MeanWell SDR-960-24 Series 960W Single Output Industrial DIN RAIL with PFC Function Owner’s Manual
MeanWell SDR-960-24 Series 960W Single Output Industrial DIN RAIL with PFC Function

Features

  • User’s Manual
  • AC input 180-264VAC only
  • 130% peak load capability
  • 110mm slim design
  • Built-in active PFC function compliance to BS EN/EN61000-3-2
  • High efficiency 94% and low power dissipation
  • Protections: Short circuit / Overload/ Over voltage/Over temperature
  • Cooling by free air convection
  • Built-in constant current limiting circuit
  • Can be installed on DIN rail TS-35/7.5 or 15
  • UL508(industrial control equipment)approved
  • BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
  • Current sharing up to 3840W(3+1)
  • Built-in DC OK relay contact
  • 100% full load burn-in test
  • 3 years warranty

SPECIFICATION

MODELSDR-960-24SDR-960-48
OUTPUTDC VOLTAGE24V48V
RATED CURRENT40A20A
CURRENT RANGE0 ~ 40A0 ~ 20A
RATED POWER960W960W
PEAK CURRENT52A26A
PEAK POWER               Note.61248W (3sec.)
RIPPLE & NOISE (max.) Note.2180mVp-p250mVp-p
VOLTAGE ADJ. RANGE24 ~ 28V48 ~ 55V
VOLTAGE TOLERANCE Note.3±1.0%±1.0%
LINE REGULATION±0.5%±0.5%
LOAD REGULATION±1.0%±1.0%
SETUP, RISE TIME1000ms, 100ms/230VAC at full load
HOLD UP TIME (Typ.)14ms / 230VAC at full load
INPUTVOLTAGE RANGE          Note.7180 ~ 264VAC          254 ~ 370VDC
FREQUENCY RANGE47 ~ 63Hz
POWER FACTOR (Typ.)PF≧0.95/230VAC at full load
EFFICIENCY (Typ.)94%94%
AC CURRENT (Typ.)6A/230VAC
INRUSH CURRENT (Typ.)COLD START 50A / 230VAC
LEAKAGE CURRENT<3.5mA / 240VAC
PROTECTIONOVERLOADNormally works within 105 ~ 130% rated output power for more than 3 seconds and then shut down o/p voltage with auto-recoveryafter 30 seconds if the peak load condition is removed
Constant current limiting within 130 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage, re-poweron to recover
OVER VOLTAGE29 ~ 33V56 ~ 65V
Protection type : Shut down o/p voltage, with auto-recovery or re-power on to recover
OVER TEMPERATUREShut down o/p voltage, recovers automatically after temperature goes down
FUNCTIONDC OK REALY CONTACT RATINGS (max.)60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
CURRENT SHARINGPlease refer to function manual
ENVIRONMENTWORKING TEMP.           Note.5-30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY-40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT±0.03%/℃ (0 ~ 50℃)
VIBRATIONComponent:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY & EMC(Note 4)SAFETY STANDARDSUL508, TUV BS EN/EN62368-1, BSMI CNS14336-1, BIS IS13252(Part1) (only for 24V), AS/NZS62368.1, EAC TP TC 004 approved ; (meet BS EN/EN60204-1)
WITHSTAND VOLTAGEI/P-O/P:3KVAC   I/P-FG:2KVAC   O/P-FG:0.5KVAC   O/P-DC OK:0.5KVAC
ISOLATION RESISTANCEI/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION              Note.8Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3 Conduction class B, Radiation class A, BS EN/EN61000-3-2,-3,EAC TP TC 020, BSMI CNS13438
EMC IMMUNITYCompliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61000-6-2 (BS EN/EN50082-2), BS EN/EN61204-3,heavy industry level, EAC TP TC 020
OTHERSMTBF660.2K hrs min.        Telcordia SR-332 (Bellcore) ; 70.7K hrs min.          MIL-HDBK-217F (25℃)
DIMENSION110*125.2*150mm (W*H*D)
PACKING2.47Kg ; 6pcs/15.8Kg/1.55CUFT
NOTE1.  All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.2.  Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.3.  Tolerance : includes set up tolerance, line regulation and load regulation.4.  The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.5.  Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.6.  3 seconds peak power max. and the average output power should not exceed the rate power.7.  Derating may be needed under low input voltage. Please check the derating curve for more details.8.  Consult MEAN WELL for deployment of Radiation class B.9.  The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Mechanical Specification

Case No.214A Unit: mm
Mechanical Specification

Terminal Pin No. Assignment (TB1)

Pin No:  Assignment
1: FG
2:  ACIN
3:  ACIL

Terminal Pin No. Assignment (TB1)

Pin No:  Assignment
1: P-(Current Share)
2: P+(Current Share)
3,4: DC OK Relay Contact

Control Pin (CN205) : DINKLE ECH250R-04P or equivalent

Mating Housing: Wire Diameter DINKLE ESC250V-04P
or equivalent (Including in the single package): 0.081-0.517mm (28-20AWG

Block Diagram

PFC fosc : 65KHz
PWM fosc : 60KHz
Block Diagram

DC OK Relay Contac

Contact Close: PSU turns on / DC OK.
Contact Open: PSU turns off / DC Fail.
Contact Ratings (max.): 30V/1A resistive load.

Peak Loading

Peak Loading
Peak Loading

Derating Curve

Derating Curve

Output derating VS input voltage

Output derating VS input voltage

Function Manual

Current sharing

  1. Parallel operation is available by connecting the units shown as below (P+,P- are connected mutually in parallel).
  2. Difference of output voltages among parallel units should be less than 0.2V.
  3. The total output current must not exceed the value determined by the following equation (Output current at parallel operation)=(The rated current per unit) x (Number of unit) x 0.9.
  4. In parallel operation 4 units is the maximum, please consult the manufacture for other applications.
  5. The power supplies should be paralleled using short and large diameter wiring and then connected to the load.
  6. When in parallel operation, the minimum output load should be greater than 5% of total output load. (Min. load >5% rated current per unit x number of unit)
  7. In parallel connection, maybe only one unit (master) operate if the total output load is less than 5% of rated load condition. The other PSUs (slaves) may go into standby mode and their output LEDs & relays will not turn on.
  8. Some minor noise may be heard at light load condition under parallel operation. This is a normal phenomenon and the performance of the PSU will not be influenced.
    Function Manual
    File Name:SDR-960-SPEC 2022-11-22

GTIN CODE

MW Search: https://www.meanwell.com/serviceGTIN.aspx

Symbol

GTIN CODE
Company Logo