PHILIPS DDC116-UL Single Zone Controller User Guide
PHILIPS DDC116-UL Single Zone Controller User Guide

The Philips Dynalite DDC116 load controller provides intelligent networked control of 0-10V and DALI broadcast lighting circuits, delivering the flexibility to easily scale your projects from room-based controls to complete building-wide networked controls.

This document provides some reference design examples of using the DDC116 controller and associated devices in different spaces. With these reference examples, you can quickly understand and perform typical controls designs and comply with different building and energy codes.

Each reference design example includes a standard sequence of operation and details on various control strategies supported in that design.

Note: The BOM table includes the standard part numbers for each device. If you are designing a project for standalone configuration with room-based controls behavior and no networking of rooms is required, then simply add ‘SSA’ suffix at the end of those respective part numbers. The ‘SSA’ suffix depicts that your design is based on products that offer pre-programmed software behaviors for standalone applications.

PABPA-SSA
PABPA-SSA

DUS804CS-UP-SSA-O or
DUS804CS-UP-SSA-V

DACM-SSA
DACM-SSA

DUS360CS-DA-SSA

Dedicated Standalone Devices

DDC116 – Single zone 0-10v/Relay Controller
PABPA-SSA – 7 Different engravings with 15 configurations
DACM-SSA – Configurable Ant umbra Comms Module
DUS804CS-UP-SSA-O or DUS804CS-UP-SSA-V – Preconfigured Ultrasonic Sensor
– and/or –
DUS360CS-DA-SSA – Configurable PIR/Daylight sensor

System Behavior
All devices that are linked together though DyNet wiring will behave as a control area and deliver a unified system behavior.

Sensor

  • Sensor configurable between occupancy (default) or vacancy mode
  • Configurable timeouts of 5, 10, 15, and 20min (default)
  • 1 min grace period on all timeouts
  • 20min witness mode to test functionality
  • Built-in daylight sensing
  • Flexibility to activate primary and secondary daylight zones

Switches

  • Recall preset lighting scenes
  • Ramping disables daylight harvesting
  • Ramping buttons only affect zones that are lit or “on”
  • Fully customizable configuration via System Builder for more demanding projects
12NCPart NumberDescription
913703376709DDC116-ULPhilips Dynalite Single Zone Controller
913703389909DUS360-DA-SSAPreprogrammed DUS360CR-DA for Single System Architecture
913703662809DUS804CS-UP-SSA-OPreprogrammed DUS804CS-UP Occupancy for Single System Architecture
913703662909DUS804CS-UP-SSA-VPreprogrammed DUS804CS-UP Vacancy for Single System Architecture
913703668809DACM-SSAPreprogrammed DACM for Single System Architecture
912401590702AL70-NW-G2-AR-4-8-FAWS- TLRD3-BZ70W, 70CRI, 4000K, Type 4, 120-277V, Selectable 50-57-65-72W, Bronze Finish
912401590701AL150-NW-G2-AR-3-8-FAWS- TLRD3-BZ150W, 70CRI, 4000K, Type 3, 120-277V, Selectable 95-115-130-145W, Bronze Finish
912401590709AL150-NW-G2-AR-4-8-FAWS- IMRI-TLRD3-BZ150W, 70CRI, 4000K, Type 4, 120-277V, Selectable 95-115-130-145W, Bi-level Motion Response, Bronze Finish
912401590699AL70-NW-G2-AR-3-8-FAWS- TLRD3-BZ70W, 70CRI, 4000K, Type 3, 120-277V, Selectable 50-57-65-72W, Bronze Finish
912401590708AL70-NW-G2-AR-4-8-FAWS- IMRI-TLRD3-BZ70W, 70CRI, 4000K, Type 4, 120-277V, Selectable 50-57-65-72W, Bi-level Motion Response, Bronze Finish
912401590710AL70-NW-G2-AR-5-8-FAWS- IMRI-TLRD3-BZ70W, 70CRI, 4000K, Type 5, 120-277V, Selectable 50-57-65-72W, Bi-level Motion Response, Bronze Finish
912401590706AL70-NW-G2-AR-3-8-FAWS- IMRI-TLRD3-BZ70W, 70CRI, 4000K, Type 3, 120-277V, Selectable 50-57-65-72W, Bi-level Motion Response, Bronze Finish
912401590704AL70-NW-G2-AR-5-8-FAWS- TLRD3-BZ70W, 70CRI, 4000K, Type 5, 120-277V, Selectable 50-57-65-72W, Bronze Finish
912401590707AL150-NW-G2-AR-3-8-FAWS- IMRI-TLRD3-BZ150W, 70CRI, 4000K, Type 3, 120-277V, Selectable 95-115-130-145W, Bi-level Motion Response, Bronze Finish
912401590711AL150-NW-G2-AR-5-8-FAWS- IMRI-TLRD3-BZ150W, 70CRI, 4000K, Type 5, 120-277V, Selectable 95-115-130-145W, Bi-level Motion Response, Bronze Finish
912401590703AL150-NW-G2-AR-4-8-FAWS- TLRD3-BZ150W, 70CRI, 4000K, Type 4, 120-277V, Selectable 95-115-130-145W, Bronze Finish
912401590705AL150-NW-G2-AR-5-8-FAWS- TLRD3-BZ150W, 70CRI, 4000K, Type 5, 120-277V, Selectable 95-115-130-145W, Bronze Finish

System Behavior

Control Strategies

Occupancy sensing
Detect the presence of occupancy to automatically turn off luminaires when an area is vacated.

Vacancy sensing
Configure lighting groups for manual on and automatic off behaviors.

Daylight harvesting
Sensors monitor available daylight and adjust luminaires to target foot-candle levels.

Lighting scenes
From local user interface stations, recall different lighting scenes.

Scheduling
Receive centralized scheduling network messages for lighting automation.

Receptacle control
With support for 20 Amp relay, easily control plug loads and receptacle outlets.

UL924 compliance
Use a dry contact input to directly trigger emergency luminaire response.

Networking
Connect multiple spaces together or integrate with a BMS system over BACnet.
Use head-end software to centrally monitor and manage spaces.

Lighting
Each lighting group is individually dimmable.

Manual override
From a user interface station, lighting can be turned on to a pre-selected scene, raised/lowered or be turned off. In a standalone configuration, system defaults to manual on/auto off mode. User must trigger the switch to turn the lights on.

Occupancy
If occupancy has not been detected after 19 minutes, lighting will be dimmed to 20%. After an additional 1-minute grace period where occupancy is still not detected, the system will turn the lighting off.
In a standalone configuration, daylight harvesting groups nearest to windows will automatically dim lighting for a target light level of 35 foot-candles.

Options if part of a larger network
Multiple rooms can be connected together as part of a larger DyNet network.

Monitor and manage areas through central head-end software. Access a graphical floor plan to visualize occupancy, light level, and temperature. Edit sensor time out and target foot-candle levels.

If needed, integrate via BACnet to 3rd party systems like HVAC or AV. User interface stations (Antumbra & Revolution) can even report the current room temperature to the central system.

Integrate and participate in Open ADR-based load shedding programs.

Diagram key
Daylight harvesting zoneDaylight harvesting zone
Mains line powerMains line power
10VDC10VDC
BeldenDyNet: Belden 150R/1501P CAT5e, or CAT6
Line PowerLine Power 120-277 VAC
dimmed luminaire10VDC dimmed luminaire
SymbolQtyPart codeDescription
Symbol Icon4DDC116-UL1 x 16 Amp relay & 0-10V to be mounted with J-box
Symbol Icon8DUS360CRMulti functional sensor. Occupancy and daylighting
Symbol Icon21 x PA4BPA-WW1 x DACM4 button Antumbra station & DACM

Diagram key
Daylight harvesting zoneDaylight harvesting zone
Mains line powerMains line power
10VDC10VDC
BeldenDyNet: Belden 150R/1501P CAT5e, or CAT6
Line PowerLine Power 120-277 VAC
dimmed luminaire10VDC dimmed luminaire
SymbolQtyPart codeDescription
Symbol Icon4DDC116-UL1 x 16 Amp relay & 0-10V to be mounted with J-box
Symbol Icon8DUS360CRMulti functional sensor. Occupancy and daylighting
Symbol Icon21 x PA4BPA-WW1 x DACM4 button Antumbra station & DACM

Diagram key
Daylight harvesting zoneDaylight harvesting zone
Mains line powerMains line power
10VDC10VDC
BeldenDyNet: Belden 150R/1501P CAT5e, or CAT6
Line PowerLine Power 120-277 VAC
10VDC dimmed luminaire
SymbolQtyPart codeDescription
Symbol Icon4DDC116-UL1 x 16 Amp relay & 0-10V to be mounted with J-box
Symbol Icon1DUS360CRMulti functional sensor. Occupancy and daylighting
occupancy and daylighting 1 DUS804CS-UPDual tech, multi functional sensor. Occupancy and daylighting.
Symbol Icon11 x PA2BPA-WW1 x DACM2 button Antumbra station & DACM
Symbol Icon11 x PA6BPA-WW1 x DACM6 button Antumbra station & DACM

SymbolQtyPart codeDescription
Symbol Icon1DDC116-UL1 * 16 Amp relay & 0-10V to be mounted with J-box
Symbol Icon3DUS360CRMulti functional sensor. Occupancy and daylighting
Diagram key
Mains line powerMains line power
10VDC0-10VDC
BeldenDyNet: Belden 1502R/1502P CAT5e, or CAT6
Line PowerLine Power 120-277 VAC
dimmed luminaire10VDC dimmed luminaire

Diagram key
Daylight harvesting zoneDaylight harvesting zone
Mains line powerMains line power
10VDC0-10VDC
BeldenDyNet: Belden 1502R/1502P CAT5e, or CAT6
Line PowerLine Power 120-277 VAC
10VDC dimmed luminaire
SymbolQtyPart codeDescription
Symbol Icon4DDC116-UL1 x 16 Amp relay & 0-10V to be mounted with J-box
Symbol Icon1DUS360CRMulti functional sensor. Occupancy and daylighting
occupancy and daylighting 1 DUS804CS-UPDual tech, multi functional sensor. Occupancy and daylighting.
Symbol Icon11 x PA6BPA-WW1 x DACM6 button Antumbra station & DACM

Diagram key
Daylight harvesting zoneDaylight harvesting zone
Mains line powerMains line power
10VDC10VDC
BeldenDyNet: Belden 1502R/1502P CAT5e, or CAT6
Line PowerLine Power 120-277 VAC
10VDC dimmed light luminaire
SymbolQtyPart codeDescription
Symbol Icon4DDC116-UL1 x 16 Amp relay & 0-10V to be mounted with J-box
Symbol Icon1DUS360CRMulti functional sensor. Occupancy and daylighting
occupancy and daylighting 1 DUS804CS-UPDual tech, multi functional sensor. Occupancy and daylighting.
Symbol Icon11 x PA2BPA -WW1 x DACM2 button Antumbra station & DACM
Symbol Icon11 x PA6BPA-WW1 x DACM6 button Antumbra station & DACM

Contact your nearest Signify dealer for more information.

QR Code
QR Code
www.dynalite.com

©2024 Signify Holding. All rights reserved.
Specifications are subject to change without notice. No representation or warranty as to the accuracy or completeness of the information included herein is given and any liability for any action in reliance thereon is disclaimed. Philips and the Philips Shield Emblem are registered trademarks of Koninklijke Philips N.V. All other trademarks are owned by Signify Holding or their respective owners.

PHILIPS Logo

Documents / Resources

PHILIPS DDC116-UL Single Zone Controller [pdf] User Guide
DDC116-UL, DUS360-DA-SSA, DUS804CS-UP-SSA-O, DUS804CS-UP-SSA-V, DDC116-UL Single Zone Controller, DDC116-UL, Single Zone Controller, Zone Controller, Controller

References

Leave a comment

Your email address will not be published. Required fields are marked *