MEAN WELL DBU-3200 3200W Intelligent Single Output Battery Charger
Front
Back
Features
- Charger for lead-acid batteries (Gel, flooded and AGM) and Li-ion batteries (lithium iron and lithium manganese)
- Built-in default 3 stage charging curves and programmable curve
- Built-in l2C interface, PMBus protocol (Optional CANBus protocol)
- Universal AC input/ Full range
- Built-in active PFC function
- Forced air cooling by built-in thermal controlled DC fans
- Output voltage and current programmable
- Built-in OR-ing FET
- Active current sharing up to 6400W(1 + 1)
- Protections: Battery under voltage I Battery no connection / Short circuit/ Over voltage/ Over temperature
- Optional conformal coating
- 5 years warranty
Description
DBU-3200 is a 3200W single output AC/DC enclosed charger in 1 U low profile with high power density, 37W/inch3 • It is an intelligent charger that has pre-loaded programmable charging curves for different types of lead-acid and Ii-ion batteries. Output programmable function allows user to adjust the charging voltage and current via the built-in potentiometer or PM Bus protocol. Various protection mechanisms as well as the temperature compensation function are provided to assure normal and safe system operation.
Applications
- Large scale DC UPS or emergency backup system
- Marine battery charger module
- Electric scooter or vehicle charger station
- Wastewater treatment system
- Electrolysis system
GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx
Model Encoding/ Order Information
Type | Communication Protocol | Note |
Blank | PMBus protocol | In Stock |
CAN | CANBus protocol | By request |
SPECIFICATION
MODEL | DBU-3200-24 | DBU-3200-48 | |||
OUTPUT | BOOST CHARGE VOLTAGE(Vboost)(default) | 28.8V | 57.6V | ||
FLOAT CHARGE VOLTAGE(Vfloat)(default) | 27.6V | 55.2V | |||
CONSTANT CURRENT(CC)(default) | 110A | 55A | |||
VOLTAGE ADJ. RANGE | By built-in potentiometer, SVR | ||||
23.5 ~ 30V | 47.5 ~ 58.8V | ||||
RECOMMENDED BATTERY CAPACITY(AMP HOURS) Note.3 | 330 ~ 1000Ah | 180 ~ 550Ah | |||
LEAKAGE CURRENT FROM BATTERY (Typ.) | 1.5mA | ||||
INPUT | VOLTAGE RANGE Note.4 | 90 ~ 264VAC 127 – 370VDC | |||
FREQUENCY RANGE | 47 ~ 63Hz | ||||
POWER FACTOR (Typ.) | 0.97/230VAC at full load | ||||
EFFICIENCY (Typ.) | 93.5% | 94.5% | |||
AC CURRENT (Typ.) Note.4 | 17A/230VAC | ||||
INRUSH CURRENT (Typ.) | COLD START 55A/230VAC | ||||
LEAKAGE CURRENT | <2mA/ 230VAC | ||||
PROTECTION | OVER VOLTAGE | 31.5 – 37.5V | 63 – 75V | ||
Protection type: Shut down o/p voltage, re-power on to recover | |||||
OVER TEMPERATURE | Shut down o/p voltage, recovers automatically after temperature goes down | ||||
FUNCTION | OUTPUT VOLTAGE PROGRAMMABLE(PV) | Adjustment of output voltage is allowable to 75 ~ 125% of nominal output voltage. Please refer to the Function Manual. | |||
OUTPUT CURRENT PROGRAMMABLE(PC) | Adjustment of output voltage is allowable to 20 -100% of rated current. Please refer to the Function Manual. | ||||
AUXILIARY POWER | 5V@ 0.3A, tolerance ± 10%, ripple 150mVp-p , 12V@ 0.8A, tolerance ± 10%, ripple 450mVp-p | ||||
REMOTE ON-OFF CONTROL | By electrical signal or dry contact Power ON:short Power OFF:open. Please refer to the Function Manual | ||||
TEMPERATURE COMPENSATION | -3mV / °C /cell/ (12V = 6 cells; 24V = 12 ce lls ; 48V = 24 cells) | ||||
ALARM SIGNAL | Isolated signal output for T-alarm and DC-OK | ||||
ENVIRONMENT | WORKING TEMP. | -30 ~ +70″C (Refer to “Derating Curve”) | |||
WORKING HUMIDITY | 20 – 90% RH non-condensing | ||||
STORAGE TEMP., HUMIDITY | -40- +85°C, 10 – 95% RH non-condensing | ||||
TEMP. COEFFICIENT | ±0.03%/°C (0 ~ 50°C) | ||||
VIBRATION | 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes | ||||
SAFETY & EMC (Note 6) | SAFETY STANDARDS | UL62368-1, CSA C22.2 No. 62368-1, TUV BS EN/EN62368-1, EAC TP TC 004 approved | |||
WITHSTAND VOLTAGE | I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:1.5KVAC | ||||
ISOLATION RESISTANCE | I/P-0/P, I/P-FG, O/P-FG:100M Ohms/ 500VDC I 25°C! 70% RH | ||||
EMC EMISSION | Parameter | Standard | Test Level/ Note | ||
Conducted | BS EN/EN55032 (CISPR32) | Class B | |||
Radiated | BS EN/EN55032 (CISPR32) | Class A | |||
Harmonic Current | BS EN/EN61000-3-2 | Class A | |||
Voltage Flicker | BS EN/EN61000-3-3 | —– | |||
EMC IMMUNITY | BS EN/EN55035, BS EN/EN61000-6-2 | ||||
Parameter | Standard | Test Level/ Note | |||
ESD | BS EN/EN61000-4-2 | Level 3, 8KV air ; Level 2, 4KV contact | |||
Radiated | BS EN/EN61000-4-3 | Level 3 | |||
EFT/ Burst | BS EN/EN61000-4-4 | Level 3 | |||
Surge | BS EN/EN61000-4-5 | 2KV/Line-Line 4KV/Line-Earth | |||
Conducted | BS EN/EN61000-4-6 | Level 3 | |||
Magnetic Field | BS EN/EN61000-4-8 | Level 4 | |||
Voltage Dips and Interruptions | BS EN/EN61000-4-11 | >95% dip 0.5 periods, 30% dip 25 periods, >95% interruptions 250 periods | |||
OTHERS | MTBF | 494.2K hrs min. Telcordia SR-332 (Bellcore); 44.8K hrs min. MIL-HDBK-217F (25°C) | |||
DIMENSION | 325.8’107’41mm (L’W’H) | ||||
PACKING | 2.76Kg;4pcs/12Kg/O .83CUFT | ||||
NOTE |
Product Liability Disclaimer : For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx |
BLOCK DIAGRAM
DERATING CURVE
STATIC CHARACTERISTICS
FUNCTION MANUAL
- PMBus Communication Interface
DBU-3200 supports PMBus Rev. 1.1 with maximum 1 OOKHz bus speed, allowing information reading, status monitoring, output trimming, etc. For details, please refer to the Installation Manual. - Charging Curve
• By factory default, this charger performs the default curve which can be programmed via PM Bus.
•To disable/ enable the charging curve, change to a 2 stage curve, a different curve frequently used for certain types of batteries in the industry, and so on, please refer to the Installation Manual.
• To program the parameters of the charging curve, SBP-001, the smart battery charging programmer designed by MEAN WELL, and a personal computer are needed . Please contact MEAN WELL for details.
• Default 3 stage charging curve
Suitable for lead-acid batteries (flooded, Gel and AGM) and Li -ion batteries (lithium iron and lithium manganese).
Embedded 3 stage charging curvesMODEL Description Vboost Vfloat CC(defau lt) 24V Default, programmable 28.8 27.6 110A Pre-defined , gel batter 28 27.2 Pre-defined, flooded battery 28.4 26.8 Pre-defined, AGM battery 29 27 48V Default, programmable 57.6 55.2 55A Pre-defined, gel batter 56 54.4 Pre-defined, flooded battery 56.8 53.6 Pre-defined, AGM battery 58 54 Note:
When using this charger un it, please configured the system with recommended battery capacity defined by specification. Should battery capacity in use be much smaller so that user needs to set a low current for charging, under such condition it might cause higher current ripple. - Front Panel LED Indicators & Corresponding Signal at Function Pins
LED Description Green
Float (stage 3) Orange
Charging (stage 1 or stage 2) Red
The LED will present a constant red light when the abnormal status (OTP, OLP, fan fail and charging timeout) arises. Red (Flashing)
The LED will flash with the red light when the internal temperature reaches 60°C; under this condit ion , the unit st ill ope rates normally without entering OTP. (In the meantime , an alarm signa l will be sent out through the PMBus interface.) - Output Voltage Programming (or, PV / remote voltage programming I remote adjust/ margin programming I dynamic voltage trim)
* In addition to the adjustment via the built-in potentiometer, the output voltage can be trimmed by applying EXTERNAL VOLTAGE. - Output Current Programming (or, PC/ remote current programming/ dynamic current trim)
* The output current can be trimmed to 20-100% of the rated current by applying EXTERNAL VOLTAGE. - Remote ON-OFF Control
The power supply can be turned ON/OFF individually or along with other units in parallel by using the “Remote ON OFF” function.Between Remote ON-OFF and +5V-AUX Power Supply Status Switch Short ON Switch Open OFF - Temperature Compensation
• To exploit the temperature compensation function , please attach the temperature sensor, NTC, which is enclosed with the charger, to the battery or the battery’s vicinity.
• The charger is able to work normally without the NTC.
When multiple chargers are connected in parallel, please configure with the NTC as exhibited in the diagram.
If the temperature compensation is not required, RTH+ (PIN 15) and RTH- (PIN 16) from each unit sti ll need to be connected. - Alarm Signal Output
• There are 2 alarm signals, DC OK and T-ALARM , in TTL signal form, on CN1. These signals are isolated from output. The maximum sink current is 10mA. - Current Sharing
DBU-3200 has the built-in active current sharing function and can be connected in parallel, up to 2 units, to provide higher output power as exhibited below:
• The power supplies to be paralleled should use short and large diameter wiring and then connected to the load.
• Difference of output voltages among parallel units should be less than 0.2V.
• The total output current must not exceed the value calculated by the following equation: Maximum output current at parallel operation=(Rated current per unit) X (Number of unit) X 0.9
• When the total output current is less than 5% of the total rated current, or say (5% of Rated current per unit) X (Number of unit) the current shared among units may not be balanced.
• CN500/SW1 Function pin connectionParallel PSU1 PSU2 CN500 SW1 CN500 SW1 1 unit X ON – – 2 unit V ON V ON (V: CN500 connected; X: CN500 not connected.)
(Q) DA,DB and -V(signal) are connected mutually in parallel.
MECHANICAL SPECIFICATION
Mounting Instruction
Hole No. | Recommended Screw Size | MAX. Penetration Depth L | Recommended mounting torque |
1 | M3 | 4mm | 6-8Kgf-cm |
2 | M4 | 5mm | 7-10Kgf-cm |
Control Pin No. Assignment(CN 1) : HRS DF11-16DP-2DS or equivalent
Mating Housing | HRS DF11-16DS or equivalent |
Terminal | HRS DF11-“SC or equivalent |
Pin No. | Function | Description |
1 | +12V-AUX | Auxiliary voltage output. 10.6- 13.2V, referenced to GND-AUX (pin2). The maximum load current is 0.8A. This output has the built-in “Oring diodes” and is not controlled by “Remote ON-OFF”. |
2 | GND-AUX | Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -VJ. |
3 | +5V-AUX | Auxiliary voltage output, 4.5-5.5V, referenced to GND-AUX (pin2). The maximum load current is 0.3A. This output has the built-in “Oring diodes” and is not controlled by “Remote ON-OFF |
4 | Remote ON-OFF | The unit can turn the output ON/OFF by electrical signal or dry contact between Remote ON /OFF and +5V-AUX. (Note.2) Short (4.5 – 5.5V): Power ON; Open (-0.5 – 0.5V): Power OFF; The maximum input voltage is 5.5V. |
5 | DC-OK | High (3.5 – 5.5V): When the Vout ;aa 16V/32V ± 1V. Low (-0.5 – 0.5V): When Vout e”; 16V/32V ± 1V. The maximum sourcing current is 10mA and only for output. (Note.2) DC OK is associated with battery low protection. |
6 | T-ALARM | High (3.5 – 5.5V): When the internal temperature exceeds the limit of temperature alarm, or when Fan fails. Low (-0.5 – 0.5V): When the internal temperature is normal, and when Fan works normally. The maximum sourcing current is 1Om A and only for output(Note.2) |
7,8,9 | A0,A1,A2 | PMBus interface address lines. (Note.1) |
10 | DO | DIP-switch interface Iines for charging curve selection . (Note .1) |
11 | PC | Connection for output current programming. (Note.1) |
12 | PV | Connection for output voltage programming. (Note.1) |
13 | +V (Signal) | Positive output voltage signal. It cannot be connected directly to the load. |
14 | -V (Signal) | Negative output voltage signal. It is for certain function reference: it cannot be connected directly to the load. |
15 | RTH+ | Temperature sensor(NTC, 5KOhm) comes along with the charger can be connected to the unit to allow temperature compensation of the charging voltage. |
16 | RTH- |
AC Input Terminal Pin No. Assignment
Control Pin No. Assignment(CN500): HRS DF11-8DP-2DS or equivalent
Mating Housing | HRS DF11-8DS or equivalent |
Terminal | HRS DF11-“SCorequivalent |
Pin No. | Function | Description |
1, 2 | DA | Differential digital signal for parallel control. |
3, 4 | DB | Differential digital signal for parallel control. |
5, 6 | -V (Signal) | Negative output voltage signal. 11 is for local sense; and certain function reference; it cannot be connected directly to the load. |
7 | NC | For standard model: None. |
SDA | For PMBus mode l: Serial Da ta used in the PMBus interface . (Note) | |
CANH | For CANBus mode l: Data line used in CANBus interface. (Note) | |
8 | NC | For standard model: None. |
SCL | For PMBus model: Serial Clock used in the PMBus interface. (Note) | |
CANL | For CANBus mode l: Data line used in CANBus inter face. (Note) |
Note: Isolated signal, referenced to GND-AUX.
Pin No. | Function | Description |
1, 2 | Terminal resistance | SW1 is the selector of terminal resistor that is designed for DA/DB signals and parallel control function. |
INSTALLATION MANUAL
Please refer to: http://www.meanwell.com/manual.html