User Guide for SATEC models including: EM132 Multi Function Meter, EM132, Multi Function Meter, Function Meter, Meter
EM132 Cost-Effective Multi-Function Transducer - SATEC
EM132-133 QUICK START GUIDE Quick Start Guide EM132-133 BG0504 REV.A3 Mechanical Installation EM132-133 QUICK START GUIDE Figure 1: Instrument Dimensions 2 BG0504 REV.A3 Mechanical Installation EM132-133 QUICK START GUIDE Figure 2: Mounting the EM13X on DIN Rail or on flat surface Only qualified personnel can perform setup. All incoming power sources must be turned off during installation. During operation of the Powermeter, hazardous voltages are present on the input terminals. Failure to observe precautions can result in serious or even fatal injury, or damage to equipment. Please refer to the installation and operation manual for further information. BG0504 REV.A3 Typical Electrical Installation EM132-133 QUICK START GUIDE Figure 3:Common Wiring Mode: 4LL3 or 4Ln3 Wiring Configuration 3-wire 2-element Direct connection using 2 CTs 4-wire Wye 3-element direct connection using 3 CTs 4-wire Wye 3-element connection using 3 PTs, 3 CTs 3-wire 2-element Open Delta connection using 2 PTs, 2 CTs 4-wire Wye 2½ -element connection using 2 PTs, 3 CTs 3-wire 2½ -element Open Delta connection using 2 PTs, 3 CTs 4-wire 3-element Delta direct connection using 3 CTs 3-wire 2½-element Broken Delta connection using 2 PTs, 3 CTs Setup Code 3dir2 4Ln3 or 4LL3 4Ln3 or 4LL3 3OP2 3Ln3 or 3LL3 3OP3 4Ln3 or 4LL3 3bLn3 or 3bLL3 NOTE: Refer to the Installation and operation manual for the wiring schematics diagrams 4 BG0504 REV.A3 Electrical Installation EM132-133 QUICK START GUIDE Figure 4: CT Wiring options BG0504 REV.A3 5 MODULE Installation This section applies to the I/O and Communication modules. EM132-133 QUICK START GUIDE MODULE 4DI/2DO MODULE ETHERNET Figure 5: PM130 PLUS modules MODULE 4 ANALOG OUT Module Connector Cover Remove Module Connector Cover before assembling module NOTE: Refer to the Installation and operation manual for the wiring schematics diagrams and setup parameters Module Connector Figure 6: Mounting module Before I/O Module installation ensure that all incoming power sources are shut OFF. Failure to observe this practice can result in serious or even fatal injury and damage to equipment. 6 BG0504 REV.A3 EM132-133 QUICK START GUIDE Basic Setup All setups can be performed directly from the display panel or via communication ports using PAS communication software, except for Communications and Display setups, which must be performed directly at the instrument panel. · Press for 5sec, until password no. blinks: · Enter Password number using , then press then new display with blinking "Reset" for 2sec · Navigate by pressing shortly (less than 1sec) to move to Basic setup · Press for 2sec, until "Conf" blinks: · Navigate by pressing shortly (less than 1sec) to move to CT setup · Press for 2sec, until "5000" blinks, then press shortly using to the desired value · Press for 2sec, until "CT" blinks, then press for 2sec, until "Basic" blinks, then press for 2sec, until "Reset" blinks, press shortly using to initial screen to move to blinking "Exit" and press for 2sec to return BG0504 REV.A3 7 DATA DISPLAY EM132-133 QUICK START GUIDE Navigating in Display Mode The front panel has a simple interface that allows you to display numerous measurement parameters in up to 38 display pages. For easier reading, the parameters are divided into three groups; each group is accessible by pressing the key and each group page is accessible by pressing the key. The initial display is as described below: First push on will display Energy measurement parameters, by pushing exp. active/reactive, etc ...as described below: will navigate to imp., Second push on will display MAX DMD parameters, by pushing Q, S, I, etc ...as described below: will navigate to MAX DMD P, Third push on will display Votage/Current measurements, by pushing V (L-L), I, Power, PF, THD, TDD, F, etc ...as described below: will navigate to V (L-N), 8 BG0504 REV.A3 Basic Menu EM132-133 QUICK START GUIDE Code ConF Pt Ratio Pt Factor Ct PowDmdPer Num.Per. ADmdPer. Frequency MaxDmdLd Parameter Wiring mode PT ratio Options 3OP2 4Ln3 3dir2 4LL3 3OP3 3Ln3 3LL3 3bLn3 3bLL3 1.0 - 6,500.0 Description 3-wire open delta using 2 CTs 4-wire Wye using 3 PTs (default) 3-wire direct connection using 2 CTs 4-wire Wye using 3 PTs 3-wire open delta using 3 CTs 4-wire Wye using 2 PTs 4-wire Wye using 2 PTs 3-wire Broken delta using 2 PTs, 3 CTs 3-wire Broken delta using 2 PTs, 3 CTs The potential transformer ratio CT primary current Power demand period Number of power demand periods Ampere/Volt demand period Nominal frequency 1-50,000A (5*) 1, 2, 5, 10, 15*, 20, 30, 60, E 1-15 (1*) 0-1800 (900*) 25, 50, 60, 400 (Hz) The primary rating of the current transformer The length of the period for power demand calculations, in minutes. E = external synchronization The number of demand periods to be averaged for sliding window demands 1 = block interval demand calculation The length of the period for volt/ampere demand calculations, in seconds. 0 = measuring peak current The nominal power utility frequency - Default setup Communication Port Menu COM1 setting Code Protocol Interface Address Baud Rate Data/Party Snd.Delay Parameter Communications protocol Interface standard Address Baud rate Data format Options Description ASCII, rtu, dnP3 ASCII, Modbus RTU (default) or DNP3.0 protocol 485 RS-485 interface (default) ASCII: 0 (default) - 99, Modbus: 1 (default) -247, DNP3.0: 0 (default) -255 110, 300, 600, 1200, 2400, 4800, 9600 (default), up to 115,200 bps 7E, 8E (7/8 bits, even parity), 8n (default) (8 bits, no parity) BG0504 REV.A3 9 Input and Output Ratings EM132-133 QUICK START GUIDE 3 voltage inputs 3 current nputs (Galvanic isolation) Communication port COM1 Communication port COM3 Power Supply (Galvanically isolated) MODULE 2DI/DO MODULE 4DI/2DO (Optional) MODULE 4 AO (Optional) Communication port COM2 (Optional) Communication port COM2 (Optional) Communication port COM2 (Optional) 57/98-400/690 VAC Voltage input terminals /5A(10A) /1A(2A) 50A(100A) 40mA:(optional) Current input terminals EIA RS-485 standard COM1 terminals DIRECT INPUT - Nominal: 690V line-to-line voltage, 828V maximum; 400V line-to-neutral, 480V maximum - Burden: <0.5 VA. INPUT USING PT - Burden: <0.15 VA 4 x Maximum wire section: 2.5 mm² (12 AWG) INPUT VIA CT with 5A secondary output - Burden: <0.2VA, Overload withstands: 20A RMS continuous, 300A RMS for 0.5 second. INPUT VIA CT with 1A secondary output - Burden: <0.05VA, Overload withstands: 3A RMS continuous, 80A RMS for 0.5 second. INPUT VIA CT with 50A direct connection - Burden: < 0.05VA, Overload withstands: 120A RMS continuous, 2000A RMS for 0.5 second. INPUT VIA CT with 40mA secondary output, using external CT Split Core CT or Solid Core CT primary 100-1200A maximum rating 3 x Maximum wire section: 16 mm² Optically isolated, max. speed 115.2Kb/s 3 x Maximum wire section: 2.5 mm² IR COM port Infra Red, max. speed 38.4Kb/s 40-300V AC/DC (standard) Power Supply input terminals DIGITAL INPUT x 2 optically isolated inputs DIGITAL OUTPUT x 1 2DI/DO terminals DIGITAL INPUT x 2 optically isolated inputs DIGITAL EMR OUTPUT x 2 SSR 4DI/2DO terminals ANALOG OUT x 4 optically isolated outputs (4 different options) 4 AO terminals Ethernet ETH connector Profibus Profibus terminals EIA RS-232-422/485 standard COM2 terminals 50/60 Hz - 9VA 3 x Maximum wire section: 2.5 mm² Dry contact, internally wetted @ 5VDC 0.15A/250 VAC - 400 VDC, 1 contact (SPST Form A) 5 x Maximum wire section: 2.5 mm² Dry contact, internally wetted @ 24VDC 5A/250 VAC; 5A/30 VDC, 1 contact (SPST Form A) 0.15A/250 VAC - 400 VDC, 1 contact (SPST Form A) 9 x Maximum wire section: 2.5 mm² ±1 mA, maximum load 5 k (100% overload) 0-20 mA, maximum load 510 4-20 mA, maximum load 510 0-1 mA, maximum load 5 k (100% overload) 5 x Maximum wire section: 2.5 mm² 10/100 Base T, auto adaptation speed, Max. speed 100Mb/s Shielded RJ45 cable Max. speed 12 Mb/s 5 x Maximum wire section: 2.5 mm2 (12 AWG) or using terminal to DB9 converter: P/N AC0153 REV.A2 Optically isolated, max. speed 115.2Kb/s to be connected to GPRS modem if ordered 5 x Maximum wire section: 2.5 mm² And DB9 connector 10 BG0504 REV.A3Dany Shacked Adobe PDF Library 19.10.123