconds timeout. Frost Protection Actual room temperature. Press button to turn On/Off frost protection. The Frostpoint temperature can be reviewed by pressing the UP button once, but can only be changed in Installer Mode. Sleep Mode 3 sec 3 sec When Sleep Mode is active all the thermostat functions will be paused. Press any button to stop the Sleep Mode. Pairing the RT310TX with the Receiver Note: If you are using the RT310RF pack, the pairing between the thermostat and the receiver is already done. If you bought the RT310TX and RXRT510 separately or if you want to re-pair thermostat with the receiver, make sure that the device is disconnected from the power supply and the switches on the receiver have been set to AUTO and ON. Then connect the receiver to the power supply and wait for the red LED to light steadily. Then switch to the OFF position and again to ON position quickly. The red flashing LED will confirm entering the pairing mode. Begin the pairing process TEST / PAIRING Press and hold TEST / PAIRING button for 3 seconds. 3 sec End the pairing process TEST / PAIRING Pairing process can take up to 9 minutes. Installer Mode 3 sec 3 sec 3 sec Press three buttons at the same time for 3 seconds. dxx Function d01 Temperature display increments d02 Temperature offset d03 Frost Protection setpoint temperature Reset of the RT310 thermostat Parameter Default value 0.1°C or 0.5°C 0.5°C +/- 3.0°C 0.0°C 5.0°C - 17.0°C 5.0°C TEST / PAIRING Once devices are successfully paired, LED on the receiver will go solid red. 3 sec Press and hold TEST / PAIRING button for 3 seconds to end the pairing process. Test the pairing process TEST / PAIRING Press TEST / PAIRING button to check the connection with 1 sec the receiver. TEST / PAIRING Press TEST / PAIRING button again to return to the main screen. 1 sec 3 TEST / PAIRING ON AUTO OFF MANUAL ON AUTO OFF MANUAL Press the RESET button once. You can use a paper clip. Your thermostat will be reset and will start up automatically. RESET Reset of the RT310TX thermostat Remove the batteries without pressing any button. Wait 2 minutes and insert the batteries again. Your device will be restarted. TEST / PAIRING + - When you want to change the batteries your device will use the internal memory to backup your settings. You have 30 seconds to change the batteries before losing your settings. + - NOTE: If you do not notice the "low battery" symbol displayed on the screen in time, it will shut down. In this case, after removing the old batteries, it is necessary to wait 5 minutes before inserting the new batteries. Otherwise, it is possible that a condenser will remain partially discharged and it can prevent the thermostat from restarting. SALUS Controls plc SALUS House Dodworth Business Park South, Whinby Road, Dodworth, Barnsley S75 3SP, UK. T: +44 (0) 1226 323961 E: sales@salus-tech.com E: techsupport@salus-tech.com www.salus-tech.com For PDF Installation guide please go to www.salus-manuals.com Issue Date: June 2019 V020 SALUS Controls is a member of the Computime Group. Maintaining a policy of continuous product development SALUS Controls plc reserve the right to change specification, design and materials of products listed in this brochure without prior notice.