MOXA ioLogik E1500 Series I-O Ethernet RemoteMOXA ioLogik E1500 Series I-O Ethernet Remote pro

Package Checklist

  • 1 ioLogik E1500 series remote I/O product
  • Quick installation guide (printed)

Specifications

Input Current150 mA @ 24 VDC
Input Voltage12 to 48 VDC
Operating Temperature-40 to 85°C (-40 to 185°F)

Installation

I/O Wiring

DI dry contact modeMOXA ioLogik E1500 Series I-O Ethernet Remote 1

DI wet contact mode (Ch-Ch isolation)MOXA ioLogik E1500 Series I-O Ethernet Remote 2

DI wet contact PNP/NPN mode (No CH-CH isolationMOXA ioLogik E1500 Series I-O Ethernet Remote 3

DIO_DI wet contact mode (no CH-CH isolation)MOXA ioLogik E1500 Series I-O Ethernet Remote 4

DIO_DO sink mode MOXA ioLogik E1500 Series I-O Ethernet Remote 5

Mounting and Cabling

The ioLogik E1500 can be used with both DIN rail and wall mounts. Whenmounting on a DIN rail, release the bottom mounting kit, install the ioLogik on the rail, and then restore the bottom mounting kit to fix the ioLogik to the rail. When using wall mounting, release both the upper and bottom DIN rail kits. The ioLogik E1500 has an M12 Ethernet port for connecting either a standard direct-Ethernet or crossover-Ethernet cable via a locking M12 connector.
Power and Networking
Connect the +12 to +48 VDC power line to the ioLogik E1500’s terminal block V+ terminal, and connect the ground from the power supply to the V- terminal. If an earth ground is available, connect the ground pin

LED Indicators

TypeColorDescription
PWRGreenSystem power in ON
OffSystem power is OFF
RDYGreenSystem is ready
Green BlinkingLocated
RedSystem Booting-up Error
Green/Red

Blinking

Safe Mode
Red BlinkingFirmware upgrade (LED flashes for 3

seconds then stays red until restart)

OffSystem is not ready
LANGreen100 Mbps
Amber10 Mbps
BlinkingData Transmitting
OffEthernet Off
EXPGreenExpansion Mode Ready
RedConfiguration Failure
OffStand-alone Mode
DIGreenChannel ON
OffChannel OFF
DIOGreenChannel ON
OffChannel OFF

System Configuration

Configuration via Web Console
Configuration of an ioLogik E1500 is done via the web console.

  • Default IP Address: 192.168.127.254
  • Subnet Mask: 255.255.255.0

Note: Be sure to configure the host PC’s IP address to the same subnet as the ioLogik E1500. For example, 192.168.127.253

ioSearch Utility

ioSearch is a search utility that helps users locate an ioLogik E1500 on the local network. The latest version of the utility can be downloaded from Moxa’s website

Load Factory Default Settings

There are three ways to restore the ioLogik E1500 to the factory default settings.

  •  Remove the two screws and the aluminum plate, and then press and hold the RESET button for 5 seconds.
  •  Right-click the specified ioLogik in the ioSearch utility and select Reset to Default.
  •  Select Load Factory Default from the web console.

Modbus Address Table

Refer to the user’s manual for details of the ioLogik’s Modbus address, or refer to the start address of the I/O channels in the web console under User-defined Modbus Addressing  Default Address.

How to Download the Software

Step 1
Click on the following link to open the Support & Downloads search tool:
http://www.moxa.com/support/support_home.aspx?isSearchShow=1
Step 2
Type the model name in the search box or select a product from the drop down box and then click Search.MOXA ioLogik E1500 Series I-O Ethernet Remote 6
Step 3
Click the Software Packages link to download the latest software for the productMOXA ioLogik E1500 Series I-O Ethernet Remote 7

Documents / Resources

MOXA ioLogik E1500 Series I-O Ethernet Remote [pdf] Installation Guide
ioLogik E1500 Series I-O Ethernet Remote, ioLogik E1500 Series, I-O Ethernet Remote

References

Leave a comment

Your email address will not be published. Required fields are marked *