NUMERIC logoUSER AND
INSTALLATION
MANUAL
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply SystemONFINITI+
1-3 kVA Online UPS
Uninterruptible Power Supply System
NEW ENERGY
TO POWER
www.numericups.com

PREFACE

Congratulations, We are delighted to welcome you to our family of customers. Thank you for choosing Numeric as your power backup solution provider; you now have access to our widest network of 254 service centres in the country.
Since 1984, Numeric has been enabling its clients to optimize their business with top notch power solutions that promise seamless and clean power with controlled environmental footprints.
We look forward to your continued patronage in the years to come!
This manual provides general information regarding installation and operation of Onfiniti+.

Disclaimer

  • The contents of this manual are bound to change without prior notice.
  • We have exercised reasonable care to give you an error-free manual. Numeric disclaims liability for any inaccuracies or omissions that may have occurred. If you find information in this manual that is incorrect, misleading or incomplete, we would appreciate your comments and suggestions.
  • Before you begin the installation of the UPS system, please read this manual thoroughly. The warranty of this product is null and void, if the product is abused/misused.

Introduction

Onfiniti+ from Numeric is a true on-line double conversion UPS available from a range of 1-3kVA, with and without a transformer. Onfiniti+ is easy to install and is a reliable power solution backed by the widest service support.
This user manual covers the UPS listed below:

  1. Onfiniti+ 1 kVA FM and Onfiniti+ 1 kVA FMI
  2. Onfiniti+ 2 KVA FM and Onfiniti+ 2 kVA FMI
  3. Onfiniti+ 3 kVA FM and Onfiniti+ 3 kVA FMI

Please verify the model of the UPS you have purchased before you begin your installation.

Important Safety Warning

Please comply strictly with all warnings and operating instructions in this manual. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully.

1-1. Transportation

  • Please transport the UPS system only in the original package to protect against shock and impact.

1-2. Preparation

  • Condensation may occur if the UPS system is moved directly from cold to warm environments. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate to the environment.
  • Do not install the UPS system near water or in moist environments.
  • Do not install the UPS system near a heater or where it would be exposed to direct sunlight.
  • Do not block ventilation holes in the UPS housing.

1-3. Installation

  • Do not connect appliances or devices which would overload the UPS system (e.g. laser printers) to the UPS output sockets.
  • Place cables in such a way that no one can step on or trip over them.
  • Do not connect domestic appliances such as hair dryers to UPS output sockets.
  • The UPS can be operated by any individual with no previous experience.
  • Connect the UPS system only to an earthed shock-proof outlet which must be easily accessible and close to the UPS system.
  • Please use only VDE-tested, CE-marked, ISI-marked mains cable (e.g. the mains cable of your computer) to connect the UPS system to the building wiring outlet (shock-proof outlet).
  • Please use only VDE-tested, CE-marked, ISI-marked power cables to connect the loads to the UPS system.
  • When installing the equipment, it should be ensured that the sum of the leakage current of the UPS and the connected devices does not exceed 3.5 mA.
  • The UPS is designed for linear load applications.

1-4. Operation

  • Do not disconnect the mains cable in the UPS system or the building wiring outlet (shock-proof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads.
  • The UPS system features its own current source (batteries). The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet.
  • In order to fully disconnect the UPS system, first press the OFF/Enter button to disconnect the mains.
  • Prevent fluids or other foreign objects from entering into the UPS system.

1-5. Maintenance, service and faults

  • The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.
    CAUTION – Risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system still connected to the battery may be electrically live and dangerous.
  • Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as bus capacitors.
  • Only persons adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
    CAUTION – Risk of electric shock. If the battery circuit is not isolated from the input voltage, hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present.
    • Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary measures specified below and any other measures necessary when working with batteries:
    – remove wristwatches, rings and other metal objects
    – use only tools with insulated grips and handles..
  • When changing batteries, install the same number and same type of batteries.
  • Do not attempt to dispose off batteries by burning them. This could cause battery explosion.
  • Do not open or destroy batteries. Escaping electrolyte may be toxic and can cause injury to the skin and eyes.
  • Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
  • Do not dismantle the UPS system.
  • Connect UPS to short circuit protected building wiring.
  • The UPS system has internal fuses on both DC & AC inputs. Those devices do not protect the upstream cables connected to DC & AC inputs and upstream breakers or fuses shall be set up in accordance with AC & DC wires ratings to meet the local national electrical code standard.

Installation and setup

NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use.
2-1. Rear panel view

UPS without ISO transformer:

NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - transformerUPS with ISO transformer:

NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - ISO

  1.  AC input
  2. Input circuit breaker
  3. USB communication port
  4. RS-232 communication port
  5. SNMP intelligent slot (optional)
  6. External battery connection
  7. Output receptacles
  8. Output terminal

2-2. Setup the UPS

Step 1 UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Please use the below recommended cable & breaker for input.

ModelWire size in sq. mm./No. of runsRecommended input breaker
1 kVA – FM/FMI1/310 A (C Curve)
2 kVA – FM/FMI2.5/320 A (C Curve)
3 kVA – FM/FMI4/332 A (C Curve)

Step 2 UPS output connection

  • For socket-type outputs, simply connect the devices to the outlets.
  • For terminal-type input or outputs, please follow the steps below, for the wiring configuration:
    a) Remove the small cover of the terminal block.
    b) Use AWG14 or 2.1 mm2 power cords.
    c) Upon completion of the wiring configuration, please check whether the wires are securely affixed.
    d) Put the small cover back to the rear panel.

Step 3 Communication connection

Communication port:

NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - Communication

To allow for unattended UPS shutdown/start-up and status monitoring, connect one end of the communication cable to the USB/RS-232 port and the other to the communication port of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through PC. The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When installing either SNMP or AS400 card in the UPS, it will provide advanced communication and monitoring options.
Note: USB port and RS-232 port can’t work at the same time.

Step 4 Turn on the UPS
Press the ON/Mute button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation.
Do not expect full battery run capability during this initial charge period.
Step 5 Install software
For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown. You may insert the provided CD into CD-ROM to install the monitoring software. If not, please follow the on-screen instructions to install the software. When your computer restarts, the monitoring software will appear as an orange plug icon located in the system tray, near the clock.

Step 6 External battery connection
This UPS series is not including batteries. Batteries are connected in a separate cabinet with protection. Please connect external batteries as per the below chart.

NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - battery

Recommended External Breaker Rating

S. No.Rating of UPSBattery Breaker
11 kVA – FM/FMI50 Adc (C Curve)
22 kVA – FM/FMI50 Adc (C Curve)
33 kVA – FM/FMI50 Adc (C Curve)

Operations

3-1. Button operation

ButtonFunction
 

 

 

ON/Mute button

•   Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn on the UPS.
•   Mute the alarm: When the UPS is on battery mode, press and hold this button for at least 5 seconds to disable or enable the alarm system. But it’s not applied to the situations when warnings or errors occur.
•   Up key: Press this button to display previous selection in UPS setting mode.
•   Switch to UPS self-test mode: Press and hold ON/Mute button for 5 seconds to enter UPS self-testing while in AC mode, ECO mode, or converter mode.
 

OFF/

Enter button

•   Turn off the UPS: Press and hold this button for at least 2 seconds to turn off the UPS. UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button.
•   Confirm selection key: Press this button to confirm selection in UPS setting mode.
 Select button•   Switch LCD message: Press this button to change the LCD message for input voltage, input frequency, battery voltage, output voltage and output frequency. It will return back to default display when pausing for 10 seconds.
•  Setting mode: Press and hold this button for 5 seconds to enter UPS setting mode when UPS is in standby or Bypass mode.
•  Down key: Press this button to display next selection in UPS setting mode.
ON/Mute + Select button•   Switch to bypass mode: When the main power is normal, press ON/Mute and Select buttons simultaneously for 5 seconds. Then UPS will enter Bypass mode. This action will be ineffective when the input voltage is out of acceptable range.

3-2. LCD Panel

NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - LCD Panel

Display Function
Remaining backup time information
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - IndicatesIndicates the remaining backup time in pie chart.
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - remainingIndicates the remaining backup time in numbers.
H: hours, M: minute, S: second
Fault information
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - warningIndicates the warning and fault occurrences.
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - warning2Indicates the warning and fault codes.
The codes are listed in details in section 5-5 .
Mute operation
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - Indicates6Indicates that the UPS alarm is disabled.
Output & battery voltage information
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - voltageIndicates the output voltage, frequency or battery voltage.
Vac: output voltage, Vdc: battery voltage, Hz: frequency
Load information
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - Indicates3Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%.
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - overloadIndicates overload.
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - UPSIndicates the load or the UPS output is short circuit.
Mode operation information
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - UPS2Indicates the UPS connects to the mains.
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - battery2Indicates the battery is working.
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - Indicates the bypassIndicates the bypass circuit is working.
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - ECOIndicates the ECO mode is enabled.
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - inverterIndicates the inverter circuit is working.
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - outputIndicates the output is working.
Battery information
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - Indicates the batteryIndicates the battery level by 0-25%, 26-50%, 51-75%, and 76-100%.
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - battery5Indicates the battery is fault.
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - battery voltageIndicates low battery level and low battery voltage.
Input & battery voltage information
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - voltage9Indicates the input voltage or frequency or battery voltage.
Vac: Input voltage, Vdc: battery voltage, Hz: input frequency

3-3. Audible Alarm

Battery ModeSounds every 4 seconds
Low BatterySounding every second
OverloadSounding twice every second
Fault BypassSounds continuously
ModeSounds every 10 seconds

3-4. LCD display wordings index

AbbreviationDisplay contentMeaning
ENANUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - ENAEnable
DISNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - DISDisable
ESCNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - ESCEscape
HLSNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - HLSHigh loss
LLSNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - LLSLow loss
BATNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - BATBattery
CFNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - CFConverter
TPNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - TPTemperature
CHNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - CHCharger
FUNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - FUBypass frequency unstable
EENUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - EEEEPROM error

3-5. UPS Setting

NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - Parameter 1

There are three parameters to set up the UPS.
Parameter 1: It’s for program alternatives. Refer to the below table.
Parameter 2 and parameter 3 are the setting options or values for each program.

01: Output voltage setting

InterfaceSetting
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - InterfaceParameter 3: Output voltage
For 200/208/220/230/240 Vac models, you may choose the following output voltage:
200: Presents output voltage is 200 Vac 208: Presents output voltage is 208 Vac 220: Presents output voltage is 220 Vac
230: Presents output voltage is 230 Vac (Default)
240: Presents output voltage is 240 Vac

02: Frequency converter enable/disable

InterfaceSetting
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - Interface2 Parameter 2 & 3: Enable or disable converter mode. You may choose the following two options:
CF ENA: Converter mode enable
CF DIS: Converter mode disable (Default)

03: Output frequency setting

InterfaceSetting
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - Output8Parameter 2 & 3: Output frequency setting.
You may set the initial frequency on battery mode:
BAT 50: Presents output frequency is 50 Hz
BAT 60: Presents output frequency is 60 Hz
If converter mode is enabled, you may choose the following output frequency:
CF 50: Presents output frequency is 50 Hz
CF 60: Presents output frequency is 60 Hz

04: ECO enable/disable

InterfaceSetting
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - Parameter Parameter 3: Enable or disable ECO function. You may choose the following two options: ENA: ECO mode enable
DIS: ECO mode disable (Default)

05: ECO voltage range setting

InterfaceSetting
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - voltage10Parameter 2 & 3: Set the acceptable high voltage point and low voltage point for ECO mode by pressing Down key or Up key.
HLS: High Loss Voltage in ECO mode in parameter 2.
For 200/208/220/230/240 Vac models, the setting range inparameter 3 is from +7 V to +24 V of the nominal voltage. (Default: +12 V)
LLS: Low Loss Voltage in ECO mode in parameter 2.
For 200/208/220/230/240 Vac models, the setting range in parameter 3 is from -7 V to -24 V of the nominal voltage. (Default: -12 V)

06: Bypass enable/disable when UPS is off

InterfaceSetting
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - Setting Parameter 3: Enable or disable Bypass function. You may choose the following two options:
ENA: Bypass enable
DIS: Bypass disable (Default)

07: Bypass voltage range setting

InterfaceSetting
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - DownParameter 2 & 3: Set the acceptable high voltage point and acceptable low voltage point for Bypass mode by pressing the Down key or Up key.
HLS: Bypass high voltage point
For 200/208/220/230/240 Vac models:
230-264: Setting the high voltage point in parameter 3 from 230 Vac to 264 Vac. (Default: 264 Vac)
LLS: Bypass low voltage point
For 200/208/220/230/240 Vac models:
170-220: Setting the low voltage point in parameter 3 from 170 Vac to 220 Vac. (Default: 170 Vac)

08: Autonomy limitation setting

InterfaceSetting
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - backupParameter 3: Set backup time on battery mode for general outlets.
0-999: Setting the backup time in minutes from 0-999 for general outlets on battery mode.
0: When setting as “0”, the backup time will be only 10 seconds.
999: When setting as “999”, the backup time setting will be disabled. (Default)

09: Battery minimum cut-off voltage setting

InterfaceSetting
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - acceptable Parameter 3: Set the acceptable battery minimum cut-off voltage point by pressing the Down key or Up key.
167-190: Setting the minimum battery cut-off voltage point in parameter 3 from 167 to 190.
Unit: 0.01 V/CELL (Default: 175)

10: Charger boost voltage setting

InterfaceSetting
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - charger Parameter 3: Set up the charger boost voltage. 225-240: Setting the charger boost voltage point in parameter 3 from 225 to 240.

Unit: 0.01 V/CELL (Default: 236)

11: Charger float voltage setting

InterfaceSetting
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - voltage5 Parameter 3: Set up the charger float voltage. 220-233: Setting the charger float voltage point in parameter 3 from 220 to 233.

Unit: 0.01 V/CELL (Default: 228)

00: Exit setting

3-6. Charging current setting

3 bat (36 V)/6 bat (72 V)/8 bat (96 V)For 10 A Model
J11 Adc
J22 Adc
J35 Adc
J4 (Default)10 Adc

3-7. Operating mode description

Operating modeDescription LCD display
Online modeWhen the input voltage is within the acceptable range, UPS will provide  pure and stable AC power to output. The UPS will also charge the battery at online mode.NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - LCD display
ECO modeEnergy saving mode:
When the input voltage is within the voltage regulation range, UPS will bypass voltage to output for energy saving.
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - Energy saving
Frequency converter modeWhen input frequency is within 40 Hz to 70 Hz, the UPS can be set at a constant output frequency, 50 Hz or 60 Hz. The UPS will still charge the battery under this mode.NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - Frequency
Battery modeWhen the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 seconds, UPS will backup power from battery.NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - Battery mode
Bypass modeWhen input voltage is within the acceptable range but UPS is overloaded, UPS will enter Bypass mode or Bypass mode can be set by front panel.
Alarm sounds every 10 seconds.
NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - Bypass mode
Standby modeUPS is powered off and no output supply power, but still can charge batteries.NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - Standby mode

3-8. Fault reference codes

Fault eventFault code
Bus start fail01
Bus over02
Bus under03
Bus unbalance04
Inverter soft start fail11
Inverter voltage high12
Charger fail45
Fault eventFault code
Inverter voltage low13
Inverter output short14
Battery voltage too high27
Battery voltage too low28
Over temperature41
Overload43

3-9. Warning indicator

WarningIcon (ffashing)Alarm
Low BatteryNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - battery voltageSounding every second
OverloadNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - overloadSounding twice every second
Battery is not connectedNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - battery2Sounding every second
 Over chargeNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - Sounding Sounding every second
Over temperatureNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - Sounding every secondSounding every second
Charger failureNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - Sounding every second5Sounding every second
Battery faultNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - Sounding every second8Sounding every second
Out of bypass voltage rangeNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - Sounding everySounding every second
Bypass frequency unstableNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - secondSounding every second
EEPROM errorNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - second9Sounding every second

Troubleshooting

If the UPS system does not operate correctly, please solve the problem by using the table below.

SymptomPossible causeRemedy
No indication and alarm even though the mains is normal.The AC input power is not connected well.Check if input power cord firmly connected to the mains.
The AC input is connected to the UPS output.Plug AC input power cord to AC input correctly.
The icon  and NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - battery2flashing on LCD display and alarm is sounding every second.The external or internal battery is incorrectly connected.Check if all batteries are connected well.
Fault code is shown as 27 and the iconNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - battery5 is lighting on LCD display and alarm is continuously sounding.Battery voltage is too high or the charger is fault.Contact your dealer.
Fault code is shown as 28 and the iconNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - battery5 is lighting on LCD display and alarm is continuously sounding.Battery voltage is too low or the charger is faulty.Contact your dealer.
The icon and NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - overloadis flashing on LCD display and alarm is sounding twice every second.UPS is overloaded.Remove excess loads from UPS output.
UPS is overloaded. Devices connected to the UPS are fed directly by the electrical network via the Bypass. 

Remove excess loads from UPS output.

After repetitive overloads, the UPS is locked in the Bypass mode. Connected devices are fed directly by the mains.Remove excess loads from UPS output first. Then shut down the UPS and restart it.
Fault code is shown as 43 and the icon NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - overload is lighting on LCD display and alarm is continuously sounding.The UPS shutdown automatically because of overload at the UPS output.Remove excess loads from UPS output and restart it.
Fault code is shown as 14 and the iconNUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - icon is lighting on LCD display and alarm is continuously sounding.The UPS shutdown automatically because short circuit occurs on the UPS output.Check output wiring and if connected devices are in short circuit status.
Symptom Possible cause Remedy
Fault code is shown as 45
on LCD display and alarm is
continuously sounding.
Charger is faulty.Contact your dealer.
Fault code is shown as 01, 02, 03, 04, 11, 12, 13 and 41 on LCD display and alarm is continuously sounding.A  UPS internal fault has occurred. There are two possible results:
1. The load is still supplied, but directly from AC power via Bypass.
2. The load is no longer supplied by power.
Contact your dealer
Battery backup time is shorter than nominal valueBatteries are not fully chargedCharge the batteries for
at least 5 hours and then
check capacity. If the problem still persists, consult your dealer.
Batteries defectContact your dealer to replace the battery.

If the problem persists, visit www.numericups.com to register your service request and contact our nearest after sales service department; or contact us.: 0484-3103266 / 4723266 with the below details:.

  1. Model number, Serial number
  2. Date on which the problem occurred
  3. LCD/LED display status, Buzzer alarm status
  4. Utility power condition, load type and capacity, environment temperature, ventilation condition
  5. The information (battery capacity, quantity) of external battery pack if the UPS is with external battery
  6. Other information for complete description of the problem

Storage and Maintenance

5.1 Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer.

NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System - deliver Be sure to deliver the used battery to a recycling facility or ship it to your dealer in the replacement battery packing material.

5.2 Storage
Before storing, charge the UPS for 5 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table:

Storage temperatureRecharge frequencyCharging duration
-25°C to 40°CEvery 3 months1-2 hours
40°C to 45°CEvery 2 months1-2 hours

5.3 Disposal
Ref standard: ISO 14001: 2015

  • After unpacking the UPS & Battery, the removed packaging materials like polythene paper, thermocole/polyethylene, carton box, nylon belt, nylon thread shall be collected and disposed through authorized recycler.
  • Batteries when found faulty/damaged must be handed over to identified authorized recycler or to Numeric, where it is disposed properly.
  • Battery contains harmful metals and chemicals such as nickel-cadmium, alkaline, mercury, nickel-metal hydride and lead acid, which contaminates if it is not disposed properly.
  • When batteries containing cadmium is used in fills, they will eventually dissolve and release the toxic substance than can seep into water supplies posing serious health hazards for the population/society.
    Hence, recycling of batteries will prevent pollution and also saves resource.

Specifications

6-1. UPS without ISO transformer

NOMINAL POWER* (KVA)1 KVA FM2 KVA 72 V FM2 KVA 96 V FM3 KVA 72 V FM3 KVA 96 V FM
PIDNU 72 01 701NU 72 01 703NU 72 01 705NU 72 01 707NU 72 01 709
Active power**1000 VA/800 W2000 VA/1600 W3000 VA/2400 W
INPUT
 Voltage rangeLow line transfer160/140/120/110 Vac ± 5%
(based on load percentage 100% – 80%/80% – 70%/70 – 60%/60% – 0)
Low line comeback175/155/135/125 Vac ± 5 %
(based on load percentage 100% – 80%/80% – 70%/70 – 60%/60% – 0)
High line transfer300 Vac ± 5%
High line comeback290 Vac ± 5%
Frequency range40 Hz ~ 70 Hz
PhaseSingle phase with ground
Power factor≧ 0.99 @ nominal input voltage
OUTPUT
Output voltage200/208/220/230/240 Vac
AC voltage regulation± 1%
Frequency range (Synchronized)46 – 54 Hz or 56 – 64 Hz
Frequency range (Battery mode)50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz
 Overload105%~110%: UPS shuts down after 10 min at battery mode or transfer to Bypass when the utility is normal 110%~130%: UPS shuts down after 1 min at battery mode or 2 min transfer to Bypass when the utility is normal 130%~150%: UPS shuts down after 3 secs at battery mode or 30 secs transfer to Bypass when the utility is normal
Current crest ratio3:1
Harmonic distortion≦ 3% THD (Linear load); ≦ 5% THD (Non-linear load)
Transfer TimeAC mode to battery modeZero
Inverter to Bypass4 ms (Typical)
Waveform (Battery mode)Pure sinewave
EXTERNAL BATTERY
Battery typeDepending on the capacity of external batteries
Battery numbers36868
Maximum battery AH120120100120100
Current of external BAT pack30 Adc max30 Adc max30 Adc max45 Adc max32 Adc max
Charging current 10 A model (FM)1 / 2 / 5 / 10 A (adjustable)
Charging voltage41.0 Vdc ± 1%82.1 Vdc ±1%109.5 Vdc ±1%82.1 Vdc ±1%109.5 Vdc ±1%
PHYSICAL
Dimension W x D x H (in mm)145 x 290 x 225145 x 397 x 238
Net weight (kgs)4.97.98.3
ENVIRONMENT
Operation humidity20-90% RH @ 0- 40°C (non-condensing)
Noise levelLess than 50 dBA @ 1 Meter (AVG)
MANAGEMENT
Smart RS-232 or USBSupports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and MAC
Optional SNMPPower management from SNMP manager and web browser

*FM – Floor Mount; FMI – Floor Mount with isloation transformer.
**Derate capacity to 80% of capacity in frequency converter mode or when the output voltage is adjusted to 208.
Vac/200 Vac. Product specifications are subject to change without further notice.

6-2. UPS with ISO transformer

NOMINAL POWER* (KVA)1 KVA FMI2 KVA 72 V FMI2 KVA 96 V FMI3 KVA 72 V FMI3 KVA 96 V FMI
PIDNU 72 01 702NU 72 01 704NU 72 01 706NU 72 01 708NU 72 01 710
Active power**1000 VA/800 W2000 VA/1600 W3000 VA/2400 W

 INPUT

 Voltage rangeLow line transfer160/140/120/110 Vac ± 5%
(based on load percentage 100% – 80%/80% – 70%/70 – 60%/60% – 0)
Low line comeback175/155/135/125 Vac ± 5%
(based on load percentage 100% – 80%/80% – 70%/70 – 60%/60% – 0)
High line transfer300 Vac ± 5%
High line comeback290 Vac ± 5%
Frequency range40 Hz ~ 70 Hz
PhaseSingle phase with ground
Power factor≧ 0.99 @ nominal input voltage
OUTPUT
Output voltage200/208/220/230/240 Vac
AC voltage regulation± 2%
Frequency range (Synchronized)46 – 54 Hz or 56 – 64 Hz
Frequency range (Battery mode)50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz
 Overload105%~110%: UPS shuts down after 10 min at battery mode or transfer to Bypass when the utility is normal
110%~130%: UPS shuts down after 1 min at battery mode or 2 min transfer to Bypass when the utility is normal
130%~150%: UPS shuts down after 3 secs at battery mode or 30 secs transfer to Bypass when the utility is normal
Current crest ratio3:1
Harmonic distortion≦ 3% THD (Linear load); ≦ 5% THD (Non-linear load)
Transfer TimeAC mode to battery modeZero
Inverter to Bypass4 ms (Typical)
Waveform (Battery mode)Pure sinewave
EXTERNAL BATTERY
Battery typeDepending on the capacity of external batteries
Battery numbers36868
Maximum battery AH120120100120100
Current of external BAT pack30 Adc max30 Adc max30 Adc max45 Adc max32 Adc max
Charging current 10 A model (FM)1 / 2 / 5 / 10 A (adjustable)
Charging voltage41.0 Vdc ± 1%82.1 Vdc ±1%109.5 Vdc ±1%82.1 Vdc ±1%109.5 Vdc ±1%
PHYSICAL
Dimension W x D x H (in mm)145 x 290 x 458145 x 397 x 458
Net weight (kgs)263536
ENVIRONMENT
Operation humidity20-90% RH @ 0- 40°C (non-condensing)
Noise levelLess than 50 dBA @ 1 Meter (AVG)
MANAGEMENT
Smart RS-232 or USBSupports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and MAC
Optional SNMPPower management from SNMP manager and web browser

*FM – Floor Mount; FMI – Floor Mount with isloation transformer.
**Derate capacity to 80% of capacity in frequency converter mode or when the output voltage is adjusted to. 208 Vac/200 Vac. or operating temperature is > 40 deg C and > 50 deg C Product specifications are subject to change without
further notice.

Head Office
10th Floor, Prestige Center Court,
Office Block, Vijaya Forum Mall, 183,
N.S.K Salai, Vadapalani,
Chennai – 600 026.
Phone: +91 44 4656 5555

Regional Offices

New Delhi
B-225, Okhla Industrial Area,
4th Floor, Phase-1,
New Delhi – 110 020.
Phone: +91 11 2699 0028
Mumbai
C/203, Corporate Avenue, Atul Projects,
Near Mirador Hotel, Chakala,
Andheri Ghatkopar Link Road,
Andheri (East), Mumbai – 400 099.
Phone : +91 22 3385 6201
Kolkata
Bhakta Tower, Plot No. KB22,
2nd & 3rd  Floor, Salt Lake City,
Sector – III, Kolkata – 700 098.
Phone : +91 33 4021 3535 / 3536
Chennai
10th Floor, Prestige Center Court,
Office Block, Vijaya Forum Mall,
183, N.S.K Salai, Vadapalani,
Chennai – 600 026.
Phone : +91 44 3024 7236 / 200

Branch Offices

Chandigarh
SCO 4, First Floor, Sector 16,
Panchkula, Chandigarh – 134 109.
Phone : +91 93160 06215
Dehradun
Unit-1 and 2, Chakrata Road,
Vijay Park Dehradun – 248001.
Uttrakhand
Phone : +91 135 661 6111
Jaipur
Plot No. J-6, Scheme-12B,
Sharma Colony, Bais Godown,
Jaipur – 302 019.
Phone : +91 141 221 9082
Lucknow
209/B, 2nd Floor, Cyber Heights,
Vibhuti Khand, Gomti Nagar,
Lucknow – 226 018.
Phone : +91 93352 01364
Bhubaneswar
N-2/72 Ground Floor, IRC Village,
Nayapally, Bhubaneswar – 751 015.
Phone: +91 674 255 0760
Guwahati
House No 02,
Rajgarh Girls High School Road
(Behind Rajgarh Girls High School),
Guwahati – 781 007.
Phone : +91 96000 87171
Patna
405, Fraser Road, Hemplaza,
4th Floor, Patna – 800 001.
Phone : +91 612 220 0657
Ahmedabad
A-101/102, Mondeal Heights,
Beside Hotel Novotel, Near Iscon Circle,
S G Highway, Ahmedabad – 380 015.
Phone : +91 79 6134 0555
Nagpur
Plot.No.174, H.No.4181/C/174, 1st Floor,
Loksewa Housing Society, Near Dr. Umathe
& Mokhare College, Bhamti Road,
Lokseva Nagar, Nagpur – 440 022.
Phone : +91 712 228 6991 / 228 9668
Ranchi
202 & 203, 2nd Floor, Sunrise Forum,
Bardwan Compound, Lalpur, 2nd Floor,
Ranchi – 834 001.
Phone : + 91 98300 62078
Bhopal
Plot No. 2, 221, 2nd Floor,  Akansha Complex,
Zone-1, M.P.Nagar, Bhopal– 462 011.
Phone : +91 755 276 4202
Pune
Pinacle 664 park avenue, 8th floor,
Plot no 102+103, CTS No. 66/4,
Final, 4, Law College Rd, Erandwane,
Pune, Maharashtra – 411 004.
Phone : +91 +20 6729 5624
Bengaluru
No-58,  First Floor, Firoze White Manor,
Bowring Hospital Road,
Shivajinagar, Bangalore -560 001.
Phone : +91 80 6822 0000
Coimbatore
No. B-15, Thirumalai Towers, No. 723,
1st Floor, Avinashi Road, Coimbatore – 641 018.
Phone : +91 422 420 4018
Hyderabad
Prestige Phoenix Building,
1st Floor, Survey no. 199,
No. 6-3-1219/J/101 & 102, Uma Nagar,
Opposite to Begumpet Metro Station
Begumpet 500016
Phone: +91 40 4567 1717/2341 4398/2341 4367
Kochi
Door No. 50/1107A9, JB Manjooran Estate,
3rd Floor, Bypass Junction,
Edappally, Kochi – 682 024.
Phone : +91 484 6604 710
Madurai
12/2, DSP Nagar,
Dinamalar Avenue,
Madurai – 625 016.
Phone : +91 452 260 4555

NUMERIC logoContact us.:
Email : customer.care@numericups.com
Phone : 0484-3103266 / 4723266
www.numericups.com

Documents / Resources

NUMERIC ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System [pdf] User Manual
1 kVA FM, 1 kVA FMI, 2 kVA FM, 2 kVA FMI, 3 kVA FM, 3 kVA FMI, ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System, ONFINITI plus, ONFINITI plus Power Supply System, 1-3 kVA Online UPS Uninterruptible Power Supply System, 1-3 kVA Online UPS Power Supply System, Online UPS Uninterruptible Power Supply System, Online UPS Power Supply System, Online Power Supply System, UPS Power Supply System, Power Supply System, Power Supply

References

Leave a comment

Your email address will not be published. Required fields are marked *