[PDF] SUBMITTAL DATA SHEET - Johnson Controls

FEATURES. • MEETS OR EXCEEDS ASHRAE 90.1-2013 / MEETS EPACT 2010. EFFICIENCY*. • SMART EQUIPMENT™ W/COMMUNICATION BACNET MS/TP.

PDF preview unavailable. Download the PDF instead.

506413-ysd-j-0419
SUBMITTAL DATA SHEET
SPLIT-SYSTEM AIR CONDITIONING CONDENSING UNITS 7.5 - 25 TONS MODELS: YC090 through 300 and YE090, 2-PIPE
YD120 through 240, 4-PIPE

JOB NAME: PURCHASER: ENGINEER: SUBMITTED TO: SUBMITTED BY: UNIT DESIGNATION:

FOR:

REF:

LOCATION: ORDER NO:
APPROVAL: DATE: SCHEDULE NO.

CONSTRUCTION: MODEL NO.

_
COOLING PERFORMANCE
TOTAL CAPACITY- - - - - - - - - - - - - - _____ MBH OUTDOOR DESIGN TMP. - - - - - - - - - - _____ °F SUCTION PRESSURE AT SATURATION - - - - - - - - - - - - - - - - - _____ PSIG SUCTION TEMPERATURE AT SATURATION - - - - - - - - - - - - - - - - - - - _____ °F
ELECTRICAL DATA
POWER SUPPLY - - - - - - - - - _____/_____/_____ TOTAL UNIT AMPACITY - - - - - - - - _____ AMPS POWER INPUT REQ. - - - - - - - - - - - - - _____ KW MINIMUM WIRE SIZE - - - - - - - - - - - - _____ AWG (COPPER CONDUCTORS) MAXIMUM FUSE SIZE - - - - - - - - - - _____ AMPS (DUAL ELEMENT)
UNIT WEIGHT
TOTAL OPERATING WEIGHT - - - - - _____ LBS

FEATURES
· MEETS OR EXCEEDS ASHRAE 90.1-2013 / MEETS EPACT 2010 EFFICIENCY*
· SMART EQUIPMENTTM W/COMMUNICATION BACNET MS/TP (PROGRAMMABLE TO MODBUS OR N2 PROTOCOLS)
· R-410A REFRIGERANT · POWDER PAINT FOR DURABILITY · WEATHERIZED CASING FOR OUTDOOR USE · PROPELLER-TYPE CONDENSER FANS · INHERENTLY PROTECTED FAN MOTORS · HIGH AND LOW PRESSURE SAFETIES · SCROLL COMPRESSORS · CRANKCASE HEATERS · ALUMINUM TUBE/ALUMINUM FIN "MICROCHANNEL" COILS · BACKSEATING SUCTION AND LIQUID LINE SERVICE VALVES · SINGLE AND DUAL REFRIGERATION CIRCUITS
(SINGLE ON YC AND DUAL ON YD MODELS) · LOW AMBIENT TO 40°F - LOW AMBIENT AVAILABLE TO 0°F · PROVISIONS FOR HOT GAS BYPASS · CSA APPROVAL · ONE YEAR LIMITED PARTS WARRANTY ON COMPLETE UNIT · FIVE YEAR LIMITED COMPRESSOR WARRANTY · LIQUID LINE DRIERS (SUPPLIED FOR FIELD INSTALLATION) · FACTORY INSTALLED DISCONNECT OPTION · FACTORY INSTALLED POWERED OR NON-POWERED 120V OUT-
LET OPTION · FULL PERIMETER BASE RAIL-FORK TRUCK ACCESSIBLE · CRANE RIGGING PROVISIONS

*WHEN COUPLED WITH MATCHING INDOOR UNIT

YC090, YE090, YC120, YD120, YC150, YD150
Johnson Controls Ducted Systems

YC180, YD180, YC240, YD240, YC300
506413-YSD-J-0419

506413-YSD-J-0419

WEIGHT DISTRIBUTION

CORNER WEIGHTS & CENTER OF GRAVITY

Size (Tons)
090 (7.5) 120 (10) 150 (12.5) 180 (15) 240 (20) 300 (25)

Model
YC090 YE090 YC120 YD120 YC150 YD150 YC180 YD180 YC240 YD240
YC300

Weight (lbs.)

Shipping

Operating

390

387

386

383

499

497

493

490

499

497

493

490

914

909

899

894

945

942

930

927

945

942

Center of Gravity (in.)

X

Y

17

32.3

18

33.5

17.3

32.3

17.4

32.5

17

32.3

17.4

32.5

32.5

31.5

32.5

31.5

30.3

31.0

32.7

31.8

30.3

31.0

4 Point Load Location (lbs.)

A

B

C

D

99

113

94

82

95.0

124.3

92.8

70.9

124

147

122

103

123

147

120

100

127

145

120

105

123

147

120

100

239

246

215

209

235

242

212

206

261

234

212

236

244

255

218

210

261

234

212

236

LEFT

D

DIM X

CG

FRONT WIDTH

C

DIM Y

LENGTH

RIGHT
YC090, YE090, YC120, YD120, YC150, YD150

D

A

DIM X

REAR FRONT
B
WIDTH

LEFT
CG

C

DIM Y

LENGTH

RIGHT
YC180, YD180, YC240, YD240,
YC300

A
REAR
B

2

Johnson Controls Ducted Systems

31.90

UNIT DIMENSIONS YC090, YE090, YC/YD120, YC/YD150
RIGHT
REAR
LEFT 59.10

506413-YSD-J-0419
FRONT

1.33 2.097

BASE RAIL DETAIL
2.375
TOP

BOTTOM 2.923 3.563

3.43

3.75

7.000

10.000 24.000 31.758
FRONT

7.000

CONVENIENCE OUTLET
A 2X (Ø 1.375)
30.994 KNOCKOUT
12.126 9.876 4.751 3.883 3.664 2.933 1.664

SYSTEM 2

2X (Ø 0.875) KNOCKOUT

7.000

23.000 37.000
58.500 RIGHT

7.000

SYSTEM 1

15.53 12.70

REAR

6.26 7.52 8.98 10.60

2X (Ø 1.375) KNOCKOUT
LEFT

2X (Ø 0.875) KNOCKOUT
12.000 10.000 4.875
4.132 2.382 1.882

*See UNIT HEIGHT DIMENSIONS, PIPING AND ELECTRICAL CONNECTIONS SIZES (next page)

Johnson Controls Ducted Systems

3

506413-YSD-J-0419

UNIT HEIGHT DIMENSIONS (INCHES)

MODEL

A

YC090

44.5

YE090

44.5

YC120

50.0

YD120

50.0

YC150

50.0

YD150

50.0

PIPING AND ELECTRICAL CONNECTIONS SIZES (INCHES)

MODEL

YC090 YE090 YC120 YD120 YC150 YD150

No. refrigeration circuits 1

1

1

2

1

2

Suction line OD (in.)

1 1/8 1 1/8 1 3/8 1 1/8 1 3/8 1 1/8

Liquid line OD (in.)

5/8 5/8

7/8

5/8

7/8

5/8

Power wiring knockout 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8

Control wiring knockout 7/8 7/8

7/8

7/8

7/8

7/8

4

Johnson Controls Ducted Systems

UNIT DIMENSIONS YC/YD180, YC/YD240 & YC300
REAR

506413-YSD-J-0419

LEFT

RIGHT

59.10

FRONT 64.10

1.33 2.097

BASE RAIL DETAIL
2.375
TOP

SYSTEM 2 SYSTEM 1

BOTTOM 2.923 3.563

3.43

3.75

7.000

23.000 37.000 64.000
FRONT

7.000

A
30.994
11.375 9.125 4.750 4.132 3.913 3.181 1.913

2X (Ø 1.375) KNOCKOUT
2X (Ø 0.875) KNOCKOUT

7.000

23.000 37.000
59.000
RIGHT

7.000

SYSTEM 2 SYSTEM 1

16.133 13.133

17.367 18.867
20.617 22.617

FRONT (PIPING DETAIL)

*See UNIT HEIGHT DIMENSIONS, PIPING AND ELECTRICAL CONNECTIONS SIZES (next page)

Johnson Controls Ducted Systems

5

UNIT HEIGHT DIMENSIONS (INCHES)

MODEL

A

YC180

44.5

YD180

44.5

YC240

50.0

YD240

50.0

YC300

50.0

PIPING AND ELECTRICAL CONNECTIONS SIZES (INCHES)

MODEL

YC180 YD180 YC240 YD240 YC300

No. Refrigeration Circuits

1

2

1

2

1

Suction Line OD (in.)

1 5/8 1 1/8 1 5/8 1 3/8 2 1/8

Liquid Line OD (in.)

7/8

5/8

7/8

5/8

7/8

Power Wiring Knockout

1 3/8 1 3/8 1 3/8 1 3/8 1 3/8

Control Wiring Knockout

7/8

7/8

7/8

7/8

7/8

MINIMUM CLEARANCES

CLEARANCE DESCRIPTION

DISTANCE IN INCHES

Overhead (Top)

120

Front

36

Rear

24

Left Side

30

Right Side

30

Bottom1

0

1. In all installations where snow accumulates and winter operation is expected, additional height must be provided to insure normal condenser airflow.
FACTORY-INSTALLED OPTIONS
DISCONNECT - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  NON-POWERED CONV. OUTLET - - - - - - - - - - - - - - - -  POWERED CONV. OUTLET - - - - - - - - - - - - - - - - - - - -  PHASE MONITOR - - - - - - - - - - - - - - - - - - - - - - - - - - -  COIL GUARD - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  LOW AMBIENT TO 0° - - - - - - - - - - - - - - - - - - - - - - - - -  TECHNICOATED COIL - - - - - - - - - - - - - - - - - - - - - - - -  E-COAT COIL - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 

FIELD-INSTALLED ACCESSORIES
COIL GUARD - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  HAIL GUARD - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  LOW AMBIENT KIT - - - - - - - - - - - - - - - - - - - - - - - - - - -  HOT GAS BYPASS KIT- - - - - - - - - - - - - - - - - - - - - - - - 
MATCHING AIR SIDE EQUIPMENT DATA
MODEL NUMBER _______________________________ SUBMITTAL FORM NUMBER ______________________

REFER TO UNIT TECHNICAL GUIDE FOR THE LIST OF STANDARD FEATURES ATTACHED NOT ATTACHED 

NOTES: ____________________________________________________________________________________________________ ____________________________________________________________________________________________________ ____________________________________________________________________________________________________ ____________________________________________________________________________________________________ ____________________________________________________________________________________________________

Subject to change without notice. Printed in U.S.A. Copyright © 2019 by Johnson Controls, Inc. All rights reserved.
York International Corporation 5005 York Drive
Norman, OK 73069

506413-YSD-J-0419 Supersedes: 506413-YSD-I-0218


FrameMaker 2017 Acrobat Distiller 11.0 (Windows)