PEPPERL FUCHS KFD2-UFC-Ex1.D Frequency Converter with Trip Values
Frequency Converter with Trip Values
KFD2-UFC-Ex1.D
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- Input for NAMUR sensors or dry contacts
- Input frequency 1 MHz … 5 kHz
- Current output 0/4 mA … 20 mA
- Relay contact and transistor output
- Start-up override
- Line fault detection (LFD)
- Up to SIL 2 acc. to IEC 61508/IEC 61511
Function
- This isolated barrier is used for intrinsic safety applications.
- The device is a universal frequency converter that changes a digital input signal into a proportional free adjustable 0/4 mA … 20 mA analog output signal and functions as a switch amplifier and a trip alarm.
- The functions of the switch outputs (2 relay outputs and 1 potential free transistor output) are easily adjustable [trip value display (min/max alarm), serially switched output, pulse divider output, error signal output].
- The device is easily configured by the use of keypad or with the PACTware configuration software.
- A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error message output.
- For additional information, refer to the manual and www.pepperl-fuchs.com.
Connection
Technical Data
General specifications | ||
Signal type Digital Input | ||
Functional safety related parameters | ||
Safety Integrity Level (SIL) SIL 2 | ||
Supply | ||
Connection terminals 23+, 24- or power feed module/Power Rail | ||
Rated voltage | Ur | 20 … 30 V DC |
Rated current | Ir | approx. 100 mA |
Power dissipation/power consumption | ≤ 2 W / 2.2 W |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | Input I: intrinsically safe: terminals 1+, 3- Input II: non-intrinsically safe: terminals 13+, 14- | |
Input I sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact | ||
Pulse duration > 50 µs | ||
Input frequency | 0.001 … 5000 Hz | |
Line fault detection | breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA | |
Input II startup override: 1 … 1000 s, adjustable in steps of 1 s | ||
Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA | ||
Open circuit voltage/short-circuit current | 18 V / 5 mA | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 outout III: terminasl 19+, 20- output IV: terminals 8+, 7- | |
Output I, II signal, relay | ||
Contact loading 253 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A | ||
Mechanical life | 5 x 107 switching cycles | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Output III electronic output, passive | ||
Contact loading 40 V DC | ||
Signal level | 1-signal: (L+) – 2.5 V (50 mA, short-circuit/overload proof) 0-signal: switched off (off-state current ≤ 10 µA) | |
Output IV | analog | |
Current range 0 … 20 mA or 4 … 20 mA | ||
Open loop voltage max. 24 V DC | ||
Load | max. 650 Ω | |
Fault signal | downscale I ≤ 3.6 mA , upscale ≥ 21.5 mA (acc. NAMUR NE43) | |
Collective error message Power Rail | ||
Transfer characteristics | ||
Input I | ||
Measurement range | 0.001 … 5000 Hz | |
Resolution 0.1 % of the measurement value , ≥ 0.001 Hz | ||
Accuracy 0.1 % of the measurement value , > 0.001 Hz | ||
Measuring time | < 100 ms | |
Influence of ambient temperature | 0.003 %/K (30 ppm) | |
Output I, II | ||
Response delay ≤ 200 ms | ||
Output IV | ||
Resolution | < 10 µA | |
Accuracy < 20 µA | ||
Influence of ambient temperature 0.005 %/K (50 ppm) | ||
Galvanic isolation | ||
Input I/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | ||
Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Mutual output I, II, III | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Output III/power supply and collective error basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff | ||
Output III/start-up override basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff | ||
Output III/IV | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff | |
Output IV/power supply and collective error | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
Start-up override/power supply and collective error | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
Interface/power supply and collective error | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
Interface/output III basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff | ||
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration via operating buttons via PACTware | ||
Labeling space for labeling at the front | ||
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU EN 61010-1:2010 | ||
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Input EN 60947-5-6:2000 | ||
Ambient conditions | ||
Ambient temperature | -20 … 60 °C (-4 … 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass 300 g | ||
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2 | ||
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | TÜV 99 ATEX 1471 | |
Marking | 1 II (1)G [Ex ia Ga] IIC 1 II (1)D [Ex ia Da] IIIC 1 I (M1) [Ex ia Ma] I | |
Supply | ||
Maximum safe voltage Um 40 V DC (Attention! Um is no rated voltage.) | ||
Input I | terminals 1+, 3-: Ex ia | |
Voltage Uo | 10.1 V | |
Current Io 13.5 mA | ||
Power Po 34 mW (linear characteristic) | ||
Input II | terminals 13+, 14- non-intrinsically safe | |
Maximum safe voltage Um | 40 V (Attention! The rated voltage can be lower.) | |
Output I, II terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe | ||
Maximum safe voltage Um 253 V (Attention! The rated voltage can be lower.) | ||
Contact loading | 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load | |
Output III | terminals 19+, 20- non-intrinsically safe | |
Maximum safe voltage Um Um 40 V (Attention! Um is no rated voltage.) | ||
Output IV terminals 8+, 7- non-intrinsically safe | ||
Maximum safe voltage | Um | 40 V DC (Attention! Um is no rated voltage.) |
Interface | RS 232 | |
Maximum safe voltage Um 40 V (Attention! Um is no rated voltage.) | ||
Certificate TÜV 02 ATEX 1885 X | ||
Marking | 1 II 3G Ex nA nC IIC T4 Gc | |
Output I, II | ||
Contact loading 50 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load | ||
Galvanic isolation |
Input I/other circuits | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | ||
International approvals | ||
FM approval | ||
Control drawing | 16-538FM-12 | |
UL approval E223772 | ||
IECEx approval | ||
IECEx certificate | IECEx TUN 04.0007 IECEx TSA 18.0007X | |
IECEx marking | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex ec nC IIC T4 Gc | |
General information | ||
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Assembly
Matching System Components

Accessories
Characteristic Curve
Maximum Switching Power of Output Contacts
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
- Pepperl+Fuchs Group www.pepperl-fuchs.com
- USA: +1 330 486 0002 pa-info@us.pepperl-fuchs.com
- Germany: +49 621 776 2222 pa-info@de.pepperl-fuchs.com
- Singapore: +65 6779 9091 pa-info@sg.pepperl-fuchs.com
- Release date: 2022-01-10
- Date of issue: 2022-01-10
Documents / Resources
![]() | PEPPERL FUCHS KFD2-UFC-Ex1.D Frequency Converter with Trip Values [pdf] Instruction Manual KFD2-UFC-Ex1.D Frequency Converter with Trip Values, KFD2-UFC-Ex1.D, Frequency Converter with Trip Values, Trip Values, Values |